Emerson 10-30kVA, 208V Non-Standard Batteries, Connecting the Battery Cabinet to the UPS

Page 30

Battery Installation

3.4.4Connecting the Battery Cabinet to the UPS

After the battery cabinet equipment has been positioned and secured for operation and the batteries have been connected, connect the power cables as described below. (See Figure 34.)

1.Verify that all incoming high and low voltage power circuits are de-energized and locked out or tagged out before installing cables or making any electrical connections.

2.Remove the UPS left side panel to gain access to the equipment ground busbar.

3.Remove the external battery terminal block plate on the lower left side of the UPS behind the front door.

4.Remove the battery cabinet front panel to gain access to the connection bars.

5.Connect the safety ground and any necessary bonding ground cables to the copper ground busbar. (example: UPS located on the bottom of the equipment below the power connections).

All cabinets in the UPS system must be connected to the user's ground connection.

NOTE

The grounding and neutral bonding arrangement must be in accordance with the National Electrical Code and all applicable local codes.

6.Connect the system battery cables from the UPS battery terminals (+ N -) to battery cabinet BCB (+ N -) as shown in Figure 34. Be sure that the battery connections are made with the right polarity, and tighten the connections to 44 lb-in. (5 N-m) (M6 Bolt). Do not close the battery circuit breaker before the equipment has been commissioned.

7.Connect supplied auxiliary control cable to pins J10.2 and J10.3 on the U2 monitoring board (see 2.3 - Dry Contacts). Add a jumper wire between J10.3 and J10.4.

3.5Non-Standard Batteries

When batteries other than a matching battery cabinet are used, a remote battery disconnect switch with overcurrent protection is required per the National Electrical Code. Contact your local Liebert sales representative about this option.

Install battery racks, cabinets and batteries in accordance with the manufacturer's instructions.

Verify that the battery area has adequate ventilation and battery operating temperature complies with the manufacturer's specifications and with all applicable national and local codes.

If you have any questions concerning batteries, battery racks or accessories, contact Liebert Global Services at 1-800-543-2378.

