4
Power | Wiring | Audible |
| ||
On | Fault | Alarm | Condition | ||
P |
|
| |||
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| ||
Off | Off | Long | System | ||
|
|
|
| beep | of power required by plugged |
|
|
|
|
| in devices exceeds the amount |
|
|
|
|
| of power your UPS can supply. |
|
|
|
|
| Turn off your UPS, unplug at |
|
|
|
|
| least one device, wait 10 |
|
|
|
|
| seconds, reset the circuit |
|
|
|
|
| breaker, then turn on your UPS. |
|
|
|
| ||
Off | On/Off | Long | Battery | ||
|
|
|
| beep | of power required by devices |
|
|
|
|
| plugged into the |
|
|
|
|
| |
|
|
|
|
| exceeds the amount of power |
|
|
|
|
| the battery can supply. Turn the |
|
|
|
|
| UPS off, unplug at least one |
|
|
|
|
| device from |
|
|
|
|
| outlets, wait 10 seconds, reset |
|
|
|
|
| the circuit breaker, then turn on |
|
|
|
|
| your UPS. |
|
|
|
| ||
On/Off | On | None | Electrical Wiring | ||
|
|
|
|
| outlet your UPS is plugged into |
|
|
|
|
| has a wiring problem, such as a |
|
|
|
|
| bad ground, a missing ground, |
|
|
|
|
| or reversed wiring. Contact an |
|
|
|
|
| electrician to repair the outlet or |
|
|
|
|
| use a different outlet. |
|
|
|
|
|
|
Replacing the battery
Warnings:
•Read and follow the Important Safety Instructions before servicing the battery. Service the battery under the supervision of personnel knowledgeable of batteries and their precautions.
•Use only the specified type of battery. See your dealer for replacement batteries.
•The battery may present a risk of electrical shock. Do not dispose of battery in a fire because it may explode. Follow all local ordinances regarding correct disposal of batteries. Almost any retailer that sells
•Do not open or damage the batteries. The batteries contain electrolytes that are harmful to skin and eyes.
•A battery can present a high risk of short circuit current and electrical shock. Take the following precautions before replacing the battery:
•Remove all watches, rings, or other metal objects.
•Only use tools with insulated handles.
•Do not lay tools or metal parts on top of the battery or any terminals.
•Wear rubber gloves and boots.
•Determine if the battery is inadvertently grounded. If grounded, remove the source of ground. Contact with a grounded battery can result in electrical shock.
To replace the battery:
1Turn off and unplug all connected devices.
2Turn the UPS off and unplug it from the AC power source.
3 Turn the UPS upside down.
Status indicators
4Remove the retaining screw.
5Slide the battery compartment cover completely off of your UPS.
6 Remove the battery from the compartment.
7Disconnect the battery wires from the battery. Note which wire is connected to the positive (+) and negative
8Install the replacement battery by connecting the red wire and black wire to the positive (+) and negative
9Put the battery back into the compartment.
10Slide back the battery compartment cover and tighten the retaining screw.
11Recharge your UPS for 4 - 8 hours to fully charge the battery.
Warning: Batteries are consider hazardous waste and must be disposed of correctly. Almost any retailer that sells