Emerson 208V, 10-30kVA Output Dry Contacts, EPO Input-Optional Firmware Before M200

Page 23

Electrical Connections

2.3.4Output Dry Contacts

There are three output dry contact relays at the X1 slot (see Figure 10 and Table 4).

Figure 10 Output dry contacts and EPO wiring for firmware before M170

+12V

X1

J13

 

 

J21

 

 

 

 

 

BFP C

BFP S

BFP O

INV C

INV S

INV O

Table 4 Output dry contact relays

 

J25

 

ACF C

ACF S

ACF O

J28

EPO-H EPO-L

X2

Position

Name

Description

 

 

 

J13.2

BFP_O

Bypass feedback protection relay. Normally open. Closed when bypass SCR is shorted.

 

 

 

J13.3

BFP_S

Bypass feedback protection relay center

 

 

 

J13.4

BFP_C

Bypass feedback protection relay. Normally closed. Open when bypass SCR is shorted.

 

 

 

J21.2

INV_O

Inverter mode relay. Normally open. Closed when UPS is in inverter mode.

 

 

 

J21.3

INV_S

Inverter mode relay center

 

 

 

J21.4

INV_C

Inverter mode relay. Normally closed. Open when UPS is in inverter mode.

 

 

 

J25.2

ACF_O

Main input fault relay. Normally open. Closed when main input is in fault.

 

 

 

J25.3

ACF_S

Main input fault relay center

 

 

 

J25.4

ACF_C

Main input fault relay. Normally closed. Open when main input is in fault.

 

 

 

NOTE

All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded for maximum runs between 82 and 164 feet (25-50m), respectively.

2.3.5EPO Input—Optional

Firmware Before M200

The UPS has an Emergency Power Off (EPO) function that operates by a button on the control panel or by a remote contact provided by the user. The EPO button is under a hinged, clear plastic shield.

The X2 slot, shown in Figure 10, is the remote EPO input interface. It is active when shorted from EPO-L to EPO-H.

If an external Emergency Stop facility is required, it is connected terminals EPO-L to EPO-H of the auxiliary terminal block (X2). It also is connected to the Normally Open remote stop switch between these two terminals using shielded cable (see Figure 10 and Table 5). If this function is not used, terminals EPO-L to EPO-H must be opened.

Table 5 EPO input contact relays

Position

Name

Description

 

 

 

J28.2

EPO_L

Emergency Power Off Low

J28.4

EPO_H

Emergency Power Off High

NOTE

The Emergency Stop action within the UPS shuts down the rectifier, inverter and static bypass. It does not internally disconnect the input power supply.

To disconnect ALL power to the UPS, open the upstream feeder breaker(s) when the remote EPO is activated.

