Emerson SERIES 600T, Series 600 Meaning / Possible Causes Troubleshooting Label, Auxpower

Page 92

Troubleshooting

Table 15 lists the warnings and some troubleshooting steps that may be taken if any of the Warnings in appear.

Table 15 Warnings

Warning

Meaning / Possible Causes

Troubleshooting

Label

 

 

AUXPOWER

Auxiliary power supply is low when the system is

 

not in OFF mode.

Check / Test Auxiliary power supply

LOW

Factory-configurable warning

 

 

 

 

 

 

VACUUM

Drag power exceeds 85W *

Check Vitals and Vacuum History

LOW

 

 

MISER HIGH

Miser voltage is higher than 2V

Calibrate board

 

 

 

RUNOUT

Runout is higher than 2.0 mil.*

Check Vitals and Runout History

HIGH

 

 

PWR SPLY

Power supply for PPMC/PCMC is lower than 21V.

Power supply for PPMC/PCMC is lower

VOLT LOW

than 21V

 

VIB

VIB inoperative while enabled

Check VIB cable connections and wiring

INOPERATIVE

 

 

OVERSPEED

Speed is higher than the Max Speed

Have Certified Service personnel check

software settings

 

 

SET TIME/

Time and date have not been set

Set Time/Date in Menu>View>Time/Date

DATE

 

 

* Warnings of this nature should be monitored and may be used to schedule preventive maintenance.

If Warnings persist, contact your local Liebert representative or contact Liebert Global Services at 800-543-2378. You may also visit the Liebert Web site for information at www.liebert.com.

NOTE

A “Standby, Motor Hot” message may be displayed as a result of consecutive and repetitive discharges. This is not a Warning but a normal operating occurrence that may occur due to frequent charging and discharging of system. Once motor cools it will automatically resume operation.

