Chapter 2 Switch Installation
Preparing for Installation
Warning To prevent the system from overheating, do not operate it in an area that exceeds the maximum recommended ambient temperature of:
113°F (45°C) Statement 1047
Warning No
Warning Installation of the equipment must comply with local and national electrical codes. Statement 1074
Warning To prevent airflow restriction, allow clearance around the ventilation openings to be at least: 3 in. (7.6 cm) Statement 1076
Note The grounding architecture of this product is
Installation Guidelines
Before installing the switch, verify that these guidelines are met:
•For the clearance to the front and rear panels, make sure that
–
–Clearance is at least 4.4 in. (11.1 cm) from switch rear panel.
–Access to ports is sufficient for unrestricted cabling.
–AC power cord can reach from the AC power outlet to the connector on the switch rear panel.
–The SFP or SFP+ module minimum bend radius and connector length is met. See the SFP or SFP+ module documentation for more information.
•For switches with the optional
•Make sure
•When connecting or disconnecting the power cord on a switch that is installed above or below a
•Cabling is away from sources of electrical noise, such as radios, power lines, and fluorescent lighting fixtures. Make sure that the cabling is safely away from other devices that might damage the cables.
•For copper connections on Ethernet ports, cable lengths from the switch to connected devices can be up to 328 feet (100 meters).
•For cable requirements for SFP+ module connections, see the “Cable and Adapter Specifications” section on page
Catalyst 3650 Switch Hardware Installation Guide
|
| ||
|
|