17

Image 23
Contents Liebert NX UPS Page Table of Contents Options Maintenance Bypass CabinetUPS Specifications Figures Tables Important Safety Instructions Battery Cabinet Precautions Glossary of Symbols Internal Inspections External InspectionsUPS Location Preliminary ChecksFinal Position Considerations in Moving the NXMechanical Considerations Special Considerations for 1+N Systems10-30kVA UPS Floor InstallationClearances Cable EntryOptional Cabinets Maintenance Bypass CabinetBattery LiebertLug Size and Torque Requirements Power CablingCable Rating Cabling Guidelines UPS Input ConfigurationBussmann Cable ConnectionsSystem Output Safety GroundProtective Devices UPS Rectifier and Bypass Input SupplyDual Input Connections Cabling ProcedureOutput System Connections-Ensure Correct Phase Rotation Common Input ConnectionsControl Cables Internal UPS Battery ConnectionsMonitor Board Features Input Dry Contacts Dry ContactsBCB box interface Maintenance Bypass Cabinet InterfaceMaintenance bypass cabinet interface BCB Box InterfaceEPO input contact relays Output Dry ContactsEPO Input-Optional Firmware Before M200 Output dry contact relaysFirmware M200 or Later UPS Batteries SafetyIntroduction Removable retainer Tray handle Insulated post for cabling External Battery Cabinet InstallationMatching Battery Cabinets Connecting the BatteriesTop cable entry Batteries BCB plate Top cable entry Battery trays BCB plate and BCBBattery tray support Service shelf Installation Considerations Ends of supports Battery tray supports attachTo interior surface of NX Front door note notchedNon-Standard Batteries Connecting the Battery Cabinet to the UPSNormal UPS Mode Bypass SwitchLocating the Cabinet Bypass ModeMaintenance Mode Cable InstallationInput/Output Wiring Power Cable InstallationMaintenance bypass control wire location Line up cabinets so that mounting holes are aligned Bolting Cabinets TogetherLBS Cable DBS Cable and SettingsLoad Bus Synchronization Performance RequirementsGeneral Configuring Parallel System OperationFeatures of Parallel System Installing Parallel System Auxiliary Dry Contact Cables Power CablesInterconnecting Parallel Control Cables Parallel System Control CablesInput Distribution Normally Closed EPO Normally Open EPOCircuit Breaker Battery Circuit Breaker BoxAvailable battery circuit breaker boxes DimensionsMidpoint Busbar Detail DPN U3813078 Rev. N Front ViewBottom View Conformity and Standards UPS Mechanical CharacteristicsEnvironmental characteristics Mechanical characteristicsUPS terminal UPS Electrical CharacteristicsDC Intermediate Circuit Battery Manufacturers and ModelsInput Rectifier Time Load Inverter OutputInverter output Bypass Input Bypass inputInstallation Drawings Main components-typical unit Dimensions -top and bottom viewsCable connections Location of internal batteries Battery 417mm 186mm 687mmW503 to W502 W501 3pcs W500 18pcs W506 to W507 W510 to W511 W502 to W503W504 to W505 W511 to W510 W507 to W506 W509 to W508 W505 to W504 W508 to W509Run From Conductors Liebert -supplied interconnect wiringRefer to for key to interconnection Maintenance Bypass interconnection A00, BR0 Liebert-supplied interconnect wiringRun From Conductors Cabinet Type Distribution Cabinet Load AC Connection Neutral Ground Distribution CabinetIsolated Ground Interconnect wiring-1+N Type a connection to NX Interconnect wiring-1+N Type A1 connection to NX Utility AC Source UPS #1-UPS #4 Module AC Input Interconnect wiring-1+N Type B connection to NXInterconnect wiring-1+N Type B1 connection to NX Ph a ,B, C Load Interconnect wiring-1+N Type C connection to NXPh A, B, C-system Input Ph a ,B, C UPS Input+ N Cabinet Side View + N Parallel Cabinet Interconnect wiring-1+N Type C1 connection to NXLineup detail-1+N Type D connection to NX Interconnect wiring-1+N Type D connection to NXUPS Lug Size and Torque Requirements Torque specificationsBattery torque rating Initial Torque Annual Torque Battery In-lb N-mCurrent Rating a OCP CB Size a Maintenance bypass cabinet electrical data single inputCurrent CB Size a Current Rating a CB Size a Maintenance bypass cabinet electrical data dual inputMulti-module bypass cabinet electrical data SR0, W00 200A300A TR0 E00, FR0G01, GR1 208 104 125 250 400 UR0, Y00 MR1208 280 400 222 300 210 250 167 225 140 175 111 150 Maintenance bypass cabinet lug sizes Maintenance Bypass Cabinet Style, lb. kg Rating Battery cabinet physical characteristicsMaintenance Bypass Cabinet weights Distance to connection points on the NX UPS Maintenance bypass cabinet dimensionsMulti-module paralleling cabinet dimensions Cable Lengths Floor to Connection Point Inside UPSSpecifications and Technical Data Specifications and Technical Data Page That Ne tIti Ti n
Related manuals
Manual 80 pages 58.87 Kb Manual 48 pages 54.46 Kb

10-30kVA, 208V specifications

The Emerson 10-30 kVA, 208V uninterruptible power supply (UPS) solution is a robust system designed to provide reliable power protection for critical applications in commercial and industrial settings. This UPS is ideal for safeguarding IT equipment, communication systems, and other sensitive electronics against power disturbances and interruptions.

One of the standout features of the Emerson 10-30 kVA UPS is its modular design, allowing for flexibility and scalability. This means that as the power needs of a facility grow, the UPS can be easily expanded without requiring a complete system overhaul. This modularity contributes to a more efficient use of resources and minimizes operational costs.

The UPS also incorporates advanced technologies such as double-conversion online architecture, which provides the highest level of power quality. This technology ensures that the output power is consistently clean and stable, effectively eliminating harmful voltage fluctuations and frequency variations. Consequently, connected load receives a pure sine wave output, preventing potential damage or operational issues with sensitive equipment.

Another key feature is the high efficiency rating of the Emerson UPS, which exceeds 95 percent in typical operating conditions. This high efficiency translates to reduced energy costs and a smaller carbon footprint, aligning with modern sustainability goals. The cooling system is designed to be efficient as well, ensuring optimal performance while maintaining a compact footprint.

The user-friendly interface enhances operability, featuring an intuitive LCD display that allows for easy monitoring of critical power parameters. Users can access real-time data related to battery health, load levels, and operational status, which aids in effective management of the power supply.

Battery management is another critical aspect of the Emerson UPS. It employs advanced battery management technologies to ensure optimal battery life and performance. Features such as intelligent battery testing and monitoring help predict potential battery failures before they occur, allowing for proactive maintenance and minimized downtime.

In summary, the Emerson 10-30 kVA, 208V UPS offers a combination of modularity, high efficiency, advanced technologies, and effective power management features that cater to the demanding needs of critical applications. With its reliable performance and user-friendly operation, this UPS solution is an excellent choice for organizations looking to protect their valuable equipment from power disturbances.