Emerson Series 600, SERIES 600T user manual Charge Mode, Ready Mode, Voltage ≥ Vcharge

Page 59

System Overview

5.3.4CHARGE Mode

To charge the Liebert FS, the Liebert FS will draw power from the UPS DC bus to accelerate the fly- wheel (as long as the UPS DC bus voltage is higher than Vcharge). In this mode, the Liebert FS State of Charge (SOC) will progressively increase from 0% to 100%.

Figure 48 CHARGE mode diagram

 

State of Charge < 0

State of Charge > 0

0%

Note: UPS DC Bus Voltage Vcharge

99

1

 

00%

.

5%

The Liebert FS will be in CHARGE mode as long as:

Liebert FS’s SOC is between 0% and 100% and

UPS DC Bus Voltage Vcharge.

NOTE

While in CHARGE mode, the Liebert FS will be capable of supporting the UPS DC bus.

5.3.5READY Mode

When the SOC reaches 100%, the unit will automatically transition into the READY mode. This is the mode in which the Liebert FS will spend most of its operating time. In this mode, the Liebert FS maintains its State Of Charge greater than 99.5%. The Liebert FS’s SOC will be allowed to drift down to SOC = 99.5%, at which point it will transition back into CHARGE mode and charge back up to READY mode and SOC = 100%. During normal operation, the Liebert FS will continue to automati- cally transition between the READY and CHARGE modes to maintain a SOC between 99.5 and 100% until either a DISCHARGE or SHUTDOWN is initiated.

Figure 49 READY mode diagram

State of Charge < 0

State of Charge > 0

Note: UPS DC Bus

Voltage Vcharge

0%

99

1

 

00%

.

5%

The Liebert FS will be in READY mode as long as:

Liebert FS’s SOC is between 99.5% and 100% and

UPS DC Bus Voltage Vcharge.

NOTE

While in READY mode—just as in CHARGE mode—the Liebert FS will be capable of supporting the UPS DC bus.

