Emerson 208V, 10-30kVA installation manual 208 280 400 222 300 210 250 167 225 140 175 111 150

Page 73

Specifications and Technical Data

Table 31 Multi-module bypass cabinet electrical data (continued)

 

 

 

System

System

System

 

 

 

System

 

 

I/P Voltage

Max Input

Input OCP

O/P Voltage

Nominal O/P

Output OCP

Size

Type

kVA

(VAC)

Current

CB Size (A)

(VAC)

Current Rating (A)

CB Size (A)

 

 

30

208

104

125

208

333

500

 

J00, KR0

20

208

70

90

208

222

300

 

15

208

53

70

208

167

225

 

 

 

 

10

208

35

45

208

111

150

 

 

10

208

146

175

208

111

150

 

 

10

220

138

175

208

111

150

4+0

 

10

480

63

80

208

111

150

 

 

10

600

51

70

208

111

150

 

 

15

208

219

300

208

167

225

 

 

15

220

207

250

208

167

225

 

 

15

480

95

125

208

167

225

 

LR1

15

600

76

100

208

167

225

 

20

208

292

400

208

222

300

 

 

 

 

20

220

276

400

208

222

300

 

 

20

480

127

175

208

222

300

 

 

20

600

101

125

208

222

300

 

 

30

208

438

600

208

333

500

 

 

30

220

414

500

208

333

500

 

 

30

480

190

250

208

333

500

 

 

30

600

152

200

208

333

500

 

 

10

220

137

175

208

111

150

 

 

10

480

63

80

208

111

150

 

 

10

600

50

60

208

111

150

 

 

15

220

205

250

208

167

225

 

 

15

480

94

125

208

167

225

 

MR1

15

600

75

90

208

167

225

 

20

220

273

400

208

222

300

 

 

 

 

20

480

125

150

208

222

300

 

 

20

600

100

125

208

222

300

 

 

30

220

410

500

208

333

500

 

 

30

480

188

225

208

333

500

 

 

30

600

150

200

208

333

500

 

 

30

208

421

500

208

333

500

 

UR0, Y00

20

208

280

400

208

222

300

 

15

208

210

250

208

167

225

 

 

 

 