80

Image 92
Contents Liebert FS DC Energy Storage System Page Table of Contents System Overview OperationMaintenance TroubleshootingAppendix A.0 UPS Interconnection Kits Appendix B.0 Data Collection ModuleAppendix D.0 Installation Drawings Appendix E.0 SpecificationsAppendix F.0 Auxiliary Backup AC Power Supply Appendix C.0 Versatile Interface BoardFigures Vii Versatile Interface Board mounted in the Liebert FS 110 Tables Page Important Safety Instructions Safety Precautions Safety Considerations General InformationRequesting Assistance from Liebert System informationGeneral System Description Liebert FSUtility Power DC Bus LoadsLiebert FS Unit Liebert FS Unit 1 Liebert FS UnitBattery N General SpecificationsGeneral system specifications LiebertFeatures and Benefits Key Technological FeaturesKey Customer Benefits Applicable Standards and CertificationKW-sec delivered GT model, 510 VDC, with filter Rectifier Utility Static SwitchBypass System Location Environmental ConsiderationsFlooring Requirements Electrical ConsiderationsAC Power Connections Status/Control ConnectionsGrounding Connections Remote Monitoring Connections-Optional14623 Inspection Before Removal From the TruckUnloading Handling UnpackingLifting the Liebert FS cabinet Removing the metal support platesStoring the Liebert FS for Delayed Installation Positioning the Liebert FSMoving the Liebert FS Manuals Serial Number Model Number PlatesFront Right Side 12-100120-09 TopBottom Internal layout Front Right Side Door open Panel removedCabinet Floor Mounting Floor Mounting BracketFront of Liebert FS Mounting ToolsConcrete, Masonry or Stone Floor Mounting Instructions Checking hole depth Bolt securing bracket to cabinet 12.7mm Floor to FlangeMounting front bolts-front side of cabinet Bubble levelWood Floor Mounting Wood Floor Mounting PartsWood Floor Mounting Tools Wood Floor Mounting InstructionsRaised Floor Mounting Instructions Raised Floor Mounting Raised Floor Mounting KitRaised Floor Mounting Tools Wiring Connections General Wiring ConsiderationsFront RearControl DC and Ground Connections Communication Access Panel Circuit Breaker Mounting PlateGround Wire Gauge Tightening Torque Approximate metric Inch Ground ConnectionsTightening torque for ground connection PoundsAC Auxiliary Control Power Supply Connections Service panel locationFused disconnect Terminal Neutral Line GroundStartup Considerations Remote monitoring DCM connections inside cabinet front doorDetailed System Description Liebert FS front viewPower Conversion Module System Module DescriptionControl Panel UPS Interconnection KitPower System Electrical system schematic Flywheel ModuleBattery Input System PerformanceVersatile Interface Board VIB User interfaces Control PanelData Collection Module DCM Igbt Power Conversion Module PCM Magnetic Levitation Module MLM Active Magnetic Levitation HardwareAxial Electromagnet Upper RadialRotor/Flywheel-Rotating Group Motor GeneratorVacuum System Vacuum system operationTemperature Flywheel Sensors SpeedCabinet System SafetyOuter Housing Rotating Group Inner Housing Coolant List of System User-Configurable Parameters Regulation Voltage Delta During Discharge Vreg Delta Max Charge Current Voltage Behavior Current SinkModes of Operation Vreg delta help screenOFF Mode Standby ModeStartup Mode UPS DC Bus Voltage = VchargeVoltage ≥ Vcharge Charge ModeReady Mode Following a Liebert FS Discharge Down to SOC = 0% Discharge ModeShutdown Mode Fault Mode Following a User CommandCoast Mode KEY # Mode Description Typical operation modesMaintenance and Reliability Access System History Operator ControlsSystem Status Indicators System Mode IndicatorsControl Panel Control panel keyboard layout refer to FigureMain screen function descriptions System Mode Indicators System Status IndicatorsSystem status indicators Operation modesDisabled UninstalledOther Status Indicators OperativeSecurity Access Menu Tree and NavigationMenu tree System Setup and Parameter Access Navigation and Operation of Control Panel2VREG View Time/DateHistory TemperaturesVoltages 123 01 03/10/05 1143 W02 03/10/05 1037 W 03 02/24/05 0403 WOptions Network-Requires DCM Option 192.168.1.155255.255.255.0 192.168.1.1Security ElectricalVitals Password screens Change passwordAbout ToolsCopyright Appl PRI-3.00 SEC-3.01 BL PRI-3.02 SEC-3.01 001 FM S/N MLM S/N 0001 PCM S/N 0002 SO# 123-456-7Inspection before Initial System Startup Initial System Startup ProcedureSystem Startup Control Parameters Setup at Initial System Startup Control Parameter Value DefaultControl parameters Software versionsRegular Startup Procedure Powering Up the Liebert FSBooting Up Inspection Before Regular StartupShutdown Procedure Validation of Control Parameters SetupInitiating Liebert FS Startup Sequence Liebert FS Startup