Emerson SERIES 600T Appendix C.4 Troubleshooting the VIB, Appendix C.4.3 Inputs Not Recognized

Page 124

Versatile Interface Board

Appendix C.4 Troubleshooting the VIB

Appendix C.4.1 UIB State Not Displayed on the Front Panel

Check that no other faults are present on the display panel.

Call Liebert for instructions on how to enable the VIB functionality.

Appendix C.4.2 VIB in “Disabled” or “Not Available” State

Attempt to enable the VIB by pressing F6 (Setup Parameters), then F3 (UIB Enable).

Verify that the cable to the VIB is plugged in properly.

Verify power is present on the Auxiliary I/O board. This is indicated by illumination of LED “LD2”.

Verify power is provided to the UIB. This is indicated by illumination of “LD1” on the Auxiliary I/O board and “LD21Pentagon on the UIB. Note that “LD2”on the Auxiliary I/O board will be illu- minated only if the UIB is connected.

Check the continuity of the cable from pin to pin.

Appendix C.4.3 Inputs Not Recognized

Verify power is present at the VIB.

Verify the VIB is enabled on the display panel.

Verify that the proper voltage is being supplied to the input.

Verify that the LED indicator corresponding to the input illuminates when the input signal is applied.

Appendix C.4.4 Outputs Not Asserted

Verify power is present at the VIB.

Verify the VIB is enabled on the display panel.

Verify that the LED indicator corresponding to the output illuminates when the output is asserted.