10

208

140

175

208

111

150

67

Image 73
Contents Liebert NX UPS Page Table of Contents UPS Specifications Maintenance Bypass CabinetOptions Figures Tables Important Safety Instructions Battery Cabinet Precautions Glossary of Symbols Internal Inspections External InspectionsUPS Location Preliminary ChecksMechanical Considerations Considerations in Moving the NXSpecial Considerations for 1+N Systems Final PositionClearances Floor InstallationCable Entry 10-30kVA UPSBattery Maintenance Bypass CabinetLiebert Optional CabinetsCable Rating Power CablingLug Size and Torque Requirements Cabling Guidelines UPS Input ConfigurationBussmann Cable ConnectionsProtective Devices Safety GroundUPS Rectifier and Bypass Input Supply System OutputOutput System Connections-Ensure Correct Phase Rotation Cabling ProcedureCommon Input Connections Dual Input ConnectionsMonitor Board Features Internal UPS Battery ConnectionsControl Cables Input Dry Contacts Dry ContactsMaintenance bypass cabinet interface Maintenance Bypass Cabinet InterfaceBCB Box Interface BCB box interfaceEPO Input-Optional Firmware Before M200 Output Dry ContactsOutput dry contact relays EPO input contact relaysFirmware M200 or Later Introduction SafetyUPS Batteries Matching Battery Cabinets External Battery Cabinet InstallationConnecting the Batteries Removable retainer Tray handle Insulated post for cablingBattery tray support Service shelf Top cable entry Battery trays BCB plate and BCBTop cable entry Batteries BCB plate Installation Considerations To interior surface of NX Battery tray supports attachFront door note notched Ends of supportsNon-Standard Batteries Connecting the Battery Cabinet to the UPSNormal UPS Mode Bypass SwitchMaintenance Mode Bypass ModeCable Installation Locating the CabinetInput/Output Wiring Power Cable InstallationMaintenance bypass control wire location Line up cabinets so that mounting holes are aligned Bolting Cabinets TogetherLoad Bus Synchronization DBS Cable and SettingsPerformance Requirements LBS CableFeatures of Parallel System Configuring Parallel System OperationGeneral Installing Parallel System Interconnecting Power CablesParallel Control Cables Parallel System Control Cables Auxiliary Dry Contact CablesInput Distribution Normally Closed EPO Normally Open EPOAvailable battery circuit breaker boxes Battery Circuit Breaker BoxDimensions Circuit BreakerBottom View Front ViewMidpoint Busbar Detail DPN U3813078 Rev. N Environmental characteristics UPS Mechanical CharacteristicsMechanical characteristics Conformity and StandardsUPS terminal UPS Electrical CharacteristicsInput Rectifier Battery Manufacturers and ModelsDC Intermediate Circuit Inverter output Inverter OutputBypass Input Bypass input Time LoadInstallation Drawings Main components-typical unit Dimensions -top and bottom viewsCable connections Location of internal batteries Battery 417mm 186mm 687mmW504 to W505 W511 to W510 W507 to W506 W509 to W508 W501 3pcs W500 18pcs W506 to W507 W510 to W511 W502 to W503W505 to W504 W508 to W509 W503 to W502Refer to for key to interconnection Liebert -supplied interconnect wiringRun From Conductors Maintenance Bypass interconnection Run From Conductors Cabinet Type Liebert-supplied interconnect wiringA00, BR0 Isolated Ground Distribution CabinetDistribution Cabinet Load AC Connection Neutral Ground Interconnect wiring-1+N Type a connection to NX Interconnect wiring-1+N Type A1 connection to NX Utility AC Source UPS #1-UPS #4 Module AC Input Interconnect wiring-1+N Type B connection to NXInterconnect wiring-1+N Type B1 connection to NX Ph A, B, C-system Input Interconnect wiring-1+N Type C connection to NXPh a ,B, C UPS Input Ph a ,B, C Load+ N Cabinet Side View + N Parallel Cabinet Interconnect wiring-1+N Type C1 connection to NXLineup detail-1+N Type D connection to NX Interconnect wiring-1+N Type D connection to NXUPS Battery torque rating Torque specificationsInitial Torque Annual Torque Battery In-lb N-m Lug Size and Torque RequirementsCurrent CB Size a Maintenance bypass cabinet electrical data single inputCurrent Rating a OCP CB Size a Current Rating a CB Size a Maintenance bypass cabinet electrical data dual inputMulti-module bypass cabinet electrical data 300A 200ASR0, W00 G01, GR1 E00, FR0TR0 208 104 125 250 400 UR0, Y00 MR1208 280 400 222 300 210 250 167 225 140 175 111 150 Maintenance bypass cabinet lug sizes Maintenance Bypass Cabinet weights Battery cabinet physical characteristicsMaintenance Bypass Cabinet Style, lb. kg Rating Multi-module paralleling cabinet dimensions Maintenance bypass cabinet dimensionsCable Lengths Floor to Connection Point Inside UPS Distance to connection points on the NX UPSSpecifications and Technical Data Specifications and Technical Data Page Iti Ne tTi n That
Related manuals
Manual 80 pages 58.87 Kb Manual 48 pages 54.46 Kb

10-30kVA, 208V specifications

The Emerson 10-30 kVA, 208V uninterruptible power supply (UPS) solution is a robust system designed to provide reliable power protection for critical applications in commercial and industrial settings. This UPS is ideal for safeguarding IT equipment, communication systems, and other sensitive electronics against power disturbances and interruptions.

One of the standout features of the Emerson 10-30 kVA UPS is its modular design, allowing for flexibility and scalability. This means that as the power needs of a facility grow, the UPS can be easily expanded without requiring a complete system overhaul. This modularity contributes to a more efficient use of resources and minimizes operational costs.

The UPS also incorporates advanced technologies such as double-conversion online architecture, which provides the highest level of power quality. This technology ensures that the output power is consistently clean and stable, effectively eliminating harmful voltage fluctuations and frequency variations. Consequently, connected load receives a pure sine wave output, preventing potential damage or operational issues with sensitive equipment.

Another key feature is the high efficiency rating of the Emerson UPS, which exceeds 95 percent in typical operating conditions. This high efficiency translates to reduced energy costs and a smaller carbon footprint, aligning with modern sustainability goals. The cooling system is designed to be efficient as well, ensuring optimal performance while maintaining a compact footprint.

The user-friendly interface enhances operability, featuring an intuitive LCD display that allows for easy monitoring of critical power parameters. Users can access real-time data related to battery health, load levels, and operational status, which aids in effective management of the power supply.

Battery management is another critical aspect of the Emerson UPS. It employs advanced battery management technologies to ensure optimal battery life and performance. Features such as intelligent battery testing and monitoring help predict potential battery failures before they occur, allowing for proactive maintenance and minimized downtime.

In summary, the Emerson 10-30 kVA, 208V UPS offers a combination of modularity, high efficiency, advanced technologies, and effective power management features that cater to the demanding needs of critical applications. With its reliable performance and user-friendly operation, this UPS solution is an excellent choice for organizations looking to protect their valuable equipment from power disturbances.