Emerson 208V, 10-30kVA installation manual Preliminary Checks, UPS Location

Page 11

Installation

1.2.1Storing for Delayed Installation

If the equipment will not be installed immediately, it must be stored indoors where the humidity is no higher than 90% and the temperature is no higher than 104°F (40°C). The storage area must protect the NX from excessive moisture (see 6.2 - UPS Environmental).

! CAUTION

If the UPS must remain disconnected from power for more than six (6) months, the battery must be recharged before use. To charge the batteries, the unit must be connected to utility power and started up—the charger operates only while the NX is operating.

! CAUTION

When batteries are installed in the UPS or are cabinet-mounted adjacent to the UPS unit, the battery—not the UPS—dictates the designed maximum ambient temperature.

1.3Preliminary Checks

1.3.1Identification

The equipment supplied has an identification tag on the back of the main door listing the type and size of the UPS.

1.4UPS Location

1.4.1Positioning the UPS

Choose a location for the UPS that offers:

Easy connection to inputs, outputs and auxiliary equipment

Enough space to service the UPS

Air circulation sufficient to expel heat produced by UPS

Protection against moisture and excessive humidity

Protection against dust and other particulate matter

Compliance with fire prevention regulations and practices

Operating environment temperature of 74-80°F (23-27°C) for maximum battery efficiency

1.4.2Environmental Considerations

Before installing the NX, verify that the UPS room satisfies the environmental conditions stipulated in 6.2 - UPS Environmental, paying particular attention to the ambient temperature and air exchange system.

The UPS unit should be installed in a cool, dry, clean-air environment with adequate ventilation to keep the ambient temperature within the specified operating range 32°F to 104°F (0°C to 40°C).

For optimal UPS and battery system performance and service life, maintain the operating tempera- ture within the range of 74-80°F, (23-27°C).

The NX UPS cooled by internal fans. Cooling air enters the unit through the front of the unit and is exhausted out the top. To permit proper air flow and prevent overheating, do NOT block or cover the ventilation openings or blow air down onto the unit. Ventilation clearance above the unit must be a minimum of 24 in. (610mm).

See Table 9 for details on heat dissipation.

Battery Location

Temperature is a major factor in determining battery life and capacity. Battery manufacturers recom- mend an operating temperature of 77°F (25°C). Ambient temperatures warmer than this reduce bat- tery life; temperatures below this reduces battery capacity. In a typical installation, battery temperature should be maintained between 74°F and 80°F (23-27°C). Batteries should be placed where there are no main heat sources or air inlets to prevent portions of batteries from being either much warmer or much cooler than other parts of the batteries.

