Emerson SERIES 600T, Series 600 user manual General, User level menu

Page 90

Troubleshooting

8.0TROUBLESHOOTING

NOTE

Refer to this section before calling Liebert Global Services for support.

8.1General

The Liebert FS is capable of detecting conditions outside of normal operating parameters and provid- ing notice at the Control Panel. This data is recorded as either Warnings or Faults and can be viewed in the software menu tree at the screen location MENU>VIEW>. These Warnings and Faults can also be communicated by the Versatile Interface Board (VIB), if this option has been installed, to an exter- nal device or system; (see Appendix C.0 - Versatile Interface Board). This data will also be recorded in the Data Collection Module option if this has been selected. Please see Appendix B.0 - Data Collection Module for instructions on how to access this data via the DCM.

Any Warnings and Faults that may occur will be displayed on the Main screen of the Control Panel. The Liebert FS’ Warnings and Faults tables (see Tables 15 and 16), describe these Warnings, mean- ings and possible causes. The operator action required or automatic system function that will result is explained.

In addition to the information displayed on the Main screen, other system information that can be used for troubleshooting is available and can be accessed from the Control Panel. From the Main screen the Menu screen can be selected by pressing (F6) on the Control Panel located below MENU.

Figure 89 USER level menu

MENU>

 

 

1.

PARAMETERS

 

2.

VIEW

 

3.

SECURITY

 

4.

ABOUT

 

5.

TOOLS

 

 

 

 

 

HOME

DONE

Selecting View displays various system statuses including real-time and historical data. You can select the function by number.

Figure 90 VIEW menu

MENU>VIEW>

 

 

 

1.

TIME/DATE

6.

NETWORK

 

2.

TEMPERATURES

7.

ELECTRICAL

 

3.

VOLTAGES

8.

VITALS

 

4.

HISTORY

 

 

 

5.

OPTIONS

 

 

 

 

 

 

 

 

 

 

 

HOME

DONE

Selecting History will provide a history of Warnings and Faults as introduced in Section 5, Opera- tions, of this manual. Other information that can be useful in troubleshooting are the Temperatures, Voltages, Options, Electrical and Vitals screens.

Warning/Fault: The Liebert FS holds 35 warning and fault information, respectively. A single screen shows seven warnings or faults. Users can move between pages using PREV, NEXT button. (See Figures 91 and 92 below).

