Wiring Inspection

Table 5 Table 310-16, National Electrical Code (Reprint)

Allowable Ampacities of Insulated Conductors Rated 0-2000 Volts, 60° to 90°C (140° to 194°F) 1

Not More Than Three Conductors in Raceway or Cable or Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F)

SIZE

 

TEMPERATURE RATING OF CONDUCTOR. SEE TABLE 310-13.

SIZE

 

 

 

 

 

 

 

 

 

 

 

60°C

75°C

 

90°C

60°C

75°C

 

90°C

 

 

(140°F)

(167°F)

 

(194°F)

(140°F)

(167°F)

 

(194°F)

 

 

TYPES

TYPES

 

TYPES

TYPES

TYPES

 

TYPES

 

 

TW=

FEPW=,

 

TBS, SA,

TW=

RH=, RHW=,

 

TBS,

 

 

UF=

RH, RHW=,

 

SIS, FEP=

UF=

THHW=,

 

SA, SIS,

 

 

 

THHW=,

 

FEPB=, MI,

 

THW=,

 

THHN=,

 

 

 

THW=,

 

RHH= RHW-2

 

THWN=,

 

THHW=,

 

 

 

THWN=,

 

THHN=, THHW=,

 

XHHW=,

 

THW-2, THWN-2,

 

 

 

XHHW=,

 

THW-2, THWN-2,

 

USE=

 

RHH==, RHW-2,

 

 

 

USE=, ZW=

 

USE-2, XHH,

 

 

 

USE-2,

 

 

 

 

 

XHHW=

 

 

 

XHH, XHHW=,

 

AWG

 

 

 

XHHW-2, ZW-2

 

 

 

XHHW-2, ZW-2

AWG

 

COPPER

 

ALUMINUM OR COPPER-CLAD ALUMINUM

kcmil

 

 

kcmil

18

.......

.......

 

14

.......

.......

 

.......

.......

16

.......

.......

 

18

.......

.......

 

.......

.......

14*

20

20

 

25

.......

.......

 

.......

.......

12*

25

25

 

30

20

20

 

25

12*

10*

30

35

 

40

25

30

 

35

10*

8

40

50

 

55

30

40

 

45

8*

6

55

65

 

75

40

50

 

60

6

4

70

85

 

95

55

65

 

75

4

3

85

100

 

110

65

75

 

85

3

2

95

115

 

130

75

90

 

100

2

1

110

130

 

150

85

100

 

115

1

1/0

125

150

 

170

100

120

 

135

1/0

2/0

145

175

 

195

115

135

 

150

2/0

3/0

165

200

 

225

130

155

 

175

3/0

4/0

195

230

 

260

150

180

 

205

4/0

250

215

255

 

290

170

205

 

230

250

300

240

285

 

320

190

230

 

255

300

350

260

310

 

350

210

250

 

280

350

400

280

335

 

380

225

270

 

305

400

500

320

380

 

430

260

310

 

350

500

600

355

420

 

475

285

340

 

385

600

700

385

460

 

520

310

375

 

420

700

750

400

475

 

535

320

385

 

435

750

800

410

490

 

555

330

395

 

450

800

900

435

520

 

585

355

425

 

480

900

1000

455

545

 

615

375

445

 

500

1000

1250

495

590

 

665

405

485

 

545

1250

1500

520

625

 

705

435

520

 

585

1500

1750

545

650

 

735

455

545

 

615

1750

2000

560

665

 

750

470

560

 

630

2000

 

 

 

 

CORRECTION FACTORS

 

 

 

 

 

 

 

 

 

 

Ambient

For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities

Ambient

Temp °C

 

shown above by the appropriate factor shown below.

 

Temp °F

21-25

1.08

1.05

 

1.04

1.08

1.05

 

1.04

70-77

26-30

1.00

1.00

 

1.00

1.00

1.00

 

1.00

78-86

31-35

.91

.94

 

.96

.91

.94

 

.96

87-95

36-40

.82

.88

 

.91

.82

.88

 

.91

96-104

41-45

.71

.82

 

.87

.71

.82

 

.87

105-113

46-50

.58

.75

 

.82

.58

.75

 

.82

114-122

51-55

.41

.67

 

.76

.41

.67

 

.76

123-131

56-60

.......

.58

 

.71

.......

.58

 

.71

132-140

61-70

.......

.33

 

.58

.......

.33

 

.58

141-158

71-80

.......

.......

 

.41

.......

.......