112

Image 124
Contents Liebert FS DC Energy Storage System Page Table of Contents System Overview OperationMaintenance TroubleshootingAppendix A.0 UPS Interconnection Kits Appendix B.0 Data Collection ModuleAppendix D.0 Installation Drawings Appendix E.0 SpecificationsAppendix F.0 Auxiliary Backup AC Power Supply Appendix C.0 Versatile Interface BoardFigures Vii Versatile Interface Board mounted in the Liebert FS 110 Tables Page Important Safety Instructions Safety Precautions Safety Considerations General InformationRequesting Assistance from Liebert System informationGeneral System Description Liebert FSUtility Power DC Bus LoadsLiebert FS Unit Liebert FS Unit 1 Liebert FS UnitBattery N General SpecificationsGeneral system specifications LiebertFeatures and Benefits Key Technological FeaturesKey Customer Benefits Applicable Standards and CertificationKW-sec delivered GT model, 510 VDC, with filter Bypass Utility Static SwitchRectifier System Location Environmental ConsiderationsFlooring Requirements Electrical ConsiderationsAC Power Connections Status/Control ConnectionsGrounding Connections Remote Monitoring Connections-OptionalUnloading Inspection Before Removal From the Truck14623 Handling UnpackingLifting the Liebert FS cabinet Removing the metal support platesStoring the Liebert FS for Delayed Installation Positioning the Liebert FSMoving the Liebert FS Manuals Serial Number Model Number PlatesBottom TopFront Right Side 12-100120-09 Internal layout Front Right Side Door open Panel removedCabinet Floor Mounting Floor Mounting BracketConcrete, Masonry or Stone Floor Mounting Instructions Mounting ToolsFront of Liebert FS Checking hole depth Bolt securing bracket to cabinet 12.7mm Floor to FlangeMounting front bolts-front side of cabinet Bubble levelWood Floor Mounting Wood Floor Mounting PartsWood Floor Mounting Tools Wood Floor Mounting InstructionsRaised Floor Mounting Tools Raised Floor Mounting Raised Floor Mounting KitRaised Floor Mounting Instructions Wiring Connections General Wiring ConsiderationsFront RearControl DC and Ground Connections Communication Access Panel Circuit Breaker Mounting PlateGround Wire Gauge Tightening Torque Approximate metric Inch Ground ConnectionsTightening torque for ground connection PoundsAC Auxiliary Control Power Supply Connections Service panel locationFused disconnect Terminal Neutral Line GroundStartup Considerations Remote monitoring DCM connections inside cabinet front doorDetailed System Description Liebert FS front viewPower Conversion Module System Module DescriptionControl Panel UPS Interconnection KitPower System Electrical system schematic Flywheel ModuleBattery Input System PerformanceData Collection Module DCM User interfaces Control PanelVersatile Interface Board VIB Igbt Power Conversion Module PCM Magnetic Levitation Module MLM Active Magnetic Levitation HardwareAxial Electromagnet Upper RadialRotor/Flywheel-Rotating Group Motor GeneratorVacuum System Vacuum system operationTemperature Flywheel Sensors SpeedOuter Housing Rotating Group Inner Housing Coolant System SafetyCabinet List of System User-Configurable Parameters Regulation Voltage Delta During Discharge Vreg Delta Max Charge Current Voltage Behavior Current SinkModes of Operation Vreg delta help screenOFF Mode Standby ModeStartup Mode UPS DC Bus Voltage = VchargeReady Mode Charge ModeVoltage ≥ Vcharge Shutdown Mode Discharge ModeFollowing a Liebert FS Discharge Down to SOC = 0% Coast Mode Following a User CommandFault Mode KEY # Mode Description Typical operation modesMaintenance and Reliability Access System History Operator ControlsSystem Status Indicators System Mode IndicatorsControl Panel Control panel keyboard layout refer to FigureMain screen function descriptions System Mode Indicators System Status IndicatorsSystem status indicators Operation modesDisabled UninstalledOther Status Indicators OperativeSecurity Access Menu Tree and NavigationMenu tree System Setup and Parameter Access Navigation and Operation of Control Panel2VREG View Time/DateVoltages TemperaturesHistory 123 01 03/10/05 1143 W02 03/10/05 1037 W 03 02/24/05 0403 WOptions Network-Requires DCM Option 192.168.1.155255.255.255.0 192.168.1.1Vitals ElectricalSecurity Password screens Change passwordAbout ToolsCopyright Appl PRI-3.00 SEC-3.01 BL PRI-3.02 SEC-3.01 001 FM S/N MLM S/N 0001 PCM S/N 0002 SO# 123-456-7System Startup Initial System Startup ProcedureInspection before Initial System Startup Control Parameters Setup at Initial System Startup Control Parameter Value DefaultControl parameters Software versionsRegular Startup Procedure Powering Up the Liebert FSBooting Up Inspection Before Regular StartupShutdown Procedure Validation of Control Parameters SetupInitiating Liebert FS Startup Sequence Liebert FS Startup SequenceSafety Precautions Liebert Global Services Routine MaintenanceMaintenance Schedule Maintenance scheduleRecord Log FrequencyTorque specifications unless otherwise labeled Optional Air FiltersTorque Requirements Detecting TroubleReporting a Problem Corrective ActionsRecommended Test Equipment Limited Life ComponentsGeneral User level menuCharge Button F5Meaning / Possible Causes Troubleshooting Label AuxpowerBus Power FaultsMore information Fault Clear Button F3 Button F5 Faults-causes and responses BUS Current OffsetTroubleshooting Fault Label Troubleshooting Action Appendix A.1 Wiring Connections Appendix A.1.1 General Wiring ConsiderationsKey to UPS model interconnection Liebert FS Model # Use With Liebert UPSFront Rear Top view of Liebert FS Cabinet with UPS interconnection kitCircuit Breaker Torque Appendix A.1.2 DC Power ConnectionsLiebert FS Positive Terminal Negative Liebert Series 610/600T/600 model ratings UPS Output Rating KVAYellow Blue Two rows Row for Liebert FS Software Control Parameter settings Liebert FS Software Control Parameter SettingLiebert Npower model ratings Liebert FS Npower UPSOutput RatingLiebert FS Software Control Parameters Liebert FS Software Setting Control ParameterSee Table UPS Interconnection Kits List of Liebert Series 300 models ratings Liebert Series 300 UPSLiebert Series 300 status/control terminal block wiring 395VDC Appendix A.5.1 Description-HiPulse UPS Interconnection Kit Liebert HiPulse model ratingsAppendix A.5.3 IKIT-A05 DC Power Connections Liebert FS positive terminal Liebert FS negative terminalAppendix A.5.5 Single Liebert FS on UPS DC Bus UPS Output Rating kVA 120Multiple Liebert FS Parallel Operation-Regular Configuration Appendix B.2 DCM Installation and Configuration Appendix B.1.2 FeaturesAppendix B.2.1 Installation Appendix B.1 General InformationLAN Connection Power Connection Appendix B.2.2 DCM Requirements192.168.1.155 255.255.255.0192.168.1.1 192.168.1.13Appendix B.2.4 Configuring DCM System Parameters Appendix B.2.3 Accessing the DCMEnter IP Address Appendix B.3.1 Logging into the DCM Appendix B.3 DCM OperationAppendix B.3.2 Status and Detailed Status Screens Appendix B.3.3 Datafiles Screen Datafiles screenAppendix B.4 DCM Troubleshooting Appendix B.4.1 DCM Troubleshooting PrinciplesAppendix B.4.2 Resetting the DCM TroubleshootingAppendix C.1 General Information-Versatile Interface Board Appendix C.1.1 Versatile Interface Board OverviewAppendix C.1.2 VIB Features VIB I/O functions Interface VIB Designation DescriptionLabel X20 O DesignationsAppendix C.2 VIB Installation and Configuration Appendix C.2.1 VIB InstallationAppendix C.2.3 VIB Input Specifications Appendix C.2.4 VIB Output SpecificationsAppendix C.3 VIB Operation Appendix C.4 Troubleshooting the VIB Appendix C.4.2 VIB in Disabled or Not Available StateAppendix C.4.1 UIB State Not Displayed on the Front Panel Appendix C.4.3 Inputs Not RecognizedAppendix D.1 Liebert FS Flywheel Submittal Document Matrix Storage Solution Flywheel Storage SolutionSubmittal documents accompanying Liebert FS No UVR, circuit breaker to terminal block wiring Appendix D.2 Other Liebert FS DrawingsElectrical connections Electrical system block diagram 24 UVR, circuit breaker to terminal block wiring 48 UVR, circuit breaker to terminal block wiringOutline drawing, Liebert FS cabinet Fused Disconnect Liebert FS Control wiring-external interconnect diagram, Liebert FS cabinet to Liebert Series 610 UPS moduleElevation drawing, Liebert FS cabinet with shipping package Elevation drawing-Liebert FS cabinet Front124 Liebert FS cabinet with optional power terminal block Cabinet Mechanical127 Liebert FS Systems Parallel + GND 138One-line module SystemsWith factory CircuitLiebert UPS Module 401 Units LiebertUPSParallel with a Liebert UPS Module Liebert UPS Module Wiring, multiple units Status/controlWiring specifications, Liebert FS and Liebert Series Wiring specifications, Liebert FS and Liebert Npower Wiring specifications, Liebert FS and Liebert Series Wiring specifications, Liebert FS and Liebert HiPulse 29-1/2 749mm Drill Template Dwg Cabinet Come with Liebert FS block diagram Power line diagram Liebert FS Cabinet Phase Unit N Input Bus + Bus Ground Bus UPS cable entry-bottomLiebert FS Cabinet Phase Unit N Input UPS cable entry-topTOP View Appendix E.0 Specifications Technical specificationsAppendix E.1 Ground Test Procedure Items RequiredAppendix F.2 Backup AC Power Supply Specification Appendix F.3 Recommended Backup Power Supply ConfigurationAppendix F.1 Overview Frequency 50 to 60HzBattery Liebert FS Pack Grid supply DC busAppendix F.3.2 Operating the Liebert FS Without Batteries GridSupply Output DistributionAppendix F.4 Scenarios Liebert FS Flywheel moduleAuxiliary Backup AC Power Supply 154 Page Ne t ItiTi n That
Related manuals
Manual 84 pages 14.4 Kb