SequenceSafety Precautions Liebert Global Services Routine MaintenanceMaintenance Schedule Maintenance scheduleRecord Log FrequencyTorque specifications unless otherwise labeled Optional Air FiltersTorque Requirements Detecting Trouble Reporting a Problem Corrective Actions Recommended Test Equipment Limited Life ComponentsGeneral User level menuCharge Button F5Meaning / Possible Causes Troubleshooting Label AuxpowerMore information Fault Clear Button F3 Button F5 FaultsBus Power Faults-causes and responses BUS Current OffsetTroubleshooting Fault Label Troubleshooting Action Appendix A.1 Wiring Connections Appendix A.1.1 General Wiring ConsiderationsKey to UPS model interconnection Liebert FS Model # Use With Liebert UPSFront Rear Top view of Liebert FS Cabinet with UPS interconnection kitLiebert FS Positive Terminal Negative Appendix A.1.2 DC Power ConnectionsCircuit Breaker Torque Liebert Series 610/600T/600 model ratings UPS Output Rating KVAYellow Blue Two rows Row for Liebert FS Software Control Parameter settings Liebert FS Software Control Parameter SettingLiebert Npower model ratings Liebert FS Npower UPSOutput RatingSee Table Liebert FS Software Setting Control ParameterLiebert FS Software Control Parameters UPS Interconnection Kits List of Liebert Series 300 models ratings Liebert Series 300 UPSLiebert Series 300 status/control terminal block wiring 395VDC Appendix A.5.1 Description-HiPulse UPS Interconnection Kit Liebert HiPulse model ratingsAppendix A.5.3 IKIT-A05 DC Power Connections Liebert FS positive terminal Liebert FS negative terminalAppendix A.5.5 Single Liebert FS on UPS DC Bus UPS Output Rating kVA 120Multiple Liebert FS Parallel Operation-Regular Configuration Appendix B.2 DCM Installation and Configuration Appendix B.1.2 FeaturesAppendix B.2.1 Installation Appendix B.1 General InformationLAN Connection Power Connection Appendix B.2.2 DCM Requirements192.168.1.155 255.255.255.0192.168.1.1 192.168.1.13Enter IP Address Appendix B.2.3 Accessing the DCMAppendix B.2.4 Configuring DCM System Parameters Appendix B.3.2 Status and Detailed Status Screens Appendix B.3 DCM OperationAppendix B.3.1 Logging into the DCM Appendix B.3.3 Datafiles Screen Datafiles screenAppendix B.4 DCM Troubleshooting Appendix B.4.1 DCM Troubleshooting PrinciplesAppendix B.4.2 Resetting the DCM TroubleshootingAppendix C.1 General Information-Versatile Interface Board Appendix C.1.1 Versatile Interface Board OverviewAppendix C.1.2 VIB Features VIB I/O functions Interface VIB Designation DescriptionLabel X20 O DesignationsAppendix C.2 VIB Installation and Configuration Appendix C.2.1 VIB InstallationAppendix C.2.3 VIB Input Specifications Appendix C.2.4 VIB Output SpecificationsAppendix C.3 VIB Operation Appendix C.4 Troubleshooting the VIB Appendix C.4.2 VIB in Disabled or Not Available StateAppendix C.4.1 UIB State Not Displayed on the Front Panel Appendix C.4.3 Inputs Not RecognizedSubmittal documents accompanying Liebert FS Storage Solution Flywheel Storage SolutionAppendix D.1 Liebert FS Flywheel Submittal Document Matrix No UVR, circuit breaker to terminal block wiring Appendix D.2 Other Liebert FS DrawingsElectrical connections Electrical system block diagram 24 UVR, circuit breaker to terminal block wiring 48 UVR, circuit breaker to terminal block wiringOutline drawing, Liebert FS cabinet Fused Disconnect Liebert FS Control wiring-external interconnect diagram, Liebert FS cabinet to Liebert Series 610 UPS moduleElevation drawing, Liebert FS cabinet with shipping package Elevation drawing-Liebert FS cabinet Front124 Liebert FS cabinet with optional power terminal block Cabinet Mechanical127 Liebert FS Systems Parallel + GND 138One-line module SystemsWith factory CircuitLiebert UPS Module 401 Parallel with a LiebertUPSUnits Liebert UPS Module Liebert UPS Module Wiring, multiple units Status/controlWiring specifications, Liebert FS and Liebert Series Wiring specifications, Liebert FS and Liebert Npower Wiring specifications, Liebert FS and Liebert Series Wiring specifications, Liebert FS and Liebert HiPulse 29-1/2 749mm Drill Template Dwg Cabinet Come with Liebert FS block diagram Power line diagram Liebert FS Cabinet Phase Unit N Input Bus + Bus Ground Bus UPS cable entry-bottomLiebert FS Cabinet Phase Unit N Input UPS cable entry-topTOP View Appendix E.0 Specifications Technical specificationsAppendix E.1 Ground Test Procedure Items RequiredAppendix F.2 Backup AC Power Supply Specification Appendix F.3 Recommended Backup Power Supply ConfigurationAppendix F.1 Overview Frequency 50 to 60HzBattery Liebert FS Pack Grid supply DC busAppendix F.3.2 Operating the Liebert FS Without Batteries GridSupply Output DistributionAppendix F.4 Scenarios Liebert FS Flywheel moduleAuxiliary Backup AC Power Supply 154 Page Ne t ItiTi n That