Emerson Series 600, SERIES 600T user manual Liebert FS Software Control Parameter settings

Page 101

UPS Interconnection Kits

Appendix A.2.4 Liebert FS Configuration - Single Liebert FS on Liebert Series 610/600T/600 DC Bus

The following Software Control Parameters must be set when the Liebert FS is connected to the DC bus of the Liebert Series 610/600T/600 UPS system.

NOTE

The Software Control Parameter values specified below are recommended. These values may require adjustments due to the battery type. These must be used unless otherwise specified by the Liebert-certified service technician at initial system startup.

Instructions to set these parameters on the Liebert FS are in 6.5.3 - Control Parameters Setup at Initial System Startup.

Table 20 Liebert FS Software Control Parameter settings

Liebert FS Software Control Parameter

Setting

 

 

Charge Voltage

520VDC

 

 

Regulation Voltage

510VDC

 

 

Vreg Delta

0VDC

 

 

Maximum Charge Current

See Table 21

 

 

Charge Amps/Volts

See Table 21

 

 

Table 21 Liebert FS Software Control Parameters varying with UPS size

UPS Output Rating (kVA)

65

80

100

125

150

 

 

 

 

 

 

Liebert FS Maximum Charge Current (A)

25

31

39

49

50

 

 

 

 

 

 

Liebert FS Charge Amps/Volts (A/V)

1.7

2.1

2.6

3.3

3.4

 

 

 

 

 

 

Appendix A.2.5 Liebert FS Configuration - Multiple Liebert FS Units on Liebert Series 610/600T/600 DC Bus

The Liebert FS Software Control Parameters must be reset when multiple Liebert FS units are con- nected in parallel on the DC bus of a Liebert Series 610/600T/600 UPS system.

Instructions to set these parameters on the Liebert FS are in 6.5.3 - Control Parameters Setup at Initial System Startup.

Multiple Liebert FS Parallel Operation - Regular Configuration with Liebert Series 610/ 600T/600

The Liebert FS Software Control Parameters must be reset when multiple Liebert FS units are con- nected in parallel on the DC bus of a Liebert Series 610/600T/600 UPS system for proper operation with longer run times or higher backup power requirements. The Liebert FS units will contribute all together at the same time to the task of supporting the UPS DC bus.

NOTE

This configuration is recommended for UPS models with output power levels greater than 150 kVA (i.e., 225, 300, 400, 450, 500, 625, 750 and 1,000 kVA).

NOTE

In this configuration, the UPS DC bus usually does NOT have batteries in parallel with the Liebert FS units, however, parallel operation with batteries is acceptable. If batteries to be used are in parallel with the Liebert FS units on the UPS DC bus, contact your local Liebert sales representative to arrange a review of the application.

NOTE

Your Liebert-certified service technician will configure the Software Control Parameter values at initial system startup depending on the number of paralleled units.

