Emerson SERIES 600T, Series 600 user manual Discharge Mode, Shutdown Mode

Page 60

System Overview

5.3.6DISCHARGE Mode

Starting from either CHARGE or READY mode, the Liebert FS will enter the DISCHARGE mode if the UPS DC Bus Voltage goes below Vcharge. In DISCHARGE mode, the Liebert FS will regulate the DC bus at Vreg.

Figure 50 DISCHARGE mode diagram

State of Charge < 0

0%

State of Charge > 0

Note: UPS DC Bus Voltage = Vreg

99

1

 

00%

.

5%

The Liebert FS will be in DISCHARGE mode as long as:

UPS DC Bus Voltage < Vcharge and

Liebert FS’s SOC is more than 0%.

The Liebert FS will leave the DISCHARGE mode and transition into CHARGE mode if the UPS DC bus recovers (UPS DC Bus Voltage = Vcharge) before the Liebert FS’s SOC reaches 0%. In case the UPS DC bus doesn’t recover before the Liebert FS’s SOC reaches 0%, the Liebert FS will transition into SHUTDOWN mode.

5.3.7SHUTDOWN Mode

In SHUTDOWN mode, the flywheel will actively spin down.

There are two ways the Liebert FS can transition into SHUTDOWN mode, by a complete discharge and by a user command.

Following a Liebert FS Discharge Down to SOC = 0%

This is the most common SHUTDOWN process. This occurs when the Liebert FS’s SOC drops below 0% and the UPS System DC Bus voltage is less than Vcharge. If the Liebert FS entered the SHUT- DOWN mode after leaving DISCHARGE mode, the Liebert FS will automatically transition into STARTUP mode provided the UPS System DC Bus voltage returns to a value greater than Vcharge (i.e., when the electric grid returns or the standby generator supplies power to the UPS).

Figure 51 SHUTDOWN mode diagram - shutdown after full discharge

State of Charge < 0

State of Charge > 0

Note: UPS DC Bus Voltage < Vcharge

0%

 

99

1

 

00%

.