78

Image 90
Contents Liebert FS DC Energy Storage System Page Table of Contents System Overview OperationMaintenance TroubleshootingAppendix A.0 UPS Interconnection Kits Appendix B.0 Data Collection ModuleAppendix F.0 Auxiliary Backup AC Power Supply Appendix D.0 Installation DrawingsAppendix E.0 Specifications Appendix C.0 Versatile Interface BoardFigures Vii Versatile Interface Board mounted in the Liebert FS 110 Tables Page Important Safety Instructions Safety Precautions Requesting Assistance from Liebert Safety ConsiderationsGeneral Information System informationGeneral System Description Liebert FSLiebert FS Unit Utility PowerDC Bus Loads Liebert FS Unit 1 Liebert FS UnitGeneral system specifications Battery NGeneral Specifications LiebertKey Customer Benefits Features and BenefitsKey Technological Features Applicable Standards and CertificationKW-sec delivered GT model, 510 VDC, with filter Utility Static Switch BypassRectifier System Location Environmental ConsiderationsFlooring Requirements Electrical ConsiderationsGrounding Connections AC Power ConnectionsStatus/Control Connections Remote Monitoring Connections-OptionalInspection Before Removal From the Truck Unloading14623 Handling UnpackingLifting the Liebert FS cabinet Removing the metal support platesMoving the Liebert FS Storing the Liebert FS for Delayed InstallationPositioning the Liebert FS Manuals Serial Number Model Number PlatesTop BottomFront Right Side 12-100120-09 Internal layout Front Right Side Door open Panel removedCabinet Floor Mounting Floor Mounting BracketMounting Tools Concrete, Masonry or Stone Floor Mounting InstructionsFront of Liebert FS Checking hole depth Bolt securing bracket to cabinet 12.7mm Floor to FlangeMounting front bolts-front side of cabinet Bubble levelWood Floor Mounting Tools Wood Floor MountingWood Floor Mounting Parts Wood Floor Mounting InstructionsRaised Floor Mounting Raised Floor Mounting Kit Raised Floor Mounting ToolsRaised Floor Mounting Instructions Front Wiring ConnectionsGeneral Wiring Considerations RearControl DC and Ground Connections Communication Access Panel Circuit Breaker Mounting PlateTightening torque for ground connection Ground Wire Gauge Tightening Torque Approximate metric InchGround Connections PoundsAC Auxiliary Control Power Supply Connections Service panel locationFused disconnect Terminal Neutral Line GroundStartup Considerations Remote monitoring DCM connections inside cabinet front doorDetailed System Description Liebert FS front viewControl Panel Power Conversion ModuleSystem Module Description UPS Interconnection KitBattery Input Power SystemElectrical system schematic Flywheel Module System PerformanceUser interfaces Control Panel Data Collection Module DCMVersatile Interface Board VIB Igbt Power Conversion Module PCM Magnetic Levitation Module MLM Active Magnetic Levitation HardwareAxial Electromagnet Upper RadialRotor/Flywheel-Rotating Group Motor GeneratorVacuum System Vacuum system operationTemperature Flywheel Sensors SpeedSystem Safety Outer Housing Rotating Group Inner Housing CoolantCabinet List of System User-Configurable Parameters Regulation Voltage Delta During Discharge Vreg Delta Max Charge Current Voltage Behavior Current SinkModes of Operation Vreg delta help screenStartup Mode OFF ModeStandby Mode UPS DC Bus Voltage = VchargeCharge Mode Ready ModeVoltage ≥ Vcharge Discharge Mode Shutdown ModeFollowing a Liebert FS Discharge Down to SOC = 0% Following a User Command Coast ModeFault Mode KEY # Mode Description Typical operation modesMaintenance and Reliability Access System History Operator ControlsControl Panel System Status IndicatorsSystem Mode Indicators Control panel keyboard layout refer to FigureMain screen function descriptions System status indicators System Mode IndicatorsSystem Status Indicators Operation modesOther Status Indicators DisabledUninstalled OperativeSecurity Access Menu Tree and NavigationMenu tree System Setup and Parameter Access Navigation and Operation of Control Panel2VREG View Time/DateTemperatures VoltagesHistory 02 03/10/05 1037 W 12301 03/10/05 1143 W 03 02/24/05 0403 WOptions 255.255.255.0 Network-Requires DCM Option192.168.1.155 192.168.1.1Electrical VitalsSecurity Password screens Change passwordCopyright Appl PRI-3.00 SEC-3.01 BL PRI-3.02 SEC-3.01 AboutTools 001 FM S/N MLM S/N 0001 PCM S/N 0002 SO# 123-456-7Initial System Startup Procedure System StartupInspection before Initial System Startup Control parameters Control Parameters Setup at Initial System StartupControl Parameter Value Default Software versionsBooting Up Regular Startup ProcedurePowering Up the Liebert FS Inspection Before Regular StartupInitiating Liebert FS Startup Sequence Shutdown ProcedureValidation of Control Parameters Setup Liebert FS Startup SequenceSafety Precautions Liebert Global Services Routine MaintenanceRecord Log Maintenance ScheduleMaintenance schedule FrequencyTorque Requirements Torque specifications unless otherwise labeledOptional Air Filters Detecting TroubleRecommended Test Equipment Reporting a ProblemCorrective Actions Limited Life ComponentsGeneral User level menuCharge Button F5Meaning / Possible Causes Troubleshooting Label AuxpowerFaults Bus PowerMore information Fault Clear Button F3 Button F5 Faults-causes and responses BUS Current OffsetTroubleshooting Fault Label Troubleshooting Action Key to UPS model interconnection Appendix A.1 Wiring ConnectionsAppendix A.1.1 General Wiring Considerations Liebert FS Model # Use With Liebert UPSFront Rear Top view of Liebert FS Cabinet with UPS interconnection kitAppendix A.1.2 DC Power Connections Circuit Breaker TorqueLiebert FS Positive Terminal Negative Liebert Series 610/600T/600 model ratings UPS Output Rating KVAYellow Blue Two rows Row for Liebert FS Software Control Parameter settings Liebert FS Software Control Parameter SettingOutput Liebert Npower model ratingsLiebert FS Npower UPS RatingLiebert FS Software Setting Control Parameter Liebert FS Software Control ParametersSee Table UPS Interconnection Kits List of Liebert Series 300 models ratings Liebert Series 300 UPSLiebert Series 300 status/control terminal block wiring 395VDC Appendix A.5.1 Description-HiPulse UPS Interconnection Kit Liebert HiPulse model ratingsAppendix A.5.3 IKIT-A05 DC Power Connections Liebert FS positive terminal Liebert FS negative terminalAppendix A.5.5 Single Liebert FS on UPS DC Bus UPS Output Rating kVA 120Multiple Liebert FS Parallel Operation-Regular Configuration Appendix B.2.1 Installation Appendix B.2 DCM Installation and ConfigurationAppendix B.1.2 Features Appendix B.1 General InformationLAN Connection Power Connection Appendix B.2.2 DCM Requirements192.168.1.1 192.168.1.155255.255.255.0 192.168.1.13Appendix B.2.3 Accessing the DCM Appendix B.2.4 Configuring DCM System ParametersEnter IP Address Appendix B.3 DCM Operation Appendix B.3.1 Logging into the DCMAppendix B.3.2 Status and Detailed Status Screens Appendix B.3.3 Datafiles Screen Datafiles screenAppendix B.4.2 Resetting the DCM Appendix B.4 DCM TroubleshootingAppendix B.4.1 DCM Troubleshooting Principles TroubleshootingAppendix C.1 General Information-Versatile Interface Board Appendix C.1.1 Versatile Interface Board OverviewAppendix C.1.2 VIB Features VIB I/O functions Interface VIB Designation DescriptionLabel X20 O DesignationsAppendix C.2.3 VIB Input Specifications Appendix C.2 VIB Installation and ConfigurationAppendix C.2.1 VIB Installation Appendix C.2.4 VIB Output SpecificationsAppendix C.3 VIB Operation Appendix C.4.1 UIB State Not Displayed on the Front Panel Appendix C.4 Troubleshooting the VIBAppendix C.4.2 VIB in Disabled or Not Available State Appendix C.4.3 Inputs Not RecognizedStorage Solution Flywheel Storage Solution Appendix D.1 Liebert FS Flywheel Submittal Document MatrixSubmittal documents accompanying Liebert FS No UVR, circuit breaker to terminal block wiring Appendix D.2 Other Liebert FS DrawingsElectrical connections Electrical system block diagram 24 UVR, circuit breaker to terminal block wiring 48 UVR, circuit breaker to terminal block wiringOutline drawing, Liebert FS cabinet Fused Disconnect Liebert FS Control wiring-external interconnect diagram, Liebert FS cabinet to Liebert Series 610 UPS moduleElevation drawing, Liebert FS cabinet with shipping package Elevation drawing-Liebert FS cabinet Front124 Liebert FS cabinet with optional power terminal block Cabinet Mechanical127 Liebert FS Systems Parallel + GND With factory 138One-line moduleSystems CircuitLiebert UPS Module 401 LiebertUPS UnitsParallel with a Liebert UPS Module Liebert UPS Module Wiring, multiple units Status/controlWiring specifications, Liebert FS and Liebert Series Wiring specifications, Liebert FS and Liebert Npower Wiring specifications, Liebert FS and Liebert Series Wiring specifications, Liebert FS and Liebert HiPulse 29-1/2 749mm Drill Template Dwg Cabinet Come with Liebert FS block diagram Power line diagram Liebert FS Cabinet Phase Unit N Input Bus + Bus Ground Bus UPS cable entry-bottomLiebert FS Cabinet Phase Unit N Input UPS cable entry-topTOP View Appendix E.0 Specifications Technical specificationsAppendix E.1 Ground Test Procedure Items RequiredAppendix F.1 Overview Appendix F.2 Backup AC Power Supply SpecificationAppendix F.3 Recommended Backup Power Supply Configuration Frequency 50 to 60HzBattery Liebert FS Pack Grid supply DC busSupply Output Appendix F.3.2 Operating the Liebert FS Without BatteriesGrid DistributionAppendix F.4 Scenarios Liebert FS Flywheel moduleAuxiliary Backup AC Power Supply 154 Page Ti n Ne tIti That
Related manuals
Manual 84 pages 14.4 Kb