47

Image 59
Contents Liebert FS DC Energy Storage System Page Table of Contents Operation System OverviewTroubleshooting MaintenanceAppendix B.0 Data Collection Module Appendix A.0 UPS Interconnection KitsAppendix C.0 Versatile Interface Board Appendix D.0 Installation DrawingsAppendix E.0 Specifications Appendix F.0 Auxiliary Backup AC Power SupplyFigures Vii Versatile Interface Board mounted in the Liebert FS 110 Tables Page Important Safety Instructions Safety Precautions System information Safety ConsiderationsGeneral Information Requesting Assistance from LiebertLiebert FS General System DescriptionLiebert FS Unit 1 Liebert FS Unit Utility PowerDC Bus Loads Liebert FS UnitLiebert Battery NGeneral Specifications General system specificationsApplicable Standards and Certification Features and BenefitsKey Technological Features Key Customer BenefitsKW-sec delivered GT model, 510 VDC, with filter Rectifier Utility Static SwitchBypass Environmental Considerations System LocationElectrical Considerations Flooring RequirementsRemote Monitoring Connections-Optional AC Power ConnectionsStatus/Control Connections Grounding Connections14623 Inspection Before Removal From the TruckUnloading Unpacking HandlingRemoving the metal support plates Lifting the Liebert FS cabinetManuals Serial Number Model Number Plates Storing the Liebert FS for Delayed InstallationPositioning the Liebert FS Moving the Liebert FSFront Right Side 12-100120-09 TopBottom Front Right Side Door open Panel removed Internal layoutFloor Mounting Bracket Cabinet Floor MountingFront of Liebert FS Mounting ToolsConcrete, Masonry or Stone Floor Mounting Instructions Checking hole depth 12.7mm Floor to Flange Bolt securing bracket to cabinetBubble level Mounting front bolts-front side of cabinetWood Floor Mounting Instructions Wood Floor MountingWood Floor Mounting Parts Wood Floor Mounting ToolsRaised Floor Mounting Instructions Raised Floor Mounting Raised Floor Mounting KitRaised Floor Mounting Tools Rear Wiring ConnectionsGeneral Wiring Considerations FrontCircuit Breaker Mounting Plate Control DC and Ground Connections Communication Access PanelPounds Ground Wire Gauge Tightening Torque Approximate metric InchGround Connections Tightening torque for ground connectionService panel location AC Auxiliary Control Power Supply ConnectionsTerminal Neutral Line Ground Fused disconnectRemote monitoring DCM connections inside cabinet front door Startup ConsiderationsLiebert FS front view Detailed System DescriptionUPS Interconnection Kit Power Conversion ModuleSystem Module Description Control PanelSystem Performance Power SystemElectrical system schematic Flywheel Module Battery InputVersatile Interface Board VIB User interfaces Control PanelData Collection Module DCM Igbt Power Conversion Module PCM Active Magnetic Levitation Hardware Magnetic Levitation Module MLMUpper Radial Axial ElectromagnetMotor Generator Rotor/Flywheel-Rotating GroupVacuum system operation Vacuum SystemFlywheel Sensors Speed TemperatureCabinet System SafetyOuter Housing Rotating Group Inner Housing Coolant List of System User-Configurable Parameters Max Charge Current Voltage Behavior Current Sink Regulation Voltage Delta During Discharge Vreg DeltaVreg delta help screen Modes of OperationUPS DC Bus Voltage = Vcharge OFF ModeStandby Mode Startup ModeVoltage ≥ Vcharge Charge ModeReady Mode Following a Liebert FS Discharge Down to SOC = 0% Discharge ModeShutdown Mode Fault Mode Following a User CommandCoast Mode Typical operation modes KEY # Mode DescriptionMaintenance and Reliability Operator Controls Access System HistoryControl panel keyboard layout refer to Figure System Status IndicatorsSystem Mode Indicators Control PanelMain screen function descriptions Operation modes System Mode IndicatorsSystem Status Indicators System status indicatorsOperative DisabledUninstalled Other Status IndicatorsMenu Tree and Navigation Security AccessMenu tree Navigation and Operation of Control Panel System Setup and Parameter Access2VREG Time/Date ViewHistory TemperaturesVoltages 03 02/24/05 0403 W 12301 03/10/05 1143 W 02 03/10/05 1037 WOptions 192.168.1.1 Network-Requires DCM Option192.168.1.155 255.255.255.0Security ElectricalVitals Change password Password screens001 FM S/N MLM S/N 0001 PCM S/N 0002 SO# 123-456-7 AboutTools Copyright Appl PRI-3.00 SEC-3.01 BL PRI-3.02 SEC-3.01Inspection before Initial System Startup Initial System Startup ProcedureSystem Startup Software versions Control Parameters Setup at Initial System StartupControl Parameter Value Default Control parametersInspection Before Regular Startup Regular Startup ProcedurePowering Up the Liebert FS Booting UpLiebert FS Startup Sequence Shutdown ProcedureValidation of Control Parameters Setup Initiating Liebert FS Startup SequenceSafety Precautions