5%

48

Image 60
Contents Liebert FS DC Energy Storage System Page Table of Contents System Overview OperationMaintenance TroubleshootingAppendix A.0 UPS Interconnection Kits Appendix B.0 Data Collection ModuleAppendix D.0 Installation Drawings Appendix E.0 SpecificationsAppendix F.0 Auxiliary Backup AC Power Supply Appendix C.0 Versatile Interface BoardFigures Vii Versatile Interface Board mounted in the Liebert FS 110 Tables Page Important Safety Instructions Safety Precautions Safety Considerations General InformationRequesting Assistance from Liebert System informationGeneral System Description Liebert FSUtility Power DC Bus LoadsLiebert FS Unit Liebert FS Unit 1 Liebert FS UnitBattery N General SpecificationsGeneral system specifications LiebertFeatures and Benefits Key Technological FeaturesKey Customer Benefits Applicable Standards and CertificationKW-sec delivered GT model, 510 VDC, with filter Utility Static Switch BypassRectifier System Location Environmental ConsiderationsFlooring Requirements Electrical ConsiderationsAC Power Connections Status/Control ConnectionsGrounding Connections Remote Monitoring Connections-OptionalInspection Before Removal From the Truck Unloading14623 Handling UnpackingLifting the Liebert FS cabinet Removing the metal support platesStoring the Liebert FS for Delayed Installation Positioning the Liebert FSMoving the Liebert FS Manuals Serial Number Model Number PlatesTop BottomFront Right Side 12-100120-09 Internal layout Front Right Side Door open Panel removedCabinet Floor Mounting Floor Mounting BracketMounting Tools Concrete, Masonry or Stone Floor Mounting InstructionsFront of Liebert FS Checking hole depth Bolt securing bracket to cabinet 12.7mm Floor to FlangeMounting front bolts-front side of cabinet Bubble levelWood Floor Mounting Wood Floor Mounting PartsWood Floor Mounting Tools Wood Floor Mounting InstructionsRaised Floor Mounting Raised Floor Mounting Kit Raised Floor Mounting ToolsRaised Floor Mounting Instructions Wiring Connections General Wiring ConsiderationsFront RearControl DC and Ground Connections Communication Access Panel Circuit Breaker Mounting PlateGround Wire Gauge Tightening Torque Approximate metric Inch Ground ConnectionsTightening torque for ground connection PoundsAC Auxiliary Control Power Supply Connections Service panel locationFused disconnect Terminal Neutral Line GroundStartup Considerations Remote monitoring DCM connections inside cabinet front doorDetailed System Description Liebert FS front viewPower Conversion Module System Module DescriptionControl Panel UPS Interconnection KitPower System Electrical system schematic Flywheel ModuleBattery Input System PerformanceUser interfaces Control Panel Data Collection Module DCMVersatile Interface Board VIB Igbt Power Conversion Module PCM Magnetic Levitation Module MLM Active Magnetic Levitation HardwareAxial Electromagnet Upper RadialRotor/Flywheel-Rotating Group Motor GeneratorVacuum System Vacuum system operationTemperature Flywheel Sensors SpeedSystem Safety Outer Housing Rotating Group Inner Housing CoolantCabinet List of System User-Configurable Parameters Regulation Voltage Delta During Discharge Vreg Delta Max Charge Current Voltage Behavior Current Sink Modes of Operation Vreg delta help screenOFF Mode Standby ModeStartup Mode UPS DC Bus Voltage = VchargeCharge Mode Ready ModeVoltage ≥ Vcharge Discharge Mode Shutdown ModeFollowing a Liebert FS Discharge Down to SOC = 0% Following a User Command Coast ModeFault Mode KEY # Mode Description Typical operation modesMaintenance and Reliability Access System History Operator ControlsSystem Status Indicators System Mode IndicatorsControl Panel Control panel keyboard layout refer to FigureMain screen function descriptions System Mode Indicators System Status IndicatorsSystem status indicators Operation modesDisabled UninstalledOther Status Indicators OperativeSecurity Access Menu Tree and NavigationMenu tree System Setup and Parameter Access Navigation and Operation of Control Panel2VREG View Time/DateTemperatures VoltagesHistory 123 01 03/10/05 1143 W02 03/10/05 1037 W 03 02/24/05 0403 WOptions Network-Requires DCM Option 192.168.1.155255.255.255.0 192.168.1.1Electrical VitalsSecurity Password screens Change passwordAbout ToolsCopyright Appl PRI-3.00 SEC-3.01 BL PRI-3.02 SEC-3.01 001 FM S/N MLM S/N 0001 PCM S/N 0002 SO# 123-456-7Initial System Startup Procedure System StartupInspection before Initial System Startup Control Parameters Setup at Initial System Startup Control Parameter Value DefaultControl parameters Software versionsRegular Startup Procedure Powering Up the Liebert FSBooting Up Inspection Before Regular StartupShutdown Procedure Validation of Control Parameters SetupInitiating Liebert FS Startup Sequence Liebert FS Startup