Series 600, SERIES 600T specifications

The Emerson SERIES 600T, as part of the SERIES 600 line, is a sophisticated device designed to meet the demands of industrial automation and control systems. Renowned for its reliability and versatility, the SERIES 600T excels in various applications across multiple sectors, including oil and gas, chemical processing, and power generation.

One of the most significant features of the SERIES 600T is its advanced measuring capability. It offers exceptional accuracy, typically within ±0.1% of the full scale. This precision makes it suitable for critical applications where measurement integrity is paramount. The SERIES 600T is also equipped with intelligent diagnostics that can predict and monitor the health of the unit, enabling proactive maintenance and minimizing downtime. This technological advancement improves both operational efficiency and safety.

Another standout characteristic is the device's robust construction designed to withstand harsh environments. The SERIES 600T is made with durable materials that provide resistance to corrosion, vibration, and temperature extremes, making it an excellent choice for rugged industrial applications. Coupled with its IP67 rating, the device is fully sealed against dust and moisture, ensuring long-term reliability in challenging conditions.

The SERIES 600 line employs cutting-edge communication protocols, including HART and Foundation Fieldbus, facilitating seamless integration into various control systems. This capability ensures that users can easily access real-time data and manage devices remotely, significantly enhancing operational efficiency.

Additionally, the SERIES 600T supports a wide range of process connections and configurations, catering to diverse installation needs. This adaptability allows for quick deployments and minimizes the time required for system changes or upgrades.

With easy-to-read displays and user-friendly interfaces, operators can quickly interpret data and metrics from the SERIES 600T. This intuitive design helps reduce the learning curve for new users, further underlining the device's legacy of reliability and efficiency.

In essence, the Emerson SERIES 600T exemplifies cutting-edge technology in the realm of industrial measurement and automation. Its combination of accuracy, durability, diagnostic capabilities, and ease of integration makes it an ideal choice for industries that prioritize reliability and precision in their operations. As industrial processes continue to evolve, devices like the SERIES 600T will undoubtedly play a crucial role in advancing efficiency and productivity in various sectors.