5

Image 11
Contents Liebert NX UPS Page Table of Contents Options Maintenance Bypass CabinetUPS Specifications Figures Tables Important Safety Instructions Battery Cabinet Precautions Glossary of Symbols Internal Inspections External InspectionsUPS Location Preliminary ChecksFinal Position Considerations in Moving the NXMechanical Considerations Special Considerations for 1+N Systems10-30kVA UPS Floor InstallationClearances Cable EntryOptional Cabinets Maintenance Bypass CabinetBattery LiebertLug Size and Torque Requirements Power CablingCable Rating Cabling Guidelines UPS Input ConfigurationBussmann Cable ConnectionsSystem Output Safety GroundProtective Devices UPS Rectifier and Bypass Input SupplyDual Input Connections Cabling ProcedureOutput System Connections-Ensure Correct Phase Rotation Common Input ConnectionsControl Cables Internal UPS Battery ConnectionsMonitor Board Features Input Dry Contacts Dry ContactsBCB box interface Maintenance Bypass Cabinet InterfaceMaintenance bypass cabinet interface BCB Box InterfaceEPO input contact relays Output Dry ContactsEPO Input-Optional Firmware Before M200 Output dry contact relaysFirmware M200 or Later UPS Batteries SafetyIntroduction Removable retainer Tray handle Insulated post for cabling External Battery Cabinet InstallationMatching Battery Cabinets Connecting the BatteriesTop cable entry Batteries BCB plate Top cable entry Battery trays BCB plate and BCBBattery tray support Service shelf Installation Considerations Ends of supports Battery tray supports attachTo interior surface of NX Front door note notchedNon-Standard Batteries Connecting the Battery Cabinet to the UPSNormal UPS Mode Bypass SwitchLocating the Cabinet Bypass ModeMaintenance Mode Cable InstallationInput/Output Wiring Power Cable InstallationMaintenance bypass control wire location Line up cabinets so that mounting holes are aligned Bolting Cabinets TogetherLBS Cable DBS Cable and SettingsLoad Bus Synchronization Performance RequirementsGeneral Configuring Parallel System OperationFeatures of Parallel System Installing Parallel System Auxiliary Dry Contact Cables Power CablesInterconnecting Parallel Control Cables Parallel System Control CablesInput Distribution Normally Closed EPO Normally Open EPOCircuit Breaker Battery Circuit Breaker BoxAvailable battery circuit breaker boxes DimensionsMidpoint Busbar Detail DPN U3813078 Rev. N Front ViewBottom View Conformity and Standards UPS Mechanical CharacteristicsEnvironmental characteristics Mechanical characteristicsUPS terminal UPS Electrical CharacteristicsDC Intermediate Circuit Battery Manufacturers and ModelsInput Rectifier Time Load Inverter OutputInverter output Bypass Input Bypass inputInstallation Drawings Main components-typical unit Dimensions -top and bottom viewsCable connections Location of internal batteries Battery 417mm 186mm 687mmW503 to W502 W501 3pcs W500 18pcs W506 to W507 W510 to W511 W502 to W503W504 to W505 W511 to W510 W507 to W506 W509 to W508 W505 to W504 W508 to W509Run From Conductors Liebert -supplied interconnect wiringRefer to for key to interconnection Maintenance Bypass interconnection A00, BR0 Liebert-supplied interconnect wiringRun From Conductors Cabinet Type Distribution Cabinet Load AC Connection Neutral Ground Distribution CabinetIsolated Ground Interconnect wiring-1+N Type a connection to NX Interconnect wiring-1+N Type A1 connection to NX Utility AC Source UPS #1-UPS #4 Module AC Input Interconnect wiring-1+N Type B connection to NXInterconnect wiring-1+N Type B1 connection to NX Ph a ,B, C Load Interconnect wiring-1+N Type C connection to NXPh A, B, C-system Input Ph a ,B, C UPS Input+ N Cabinet Side View + N Parallel Cabinet Interconnect wiring-1+N Type C1 connection to NXLineup detail-1+N Type D connection to NX Interconnect wiring-1+N Type D connection to NXUPS Lug Size and Torque Requirements Torque specificationsBattery torque rating Initial Torque Annual Torque Battery In-lb N-mCurrent Rating a OCP CB Size a Maintenance bypass cabinet electrical data single inputCurrent CB Size a Current Rating a CB Size a Maintenance bypass cabinet electrical data dual inputMulti-module bypass cabinet electrical data SR0, W00 200A300A TR0 E00, FR0G01, GR1 208 104 125 250 400 UR0, Y00 MR1208 280 400 222 300 210 250 167 225 140 175 111 150 Maintenance bypass cabinet lug sizes Maintenance Bypass Cabinet Style, lb. kg Rating Battery cabinet physical characteristicsMaintenance Bypass Cabinet weights Distance to connection points on the NX UPS Maintenance bypass cabinet dimensionsMulti-module paralleling cabinet dimensions Cable Lengths Floor to Connection Point Inside UPSSpecifications and Technical Data Specifications and Technical Data Page That Ne tIti Ti n
Related manuals
Manual 80 pages 58.87 Kb Manual 48 pages 54.46 Kb

10-30kVA, 208V specifications

The Emerson 10-30 kVA, 208V uninterruptible power supply (UPS) solution is a robust system designed to provide reliable power protection for critical applications in commercial and industrial settings. This UPS is ideal for safeguarding IT equipment, communication systems, and other sensitive electronics against power disturbances and interruptions.

One of the standout features of the Emerson 10-30 kVA UPS is its modular design, allowing for flexibility and scalability. This means that as the power needs of a facility grow, the UPS can be easily expanded without requiring a complete system overhaul. This modularity contributes to a more efficient use of resources and minimizes operational costs.

The UPS also incorporates advanced technologies such as double-conversion online architecture, which provides the highest level of power quality. This technology ensures that the output power is consistently clean and stable, effectively eliminating harmful voltage fluctuations and frequency variations. Consequently, connected load receives a pure sine wave output, preventing potential damage or operational issues with sensitive equipment.

Another key feature is the high efficiency rating of the Emerson UPS, which exceeds 95 percent in typical operating conditions. This high efficiency translates to reduced energy costs and a smaller carbon footprint, aligning with modern sustainability goals. The cooling system is designed to be efficient as well, ensuring optimal performance while maintaining a compact footprint.

The user-friendly interface enhances operability, featuring an intuitive LCD display that allows for easy monitoring of critical power parameters. Users can access real-time data related to battery health, load levels, and operational status, which aids in effective management of the power supply.

Battery management is another critical aspect of the Emerson UPS. It employs advanced battery management technologies to ensure optimal battery life and performance. Features such as intelligent battery testing and monitoring help predict potential battery failures before they occur, allowing for proactive maintenance and minimized downtime.

In summary, the Emerson 10-30 kVA, 208V UPS offers a combination of modularity, high efficiency, advanced technologies, and effective power management features that cater to the demanding needs of critical applications. With its reliable performance and user-friendly operation, this UPS solution is an excellent choice for organizations looking to protect their valuable equipment from power disturbances.