24

Image 30
Contents Liebert NX UPS Page Table of Contents Maintenance Bypass Cabinet UPS SpecificationsOptions Figures Tables Important Safety Instructions Battery Cabinet Precautions Glossary of Symbols External Inspections Internal InspectionsPreliminary Checks UPS LocationSpecial Considerations for 1+N Systems Considerations in Moving the NXMechanical Considerations Final PositionCable Entry Floor InstallationClearances 10-30kVA UPSLiebert Maintenance Bypass CabinetBattery Optional CabinetsPower Cabling Cable RatingLug Size and Torque Requirements UPS Input Configuration Cabling GuidelinesCable Connections BussmannUPS Rectifier and Bypass Input Supply Safety GroundProtective Devices System OutputCommon Input Connections Cabling ProcedureOutput System Connections-Ensure Correct Phase Rotation Dual Input ConnectionsInternal UPS Battery Connections Monitor Board FeaturesControl Cables Dry Contacts Input Dry ContactsBCB Box Interface Maintenance Bypass Cabinet InterfaceMaintenance bypass cabinet interface BCB box interfaceOutput dry contact relays Output Dry ContactsEPO Input-Optional Firmware Before M200 EPO input contact relaysFirmware M200 or Later Safety IntroductionUPS Batteries Connecting the Batteries External Battery Cabinet InstallationMatching Battery Cabinets Removable retainer Tray handle Insulated post for cablingTop cable entry Battery trays BCB plate and BCB Battery tray support Service shelfTop cable entry Batteries BCB plate Installation Considerations Front door note notched Battery tray supports attachTo interior surface of NX Ends of supportsConnecting the Battery Cabinet to the UPS Non-Standard BatteriesBypass Switch Normal UPS ModeCable Installation Bypass ModeMaintenance Mode Locating the CabinetPower Cable Installation Input/Output WiringMaintenance bypass control wire location Bolting Cabinets Together Line up cabinets so that mounting holes are alignedPerformance Requirements DBS Cable and SettingsLoad Bus Synchronization LBS CableConfiguring Parallel System Operation Features of Parallel SystemGeneral Installing Parallel System Parallel Control Cables Parallel System Control Cables Power CablesInterconnecting Auxiliary Dry Contact CablesInput Distribution Normally Open EPO Normally Closed EPODimensions Battery Circuit Breaker BoxAvailable battery circuit breaker boxes Circuit BreakerFront View Bottom ViewMidpoint Busbar Detail DPN U3813078 Rev. N Mechanical characteristics UPS Mechanical CharacteristicsEnvironmental characteristics Conformity and StandardsUPS Electrical Characteristics UPS terminalBattery Manufacturers and Models Input RectifierDC Intermediate Circuit Bypass Input Bypass input Inverter OutputInverter output Time LoadInstallation Drawings Dimensions -top and bottom views Main components-typical unitCable connections Battery 417mm 186mm 687mm Location of internal batteriesW505 to W504 W508 to W509 W501 3pcs W500 18pcs W506 to W507 W510 to W511 W502 to W503W504 to W505 W511 to W510 W507 to W506 W509 to W508 W503 to W502Liebert -supplied interconnect wiring Refer to for key to interconnectionRun From Conductors Maintenance Bypass interconnection Liebert-supplied interconnect wiring Run From Conductors Cabinet TypeA00, BR0 Distribution Cabinet Isolated GroundDistribution Cabinet Load AC Connection Neutral Ground Interconnect wiring-1+N Type a connection to NX Interconnect wiring-1+N Type A1 connection to NX Interconnect wiring-1+N Type B connection to NX Utility AC Source UPS #1-UPS #4 Module AC InputInterconnect wiring-1+N Type B1 connection to NX Ph a ,B, C UPS Input Interconnect wiring-1+N Type C connection to NXPh A, B, C-system Input Ph a ,B, C LoadInterconnect wiring-1+N Type C1 connection to NX + N Cabinet Side View + N Parallel CabinetInterconnect wiring-1+N Type D connection to NX Lineup detail-1+N Type D connection to NXUPS Initial Torque Annual Torque Battery In-lb N-m Torque specificationsBattery torque rating Lug Size and Torque RequirementsMaintenance bypass cabinet electrical data single input Current CB Size aCurrent Rating a OCP CB Size a Maintenance bypass cabinet electrical data dual input Current Rating a CB Size aMulti-module bypass cabinet electrical data 200A 300ASR0, W00 E00, FR0 G01, GR1TR0 208 104 125 250 400 MR1 UR0, Y00208 280 400 222 300 210 250 167 225 140 175 111 150 Maintenance bypass cabinet lug sizes Battery cabinet physical characteristics Maintenance Bypass Cabinet weightsMaintenance Bypass Cabinet Style, lb. kg Rating Cable Lengths Floor to Connection Point Inside UPS Maintenance bypass cabinet dimensionsMulti-module paralleling cabinet dimensions Distance to connection points on the NX UPSSpecifications and Technical Data Specifications and Technical Data Page Ti n Ne tIti That
Related manuals
Manual 80 pages 58.87 Kb Manual 48 pages 54.46 Kb

10-30kVA, 208V specifications

The Emerson 10-30 kVA, 208V uninterruptible power supply (UPS) solution is a robust system designed to provide reliable power protection for critical applications in commercial and industrial settings. This UPS is ideal for safeguarding IT equipment, communication systems, and other sensitive electronics against power disturbances and interruptions.

One of the standout features of the Emerson 10-30 kVA UPS is its modular design, allowing for flexibility and scalability. This means that as the power needs of a facility grow, the UPS can be easily expanded without requiring a complete system overhaul. This modularity contributes to a more efficient use of resources and minimizes operational costs.

The UPS also incorporates advanced technologies such as double-conversion online architecture, which provides the highest level of power quality. This technology ensures that the output power is consistently clean and stable, effectively eliminating harmful voltage fluctuations and frequency variations. Consequently, connected load receives a pure sine wave output, preventing potential damage or operational issues with sensitive equipment.

Another key feature is the high efficiency rating of the Emerson UPS, which exceeds 95 percent in typical operating conditions. This high efficiency translates to reduced energy costs and a smaller carbon footprint, aligning with modern sustainability goals. The cooling system is designed to be efficient as well, ensuring optimal performance while maintaining a compact footprint.

The user-friendly interface enhances operability, featuring an intuitive LCD display that allows for easy monitoring of critical power parameters. Users can access real-time data related to battery health, load levels, and operational status, which aids in effective management of the power supply.

Battery management is another critical aspect of the Emerson UPS. It employs advanced battery management technologies to ensure optimal battery life and performance. Features such as intelligent battery testing and monitoring help predict potential battery failures before they occur, allowing for proactive maintenance and minimized downtime.

In summary, the Emerson 10-30 kVA, 208V UPS offers a combination of modularity, high efficiency, advanced technologies, and effective power management features that cater to the demanding needs of critical applications. With its reliable performance and user-friendly operation, this UPS solution is an excellent choice for organizations looking to protect their valuable equipment from power disturbances.