89

Image 101
Contents Liebert FS DC Energy Storage System Page Table of Contents Operation System OverviewTroubleshooting MaintenanceAppendix B.0 Data Collection Module Appendix A.0 UPS Interconnection KitsAppendix E.0 Specifications Appendix D.0 Installation DrawingsAppendix F.0 Auxiliary Backup AC Power Supply Appendix C.0 Versatile Interface BoardFigures Vii Versatile Interface Board mounted in the Liebert FS 110 Tables Page Important Safety Instructions Safety Precautions General Information Safety ConsiderationsRequesting Assistance from Liebert System informationLiebert FS General System DescriptionDC Bus Loads Utility PowerLiebert FS Unit Liebert FS Unit 1 Liebert FS UnitGeneral Specifications Battery NGeneral system specifications LiebertKey Technological Features Features and BenefitsKey Customer Benefits Applicable Standards and CertificationKW-sec delivered GT model, 510 VDC, with filter Rectifier Utility Static SwitchBypass Environmental Considerations System LocationElectrical Considerations Flooring RequirementsStatus/Control Connections AC Power ConnectionsGrounding Connections Remote Monitoring Connections-Optional14623 Inspection Before Removal From the TruckUnloading Unpacking HandlingRemoving the metal support plates Lifting the Liebert FS cabinetPositioning the Liebert FS Storing the Liebert FS for Delayed InstallationMoving the Liebert FS Manuals Serial Number Model Number PlatesFront Right Side 12-100120-09 TopBottom Front Right Side Door open Panel removed Internal layoutFloor Mounting Bracket Cabinet Floor MountingFront of Liebert FS Mounting ToolsConcrete, Masonry or Stone Floor Mounting Instructions Checking hole depth 12.7mm Floor to Flange Bolt securing bracket to cabinetBubble level Mounting front bolts-front side of cabinetWood Floor Mounting Parts Wood Floor MountingWood Floor Mounting Tools Wood Floor Mounting InstructionsRaised Floor Mounting Instructions Raised Floor Mounting Raised Floor Mounting KitRaised Floor Mounting Tools General Wiring Considerations Wiring ConnectionsFront RearCircuit Breaker Mounting Plate Control DC and Ground Connections Communication Access PanelGround Connections Ground Wire Gauge Tightening Torque Approximate metric InchTightening torque for ground connection PoundsService panel location AC Auxiliary Control Power Supply ConnectionsTerminal Neutral Line Ground Fused disconnectRemote monitoring DCM connections inside cabinet front door Startup ConsiderationsLiebert FS front view Detailed System DescriptionSystem Module Description Power Conversion ModuleControl Panel UPS Interconnection KitElectrical system schematic Flywheel Module Power SystemBattery Input System PerformanceVersatile Interface Board VIB User interfaces Control PanelData Collection Module DCM Igbt Power Conversion Module PCM Active Magnetic Levitation Hardware Magnetic Levitation Module MLMUpper Radial Axial ElectromagnetMotor Generator Rotor/Flywheel-Rotating GroupVacuum system operation Vacuum SystemFlywheel Sensors Speed TemperatureCabinet System SafetyOuter Housing Rotating Group Inner Housing Coolant List of System User-Configurable Parameters Max Charge Current Voltage Behavior Current Sink Regulation Voltage Delta During Discharge Vreg DeltaVreg delta help screen Modes of OperationStandby Mode OFF ModeStartup Mode UPS DC Bus Voltage = VchargeVoltage ≥ Vcharge Charge ModeReady Mode Following a Liebert FS Discharge Down to SOC = 0% Discharge ModeShutdown Mode Fault Mode Following a User CommandCoast Mode Typical operation modes KEY # Mode DescriptionMaintenance and Reliability Operator Controls Access System HistorySystem Mode Indicators System Status IndicatorsControl Panel Control panel keyboard layout refer to FigureMain screen function descriptions System Status Indicators System Mode IndicatorsSystem status indicators Operation modesUninstalled DisabledOther Status Indicators OperativeMenu Tree and Navigation Security AccessMenu tree Navigation and Operation of Control Panel System Setup and Parameter Access2VREG Time/Date ViewHistory TemperaturesVoltages 01 03/10/05 1143 W 12302 03/10/05 1037 W 03 02/24/05 0403 WOptions 192.168.1.155 Network-Requires DCM Option255.255.255.0 192.168.1.1Security ElectricalVitals Change password Password screensTools AboutCopyright Appl PRI-3.00 SEC-3.01 BL PRI-3.02 SEC-3.01 001 FM S/N MLM S/N 0001 PCM S/N 0002 SO# 123-456-7Inspection before Initial System Startup Initial System Startup ProcedureSystem Startup Control Parameter Value Default Control Parameters Setup at Initial System StartupControl parameters Software versionsPowering Up the Liebert FS Regular Startup ProcedureBooting Up Inspection Before Regular StartupValidation of Control Parameters Setup Shutdown ProcedureInitiating Liebert FS Startup Sequence Liebert FS Startup