 

.41

159-176

*Unless otherwise specifically permitted in Section 240-3 of this Code, the overcurrent protection for conductor types marked with an asterisk (*) shall not exceed 15 amperes for No. 14, 20 amperes for No. 12, and 30 amperes for No. 10 copper; or 15 amperes for No. 12 and 25 amperes for No. 10 aluminum and copper-clad aluminum after any correction factors for ambient temperature and number of conductors have been applied.

1.Reprinted with permission from NEC 1999, NFPA 70, the National Electrical Code®, Copyright 1998, National Fire Protection Association, Quincy, MA 02269. This reprinted material is not the complete and official position of the National Fire Protection Association, on the referenced subject which is represented only by the standard in its entirety.

30

Image 36
Contents Liebert Series 610 UPS Battery Cabinet Precautions Contacting Liebert for SupportTable of Contents Figures Iii Tables Important Safety Instructions Page Installation Considerations Multi-Module 500 to 750kVA UPS Types of System Control Cabinets System Control CabinetsUnloading and Handling External Inspections Internal Inspections and Shipping Material RemovalInspections Equipment Location Battery Safety Precautions Battery InstallationBattery Safety Precautions in French Per CSA Requirements AvertissementBattery Cabinets Open-Rack Batteries Configuring Your Neutral and Ground Connections Preferred Grounding Configuration, Wye-Connected Service Preferred grounding configuration, wye-connected serviceAlternate Grounding Configuration, Wye-Connected Service Alternate grounding configuration, wye-connected servicePreferred Grounding Configuration With Isolated Bypass Preferred grounding configuration with isolated bypassAlternate Grounding Configuration, Non-Isolated Alternate grounding configuration, non-isolatedConfiguring Your Neutral and Ground Connections Preferred grounding configuration, impedance-grounded wye Preferred Grounding Configuration, Battery Systems Preferred grounding configuration, battery systemsWiring Considerations Power Wiring Scct Control Wiring Abbreviations for circuit breakersBattery Wiring Wiring Connections Specific ConnectionsWiring Connections Wiring Inspection Power wiring terminals, factory suppliedField-supplied lugs 16, National Electrical Code Reprint Installation Drawings 97-797600-176 Rev 88-797658-84 Rev 88-797658-94 Rev 88-797657-26 Rev 88-797657-95 Rev Outline drawing, 500kVA Multi-Module UPS, 12-pulse rectifier 88-797657-92 Rev 88-797668-84 Rev 88-797668-90 Rev 88-797665-29 Rev 88-797665-90 Rev 88-797656-66 Rev 88-797656-86 Rev 88-797668-66 Rev 88-797668-86 Rev 88-797664-68 Rev 88-797664-88 Rev 88-797677-65 Rev Base mounting patterns, 500kVA module, 6-pulse rectifier Base mounting patterns, 500kVA module, 12-pulse rectifier 88-797613-28 Rev Base mounting patterns, 625-750kVA module, 6-pulse rectifier 88-797613-29 Rev 88-797613-19 Rev 88-797613-27 Rev Shipping split detail, 500kVA, 12-pulse rectifier 88-797612-08 Rev Shipping split detail, 625-750kVA, 6-pulse rectifier 88-797612-09 Rev Shipping split detail, 625-750kVA, 12-pulse rectifier 88-797612-07 Rev Battery power pack system Battery power pack, Size a 88-797607-63 Rev Outline drawing, System Control Cabinet SCCT, 200-1200A 88-797613-71 Rev Outline drawing, System Control Cabinet SCCT, 1600-2000A 88-797613-78 Rev Outline drawing, System Control Cabinet SCCT, 2500-3000A 88-797613-73 Rev Outline drawing, System Control Cabinet SCCT, 4000A Base mounting patterns, System Control Cabinet SCCT, 4000A 96-797619-58A Rev 96-797619-66A Rev Control connection location diagram, Scct 96-797619-51A Rev 96-797619-60 Rev 96-797619-19A Rev 96-797619-20 Rev 96-797619-21 Rev 96-797619-130 Rev 96-797619-28 Rev 96-797619-128 Rev 96-797619-62 Rev 96-797619-90 Rev 96-797619-91 Rev 96-797619-52A Rev 96-797619-53A Rev 96-797619-54A Rev 96-797619-55A Rev 96-797619-56A Rev 96-797619-57A Rev 88-797616-09 Rev 88-797616-13 Rev 88-797616-07 Rev Outline drawing, remote status panel, surface mount Installation Drawings Data, Series 610, 500-750kVA, Multi-Module Systems Site planning data-600V input Site planning data-480V input System Control Cabinets Page Page Page Environmental Systems 800-543-2778 Outside the United States