SequenceSafety Precautions Liebert Global Services Routine MaintenanceMaintenance Schedule Maintenance scheduleRecord Log FrequencyTorque specifications unless otherwise labeled Optional Air FiltersTorque Requirements Detecting TroubleReporting a Problem Corrective ActionsRecommended Test Equipment Limited Life ComponentsGeneral User level menuCharge Button F5Meaning / Possible Causes Troubleshooting Label AuxpowerFaults Bus PowerMore information Fault Clear Button F3 Button F5 Faults-causes and responses BUS Current OffsetTroubleshooting Fault Label Troubleshooting Action Appendix A.1 Wiring Connections Appendix A.1.1 General Wiring ConsiderationsKey to UPS model interconnection Liebert FS Model # Use With Liebert UPSFront Rear Top view of Liebert FS Cabinet with UPS interconnection kitAppendix A.1.2 DC Power Connections Circuit Breaker TorqueLiebert FS Positive Terminal Negative Liebert Series 610/600T/600 model ratings UPS Output Rating KVAYellow Blue Two rows Row for Liebert FS Software Control Parameter settings Liebert FS Software Control Parameter SettingLiebert Npower model ratings Liebert FS Npower UPSOutput RatingLiebert FS Software Setting Control Parameter Liebert FS Software Control ParametersSee Table UPS Interconnection Kits List of Liebert Series 300 models ratings Liebert Series 300 UPSLiebert Series 300 status/control terminal block wiring 395VDC Appendix A.5.1 Description-HiPulse UPS Interconnection Kit Liebert HiPulse model ratingsAppendix A.5.3 IKIT-A05 DC Power Connections Liebert FS positive terminal Liebert FS negative terminalAppendix A.5.5 Single Liebert FS on UPS DC Bus UPS Output Rating kVA 120Multiple Liebert FS Parallel Operation-Regular Configuration Appendix B.2 DCM Installation and Configuration Appendix B.1.2 FeaturesAppendix B.2.1 Installation Appendix B.1 General InformationLAN Connection Power Connection Appendix B.2.2 DCM Requirements192.168.1.155 255.255.255.0192.168.1.1 192.168.1.13Appendix B.2.3 Accessing the DCM Appendix B.2.4 Configuring DCM System ParametersEnter IP Address Appendix B.3 DCM Operation Appendix B.3.1 Logging into the DCMAppendix B.3.2 Status and Detailed Status Screens Appendix B.3.3 Datafiles Screen Datafiles screenAppendix B.4 DCM Troubleshooting Appendix B.4.1 DCM Troubleshooting PrinciplesAppendix B.4.2 Resetting the DCM TroubleshootingAppendix C.1 General Information-Versatile Interface Board Appendix C.1.1 Versatile Interface Board OverviewAppendix C.1.2 VIB Features VIB I/O functions Interface VIB Designation DescriptionLabel X20 O DesignationsAppendix C.2 VIB Installation and Configuration Appendix C.2.1 VIB InstallationAppendix C.2.3 VIB Input Specifications Appendix C.2.4 VIB Output SpecificationsAppendix C.3 VIB Operation Appendix C.4 Troubleshooting the VIB Appendix C.4.2 VIB in Disabled or Not Available StateAppendix C.4.1 UIB State Not Displayed on the Front Panel Appendix C.4.3 Inputs Not RecognizedStorage Solution Flywheel Storage Solution Appendix D.1 Liebert FS Flywheel Submittal Document MatrixSubmittal documents accompanying Liebert FS No UVR, circuit breaker to terminal block wiring Appendix D.2 Other Liebert FS DrawingsElectrical connections Electrical system block diagram 24 UVR, circuit breaker to terminal block wiring 48 UVR, circuit breaker to terminal block wiringOutline drawing, Liebert FS cabinet Fused Disconnect Liebert FS Control wiring-external interconnect diagram, Liebert FS cabinet to Liebert Series 610 UPS moduleElevation drawing, Liebert FS cabinet with shipping package Elevation drawing-Liebert FS cabinet Front124 Liebert FS cabinet with optional power terminal block Cabinet Mechanical127 Liebert FS Systems Parallel + GND 138One-line module SystemsWith factory CircuitLiebert UPS Module 401 LiebertUPS UnitsParallel with a Liebert UPS Module Liebert UPS Module Wiring, multiple units Status/controlWiring specifications, Liebert FS and Liebert Series Wiring specifications, Liebert FS and Liebert Npower Wiring specifications, Liebert FS and Liebert Series Wiring specifications, Liebert FS and Liebert HiPulse 29-1/2 749mm Drill Template Dwg Cabinet Come with Liebert FS block diagram Power line diagram Liebert FS Cabinet Phase Unit N Input Bus + Bus Ground Bus UPS cable entry-bottomLiebert FS Cabinet Phase Unit N Input UPS cable entry-topTOP View Appendix E.0 Specifications Technical specificationsAppendix E.1 Ground Test Procedure Items RequiredAppendix F.2 Backup AC Power Supply Specification Appendix F.3 Recommended Backup Power Supply ConfigurationAppendix F.1 Overview Frequency 50 to 60HzBattery Liebert FS Pack Grid supply DC busAppendix F.3.2 Operating the Liebert FS Without Batteries GridSupply Output DistributionAppendix F.4 Scenarios Liebert FS Flywheel moduleAuxiliary Backup AC Power Supply 154 Page Ne t ItiTi n That