Chapter 2 Installing the Cisco MDS 9100 Series
Grounding the Switch
Grounding the Switch
A grounding pad with two threaded M4 holes is provided on the chassis for attaching a grounding lug. Figure
Figure 2-19 Location of Switch Ground on the Cisco MDS 9100 Series
Grounding pad location
System grounding pad
| Wire | |
Grounding | Screws (M4) | |
94943 | ||
lug | ||
|
Warning When installing or replacing the unit, the ground connection must always be made first and disconnected last. Statement 1046
Caution We recommend grounding the chassis, even if the rack is already grounded.
Note If the rack is less than
Caution All power supplies must be grounded. The receptacles of the AC power cables used to provide power to the chassis must be the grounding type, and the grounding conductors should connect to protective earth ground at the service equipment.
Note The grounding lug must be NRTL listed and compatible with copper conductors. Only copper conductors (wires) must be used and the copper conductor must comply with National Electrical Code (NEC) for ampacity.
|
| Cisco MDS 9100 Series Hardware Installation Guide |
|
| |
|
|
| |||
|
|
|
| ||
|
|
|
|