Routine Maintenance Liebert Global ServicesFrequency Maintenance ScheduleMaintenance schedule Record LogDetecting Trouble Torque specifications unless otherwise labeledOptional Air Filters Torque RequirementsLimited Life Components Reporting a ProblemCorrective Actions Recommended Test EquipmentUser level menu GeneralButton F5 ChargeAuxpower Meaning / Possible Causes Troubleshooting LabelMore information Fault Clear Button F3 Button F5 FaultsBus Power BUS Current Offset Faults-causes and responsesTroubleshooting Fault Label Troubleshooting Action Liebert FS Model # Use With Liebert UPS Appendix A.1 Wiring ConnectionsAppendix A.1.1 General Wiring Considerations Key to UPS model interconnectionTop view of Liebert FS Cabinet with UPS interconnection kit Front RearLiebert FS Positive Terminal Negative Appendix A.1.2 DC Power ConnectionsCircuit Breaker Torque UPS Output Rating KVA Liebert Series 610/600T/600 model ratingsYellow Blue Two rows Row for Liebert FS Software Control Parameter Setting Liebert FS Software Control Parameter settingsRating Liebert Npower model ratingsLiebert FS Npower UPS OutputSee Table Liebert FS Software Setting Control ParameterLiebert FS Software Control Parameters UPS Interconnection Kits Liebert Series 300 UPS List of Liebert Series 300 models ratingsLiebert Series 300 status/control terminal block wiring 395VDC Liebert HiPulse model ratings Appendix A.5.1 Description-HiPulse UPS Interconnection KitLiebert FS positive terminal Liebert FS negative terminal Appendix A.5.3 IKIT-A05 DC Power ConnectionsUPS Output Rating kVA 120 Appendix A.5.5 Single Liebert FS on UPS DC BusMultiple Liebert FS Parallel Operation-Regular Configuration Appendix B.1 General Information Appendix B.2 DCM Installation and ConfigurationAppendix B.1.2 Features Appendix B.2.1 InstallationAppendix B.2.2 DCM Requirements LAN Connection Power Connection192.168.1.13 192.168.1.155255.255.255.0 192.168.1.1Enter IP Address Appendix B.2.3 Accessing the DCMAppendix B.2.4 Configuring DCM System Parameters Appendix B.3.2 Status and Detailed Status Screens Appendix B.3 DCM OperationAppendix B.3.1 Logging into the DCM Datafiles screen Appendix B.3.3 Datafiles ScreenTroubleshooting Appendix B.4 DCM TroubleshootingAppendix B.4.1 DCM Troubleshooting Principles Appendix B.4.2 Resetting the DCMAppendix C.1.1 Versatile Interface Board Overview Appendix C.1 General Information-Versatile Interface BoardVIB I/O functions Interface VIB Designation Description Appendix C.1.2 VIB FeaturesO Designations Label X20Appendix C.2.4 VIB Output Specifications Appendix C.2 VIB Installation and ConfigurationAppendix C.2.1 VIB Installation Appendix C.2.3 VIB Input SpecificationsAppendix C.3 VIB Operation Appendix C.4.3 Inputs Not Recognized Appendix C.4 Troubleshooting the VIBAppendix C.4.2 VIB in Disabled or Not Available State Appendix C.4.1 UIB State Not Displayed on the Front PanelSubmittal documents accompanying Liebert FS Storage Solution Flywheel Storage SolutionAppendix D.1 Liebert FS Flywheel Submittal Document Matrix Appendix D.2 Other Liebert FS Drawings No UVR, circuit breaker to terminal block wiringElectrical connections Electrical system block diagram 48 UVR, circuit breaker to terminal block wiring 24 UVR, circuit breaker to terminal block wiringOutline drawing, Liebert FS cabinet Fused Disconnect Liebert FS FS cabinet to Liebert Series 610 UPS module Control wiring-external interconnect diagram, LiebertElevation drawing, Liebert FS cabinet with shipping package Front Elevation drawing-Liebert FS cabinet124 Liebert FS cabinet with optional power terminal block Mechanical Cabinet127 Liebert FS Systems Parallel + GND Circuit 138One-line moduleSystems With factoryLiebert UPS Module 401 Parallel with a LiebertUPSUnits Liebert UPS Module Liebert UPS Module Status/control Wiring, multiple unitsWiring specifications, Liebert FS and Liebert Series Wiring specifications, Liebert FS and Liebert Npower Wiring specifications, Liebert FS and Liebert Series Wiring specifications, Liebert FS and Liebert HiPulse 29-1/2 749mm Drill Template Dwg Cabinet Come with Liebert FS block diagram Power line diagram UPS cable entry-bottom Liebert FS Cabinet Phase Unit N Input Bus + Bus Ground BusUPS cable entry-top Liebert FS Cabinet Phase Unit N InputTOP View Technical specifications Appendix E.0 SpecificationsItems Required Appendix E.1 Ground Test ProcedureFrequency 50 to 60Hz Appendix F.2 Backup AC Power Supply SpecificationAppendix F.3 Recommended Backup Power Supply Configuration Appendix F.1 OverviewGrid supply DC bus Battery Liebert FS PackDistribution Appendix F.3.2 Operating the Liebert FS Without BatteriesGrid Supply OutputLiebert FS Flywheel module Appendix F.4 ScenariosAuxiliary Backup AC Power Supply 154 Page That Ne tIti Ti n
Related manuals
Manual 84 pages 14.4 Kb