Configuring Your Neutral and Ground Connections
6.2Alternate Grounding Configuration, Wye-Connected  Service
This configuration must NOT be used when 
The alternate configuration is similar to that shown in 6.1 - Preferred Grounding Configuration, 
Please note that this configuration represents a price/performance 
Proper adjustment of ground fault interrupters is necessary to avoid unwanted tripping.
Figure 5 Alternate grounding configuration, wye-connected  service
This configuration is reserved for applications that meet all the following criteria:
• The facility has 
• The module rectifier input and bypass input are fed from the same source.
• The connected load is strictly 
• Special precautions are taken to prevent tripping the ground fault interrupters. The time delay should be set to at least 0.2 seconds to prevent tripping when the UPS performs a trans- fer or retransfer operation.
! CAUTION
Failure to properly set the ground fault interrupters could cause loss of power to the critical load.
15