Chapter 5 Troubleshooting
Troubleshooting Backplane Modules
Step 4 Determine whether the airflow is restricted or if the ambient temperature in the room is too warm.
Step 5 Determine whether the power supply is functioning properly. See the “Troubleshooting the Power Supply” section on page
Step 6 Verify that the fan assembly is properly seated in the backplane by loosening the captive installation screws, removing the fan assembly, and reinstalling it.
Step 7 Restart the system.
Step 8 Verify that all fans are operating. You should hear the fans at system start.
Step 9 If the system is still detecting a fan assembly failure, contact the Cisco TAC for assistance.
Troubleshooting Backplane Modules
The Cisco Catalyst 4500 Series redundancy scheme uses removable redundancy modules (also called
The following conditions indicate that you may need to replace the redundancy modules and clock module:
|