Tripp Lite SU60KX manual KTV Models, SU40K SU60K SU60KTV SU80KTV

Page 4

1 Basic Operation (continued)

1.1 Technical Specifications (continued)

K and KTV Models:

 

Model

SU40K

SU60K

SU60KTV

SU80KTV

 

(Capacity)

(40kVA/32kW)

(60kVA/48kW)

(60kVA/48kW)

(80kVA/64kW)

Input

Input Voltage

120/208V AC, 3O,

277/480V AC, 3O,

 

 

4-wire + ground, wye

4-wire + ground, wye

 

Voltage Regulation

-25% ~ +20%

 

 

 

 

Harmonic Distortion

< 5% (Full Load)

 

 

 

 

PFC (Full Load)

> 0.99

 

 

 

 

Frequency

50 / 60 Hz

 

 

 

 

Frequency Tolerance

45 ~ 65 Hz

 

 

 

Output

Output Voltage

120/208V AC, 3O,

277/480V AC, 3O,

 

 

4-wire + ground, wye

4-wire + ground, wye

 

Output Frequency

 

 

50 / 60 Hz

 

 

 

 

 

 

Total Harmonic (Linear Load)

3%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage Regulation

Static

±1%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency Regulation

Dynamic

±7% (10% ~ 90% Linear Load)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Interior Oscillator

±0.05 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Synchronized

±5%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overload

 

 

125% : 10 minutes; 150% : 1 minute

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Audible Warning

Battery Backup

 

 

Intermittent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS Abnormal

 

 

Continuous

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Display

LED

 

 

UPS Status: Normal • Bypass • Backup • Fault

 

 

 

 

 

 

 

 

 

 

 

LCD

 

 

Input/Output • Bypass • Inverter • Frequency • Loading • Battery Voltage

 

 

 

 

UPS abnormal messages with intelligent self-diagnosis.

 

 

 

 

 

 

 

 

 

 

 

 

 

Interface

Standard

 

 

RS-232, Dry Contact

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Optional

 

 

SNMPWEBCARD

 

 

 

 

 

 

 

 

 

 

 

 

 

Others

Parallel Redundancy

 

 

Yes (1+1 for 2 UPS systems of the same type and capacity only.)

 

 

 

 

 

 

 

 

 

 

 

EPO

 

 

Standard (Local and Remote)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SRAM Event Log

 

 

500 Records

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter Configuration

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hot Standby Installation

 

 

Optional

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery Temperature Compensation

Optional

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery Cold-Start

 

 

Standard

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overall

Efficiency

Normal

92%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ECO

96%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transfer Time

 

 

0 ms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature

 

 

32° F ~ 104° F (0° C ~ 40° C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Humidity (non-condensing)

90%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Noise (1 m)

 

 

65 dBA

 

68 dBA

 

70 dBA

 

70 dBA

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions (Power Module)

Width

520 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth

850 mm

 

950 mm

 

 

850 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

1696 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Weight (Power Module)

 

 

682 kg*

 

534 kg

 

534 kg

 

584 kg

 

 

 

 

 

 

 

 

 

 

 

* With internal batteries.

