1 Basic Operation (continued)

1.6 Start-Up, Shutdown and Bypass

Warning: The UPS system’s output voltage is set at 220/380V by default. If you require output voltage of 230/400V or 240/415V, you must change the UPS system’s output voltage by accessing the output setup menu described in Section 10-9 of the owner’s manual. You must place the UPS system in bypass mode before changing the output voltage. Do not connect your equipment to the UPS system’s output until you have set the proper parameters.

1.6.1 Control Panel and Breaker Diagrams

“NORMAL” LED

“BATTERY” LED

“BYPASS” LED

“FAULT” LED

LCD Status Screen

“ESC” (Escape) Button

Scroll Buttons ( and )

Enter Button ( )

ON Button

OFF Button

“EPO” (Emergency Power Off) Button

Output Circuit Breaker Switch

Manual Bypass Circuit Breaker Switch

Bypass Input Circuit Breaker Switch

Main Input Circuit Breaker Switch

1.6.2 Preliminary Checklist (Single UPS)

E

F

I

K

A

 

 

 

B

G

 

 

C

 

 

 

 

 

D

 

 

 

1

H

J

 

 

 

 

Control Panel

L

M

N

O

Output

Manual

Bypass

Main

2

Bypass

Input

Input

Circuit Breaker Switches (UPS System Front Panel)

All circuit breaker switches should be off, including the breaker of the external battery cabinet (if present).

Confirm that no voltage potential exists between Neutral and Ground.

Confirm that the input power source matches the rating (voltage, frequency and phase) of the UPS system.

Note: After start-up, the UPS system will perform a brief self-test and display the results on the LCD screen. After a successful self-test, the UPS system will provide AC power to the connected equipment load.

1.6.3 Standard Start-Up Procedure (Single UPS)

If there is an external battery cabinet connected, switch on the circuit breaker of the external battery cabinet.

Confirm that the manual bypass circuit breaker switch is off.

A

1

 

A

 

 

Output

Manual

Bypass

Main

2

Bypass

Input

Input

 

 

 

18

Image 18
Contents Th Street, Chicago, IL 60609 USA Table of Contents Basic Operation Technical SpecificationsKX Models KTV Models SU40K SU60K SU60KTV SU80KTVSU80K Model Model Capacity SU80K 80kVA/64kWFeatures Advanced FeaturesControl Panel Features Front and Rear Panel Features 3a SU40KX front3b SU40KX rear 3c SU40K front 3d SU40K rear 3e SU80K front 3f SU80K rear Internal Battery Layout Operating PrinciplesSystem Layout Power Module Layout 3a Power Module Block DiagramOpening and Closing the Unit Auto Bypass Mode Single UPS Online Normal Mode Single UPSBattery Backup Mode Single UPS Manual Bypass Mode Single UPSOnline Mode Parallel UPS Battery Backup Mode Parallel UPSAuto Bypass Mode Parallel UPS Manual Bypass Mode Parallel UPS Hot Standby Mode Parallel UPSPreliminary Checklist Single UPS Control Panel and Breaker DiagramsNormal LED Battery LED Bypass LED Fault LED Standard Start-Up Procedure Single UPSBattery Start-Up Procedure Single UPS Manual Bypass Procedure Single UPS Shutdown Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPSShutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Printed Circuit Boards PCB SU80KX SU60KX SU40KX SU80KTV SU20KXPCB Location System F3 FB M LA, LB, LC, LD Models LA, LB, LC LA, LB, LC, LD F1BYP F1MAIN F2BYP F2MAIN LCD PCB Location Power Module PCB Board Name Description1c SU40KX Block Diagram Block and Wiring Diagrams1a SU20KX Block Diagram KX ModelsDC Auxiliary Power Circuit Auxiliary Power Failure DetectionTheory of Operation Output Current Detection W18Input Voltage Detection Located at NH-SYS-M board System MCU and Control CircuitOutput Voltage Detection Located at NH-SYS-M board System MCU and Control CircuitBattery Voltage Detection UP10BBypass SCR Short-Circuit Detection Scrst RBypass SCR Driver TSA1Watchdog for System MCU LCD Panel Control Circuit To LCDFan Control Circuit Located on NH-SYS-M board System MCU and Control CircuitBypass SCR Temperature Detection Communication Circuit for RS232RS232 Port Communication Circuit for SlotsCommunication Circuit for Output Dry Contact Output DRY ContactCommunication Circuit for Input Dry Contact and Repo Input DRY ContactExternal Battery Cabinet Temperature Detection EXTBTEMP1Detection Circuit for Manual Bypass Switch Detection Circuit for Output BreakerControl Circuit for Power Module CentralokTo PM1 to PM2 CM93 CM106 CM109 Control Circuit for External ParallelTheory of Operation 01 RS232 Port Emergency Power Off EPOCommunication 02a Front Control PanelRemote Emergency Power Off Repo 02b02c Setting Eeprom on the NH-M Board Polling and Updating EepromCalibrating Eeprom Gain Setting Output Dry Contact Status Upgrading Firmware for the System Board Output Manual Bypass Main Input N C S T G R G I N G R a D E Communication Upgrading Firmware for the Power Module PM1 U P S T G R G I N Link the UPS to a PC via the RS232 port Communication Communication Communication T I N G L O W E D Downloading the Event Log Internal Battery Battery StringsFront View of SU20KX and SU40KX Installing and Removing Internal Batteries Terminals Damage the UPS system and create a serious risk of personal Battery compartment. Warning Observe proper polarity byConnecting negative to negative black to black and positive Injury and property damageBattery Cabinet 2a BP480V26B 2b BP480V40CInternal Battery 2e Connection between UPS and Battery Cabinet 2f Wiring between UPS and Battery Cabinet2d W1 and W2 Cables Troubleshooting Alarm Messages1a Warning Message List 1b Power Module Warning Message List ConditionTroubleshooting Flow Charts Main VOLT/FREQ NOKMain Sequence NOK Bypass VOLT/FREQ NOK Bypass Static Switch Over Temperature Bypass Sequence NOKBypass Static Switch Fault Bypass Static Switch OverloadSame fault message? Replace the power module UPS Internal Comm AbnormalBattery Test Fail Battery Over Charge10a Battery BAD 11a 11bBypass FAN Failure 12a 12b 12cTransformer Overheat 13a 13bPS Output Volt NOK 14a 14bPS EXT Parallel Comm Abnormal 15a 15bParallel Failure 16a 16bRedundancy Loss 17aPower Module Failure Power Module Identify115 116 Power Module Replacement AC Input DC Input Output 119 120 UPS Procedure Preventive MaintenanceSafety Overview Suggested tools and suppliesInternal Battery Procedure Software Tools Appendix a Service Equipment and ToolsRecommended Equipment and Tools Multi-Meter OscilloscopeTable B.1 Appendix B Torque TableKX Models Fig B.aModels Table B.2Table B.3 Fig B.b Fig B.c KTV Models Table B.4Fig B.d Appendix C PCB and Test Point NH-SYS-P BoardNH-SYS-R Board