Series 600, SERIES 600T specifications

The Emerson SERIES 600T, as part of the SERIES 600 line, is a sophisticated device designed to meet the demands of industrial automation and control systems. Renowned for its reliability and versatility, the SERIES 600T excels in various applications across multiple sectors, including oil and gas, chemical processing, and power generation.

One of the most significant features of the SERIES 600T is its advanced measuring capability. It offers exceptional accuracy, typically within ±0.1% of the full scale. This precision makes it suitable for critical applications where measurement integrity is paramount. The SERIES 600T is also equipped with intelligent diagnostics that can predict and monitor the health of the unit, enabling proactive maintenance and minimizing downtime. This technological advancement improves both operational efficiency and safety.

Another standout characteristic is the device's robust construction designed to withstand harsh environments. The SERIES 600T is made with durable materials that provide resistance to corrosion, vibration, and temperature extremes, making it an excellent choice for rugged industrial applications. Coupled with its IP67 rating, the device is fully sealed against dust and moisture, ensuring long-term reliability in challenging conditions.

The SERIES 600 line employs cutting-edge communication protocols, including HART and Foundation Fieldbus, facilitating seamless integration into various control systems. This capability ensures that users can easily access real-time data and manage devices remotely, significantly enhancing operational efficiency.

Additionally, the SERIES 600T supports a wide range of process connections and configurations, catering to diverse installation needs. This adaptability allows for quick deployments and minimizes the time required for system changes or upgrades.

With easy-to-read displays and user-friendly interfaces, operators can quickly interpret data and metrics from the SERIES 600T. This intuitive design helps reduce the learning curve for new users, further underlining the device's legacy of reliability and efficiency.

In essence, the Emerson SERIES 600T exemplifies cutting-edge technology in the realm of industrial measurement and automation. Its combination of accuracy, durability, diagnostic capabilities, and ease of integration makes it an ideal choice for industries that prioritize reliability and precision in their operations. As industrial processes continue to evolve, devices like the SERIES 600T will undoubtedly play a crucial role in advancing efficiency and productivity in various sectors.