3 Communication (continued)
3.2 Setting Output Dry Contact Status
The UPS provides six output dry contact closures. The status of each output dry contact closure can be programmed from 19 status events:
1.Load on inverter (Default)
2.Load on auto bypass (Default)
3.Backup mode input main failure (Default)
4.Battery low (Default)
5.Bypass input abnormal (Default)
6.Battery test failure (Default)
7.Internal communication failure
8.External parallel communication failure
9.Output overload warning/shutdown
10.Power module fault shutdown
11.Power module warning
12.EPO activated
13.Load on manual bypass
14.Battery cabinet over temperature warning/shutdown
15.Output voltage abnormal
16.Battery need replace
17.Bypass over temperature warning/shutdown
18.Battery ground fault
19.Bypass static switch fault
Fig 3.2a
To change the status of an output dry contact closure:
(a)Link the UPS with a PC via the RS232 port
(b)Run the program
(c)Select the PC COM Port and click “Open COM Port”
(d)Click “Get Status” to poll the UPS settings
(e)After you change the status, click “Confirm Change” to update the UPS settings