4

Image 4
Contents Th Street, Chicago, IL 60609 USA Table of Contents Technical Specifications Basic OperationKX Models KTV Models SU40K SU60K SU60KTV SU80KTVSU80K Model Model Capacity SU80K 80kVA/64kWAdvanced Features FeaturesControl Panel Features Front and Rear Panel Features 3a SU40KX front3b SU40KX rear 3c SU40K front 3d SU40K rear 3e SU80K front 3f SU80K rear Operating Principles Internal Battery LayoutSystem Layout 3a Power Module Block Diagram Power Module LayoutOpening and Closing the Unit Online Normal Mode Single UPS Battery Backup Mode Single UPSAuto Bypass Mode Single UPS Manual Bypass Mode Single UPSBattery Backup Mode Parallel UPS Online Mode Parallel UPSAuto Bypass Mode Parallel UPS Manual Bypass Mode Parallel UPS Hot Standby Mode Parallel UPSControl Panel and Breaker Diagrams Normal LED Battery LED Bypass LED Fault LEDPreliminary Checklist Single UPS Standard Start-Up Procedure Single UPSBattery Start-Up Procedure Single UPS Manual Bypass Procedure Single UPS Shutdown Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPSShutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Printed Circuit Boards PCB SU80KX SU60KX SU40KX SU80KTV SU20KXPCB Location System F3 FB M LA, LB, LC, LD Models LA, LB, LC LA, LB, LC, LD F1BYP F1MAIN F2BYP F2MAIN LCD PCB Location Power Module PCB Board Name DescriptionBlock and Wiring Diagrams 1a SU20KX Block Diagram1c SU40KX Block Diagram KX ModelsAuxiliary Power Failure Detection DC Auxiliary Power CircuitTheory of Operation Output Current Detection W18Input Voltage Detection Located at NH-SYS-M board System MCU and Control CircuitOutput Voltage Detection Located at NH-SYS-M board System MCU and Control CircuitBattery Voltage Detection UP10BBypass SCR Short-Circuit Detection Scrst RBypass SCR Driver TSA1Watchdog for System MCU LCD Panel Control Circuit To LCDFan Control Circuit Located on NH-SYS-M board System MCU and Control CircuitBypass SCR Temperature Detection Communication Circuit for RS232RS232 Port Communication Circuit for SlotsCommunication Circuit for Output Dry Contact Output DRY ContactCommunication Circuit for Input Dry Contact and Repo Input DRY ContactExternal Battery Cabinet Temperature Detection EXTBTEMP1Detection Circuit for Manual Bypass Switch Detection Circuit for Output BreakerControl Circuit for Power Module CentralokTo PM1 to PM2 CM93 CM106 CM109 Control Circuit for External ParallelTheory of Operation Emergency Power Off EPO Communication01 RS232 Port 02a Front Control Panel02b Remote Emergency Power Off Repo02c Setting Eeprom on the NH-M Board Polling and Updating EepromCalibrating Eeprom Gain Setting Output Dry Contact Status Upgrading Firmware for the System Board Output Manual Bypass Main Input N C S T G R G I N G R a D E Communication Upgrading Firmware for the Power Module PM1 U P S T G R G I N Link the UPS to a PC via the RS232 port Communication Communication Communication T I N G L O W E D Downloading the Event Log Battery Strings Internal BatteryFront View of SU20KX and SU40KX Installing and Removing Internal Batteries Terminals Battery compartment. Warning Observe proper polarity by Connecting negative to negative black to black and positiveDamage the UPS system and create a serious risk of personal Injury and property damageBattery Cabinet 2a BP480V26B 2b BP480V40CInternal Battery 2f Wiring between UPS and Battery Cabinet 2e Connection between UPS and Battery Cabinet2d W1 and W2 Cables Alarm Messages Troubleshooting1a Warning Message List 1b Power Module Warning Message List ConditionTroubleshooting Flow Charts Main VOLT/FREQ NOKMain Sequence NOK Bypass VOLT/FREQ NOK Bypass Static Switch Over Temperature Bypass Sequence NOKBypass Static Switch Fault Bypass Static Switch OverloadSame fault message? Replace the power module UPS Internal Comm AbnormalBattery Over Charge Battery Test Fail10a Battery BAD 11a 11bBypass FAN Failure 12a 12b 12cTransformer Overheat 13a 13bPS Output Volt NOK 14a 14bPS EXT Parallel Comm Abnormal 15a 15bParallel Failure 16a 16bRedundancy Loss 17aPower Module Failure Power Module Identify115 116 Power Module Replacement AC Input DC Input Output 119 120 Preventive Maintenance Safety OverviewUPS Procedure Suggested tools and suppliesInternal Battery Procedure Appendix a Service Equipment and Tools Recommended Equipment and ToolsSoftware Tools Multi-Meter OscilloscopeAppendix B Torque Table KX ModelsTable B.1 Fig B.aTable B.2 ModelsTable B.3 Fig B.b Fig B.c Table B.4 KTV ModelsFig B.d NH-SYS-P Board Appendix C PCB and Test PointNH-SYS-R Board