SequenceSafety Precautions Routine Maintenance Liebert Global ServicesMaintenance schedule Maintenance ScheduleRecord Log FrequencyOptional Air Filters Torque specifications unless otherwise labeledTorque Requirements Detecting TroubleCorrective Actions Reporting a ProblemRecommended Test Equipment Limited Life ComponentsUser level menu GeneralButton F5 ChargeAuxpower Meaning / Possible Causes Troubleshooting LabelMore information Fault Clear Button F3 Button F5 FaultsBus Power BUS Current Offset Faults-causes and responsesTroubleshooting Fault Label Troubleshooting Action Appendix A.1.1 General Wiring Considerations Appendix A.1 Wiring ConnectionsKey to UPS model interconnection Liebert FS Model # Use With Liebert UPSTop view of Liebert FS Cabinet with UPS interconnection kit Front Rear Liebert FS Positive Terminal Negative Appendix A.1.2 DC Power Connections Circuit Breaker Torque UPS Output Rating KVA Liebert Series 610/600T/600 model ratingsYellow Blue Two rows Row for Liebert FS Software Control Parameter Setting Liebert FS Software Control Parameter settingsLiebert FS Npower UPS Liebert Npower model ratingsOutput RatingSee Table Liebert FS Software Setting Control ParameterLiebert FS Software Control Parameters UPS Interconnection Kits Liebert Series 300 UPS List of Liebert Series 300 models ratingsLiebert Series 300 status/control terminal block wiring 395VDC Liebert HiPulse model ratings Appendix A.5.1 Description-HiPulse UPS Interconnection KitLiebert FS positive terminal Liebert FS negative terminal Appendix A.5.3 IKIT-A05 DC Power ConnectionsUPS Output Rating kVA 120 Appendix A.5.5 Single Liebert FS on UPS DC BusMultiple Liebert FS Parallel Operation-Regular Configuration Appendix B.1.2 Features Appendix B.2 DCM Installation and ConfigurationAppendix B.2.1 Installation Appendix B.1 General InformationAppendix B.2.2 DCM Requirements LAN Connection Power Connection255.255.255.0 192.168.1.155192.168.1.1 192.168.1.13Enter IP Address Appendix B.2.3 Accessing the DCMAppendix B.2.4 Configuring DCM System Parameters Appendix B.3.2 Status and Detailed Status Screens Appendix B.3 DCM OperationAppendix B.3.1 Logging into the DCM Datafiles screen Appendix B.3.3 Datafiles ScreenAppendix B.4.1 DCM Troubleshooting Principles Appendix B.4 DCM TroubleshootingAppendix B.4.2 Resetting the DCM TroubleshootingAppendix C.1.1 Versatile Interface Board Overview Appendix C.1 General Information-Versatile Interface BoardVIB I/O functions Interface VIB Designation Description Appendix C.1.2 VIB FeaturesO Designations Label X20Appendix C.2.1 VIB Installation Appendix C.2 VIB Installation and ConfigurationAppendix C.2.3 VIB Input Specifications Appendix C.2.4 VIB Output SpecificationsAppendix C.3 VIB Operation Appendix C.4.2 VIB in Disabled or Not Available State Appendix C.4 Troubleshooting the VIBAppendix C.4.1 UIB State Not Displayed on the Front Panel Appendix C.4.3 Inputs Not RecognizedSubmittal documents accompanying Liebert FS Storage Solution Flywheel Storage SolutionAppendix D.1 Liebert FS Flywheel Submittal Document Matrix Appendix D.2 Other Liebert FS Drawings No UVR, circuit breaker to terminal block wiringElectrical connections Electrical system block diagram 48 UVR, circuit breaker to terminal block wiring 24 UVR, circuit breaker to terminal block wiringOutline drawing, Liebert FS cabinet Fused Disconnect Liebert FS FS cabinet to Liebert Series 610 UPS module Control wiring-external interconnect diagram, LiebertElevation drawing, Liebert FS cabinet with shipping package Front Elevation drawing-Liebert FS cabinet124 Liebert FS cabinet with optional power terminal block Mechanical Cabinet127 Liebert FS Systems Parallel + GND Systems 138One-line moduleWith factory CircuitLiebert UPS Module 401 Parallel with a LiebertUPSUnits Liebert UPS Module Liebert UPS Module Status/control Wiring, multiple unitsWiring specifications, Liebert FS and Liebert Series Wiring specifications, Liebert FS and Liebert Npower Wiring specifications, Liebert FS and Liebert Series Wiring specifications, Liebert FS and Liebert HiPulse 29-1/2 749mm Drill Template Dwg Cabinet Come with Liebert FS block diagram Power line diagram UPS cable entry-bottom Liebert FS Cabinet Phase Unit N Input Bus + Bus Ground BusUPS cable entry-top Liebert FS Cabinet Phase Unit N InputTOP View Technical specifications Appendix E.0 SpecificationsItems Required Appendix E.1 Ground Test ProcedureAppendix F.3 Recommended Backup Power Supply Configuration Appendix F.2 Backup AC Power Supply SpecificationAppendix F.1 Overview Frequency 50 to 60HzGrid supply DC bus Battery Liebert FS PackGrid Appendix F.3.2 Operating the Liebert FS Without BatteriesSupply Output DistributionLiebert FS Flywheel module Appendix F.4 ScenariosAuxiliary Backup AC Power Supply 154 Page Iti Ne tTi n That