7 Preventive Maintenance (continued)

7.4Internal Battery Procedure

c)Use the infrared thermometer to measure the ambient temperature near the battery module and the internal temperature of the battery module. Note that the best place to read ambient temperature is on the floor immediately behind the battery module. Battery module internal temperature should be taken at one of the jars on a top tier.

d)Use the digital multi-meter to read the voltage across each tray. Note if the voltage is outside the range 130V to 138V for any tray.

e)Replace the tray and re-connect the Anderson connectors.

f)Repeat steps d) through e) for the remaining battery trays.

g)When the battery cabinet inspection is complete, replace the cover. Turn on the Main input circuit breaker and Bypass input breaker on the UPS. When the static switch is operating, turn off the Manual Bypass switch

h)Verify using the LCD display that the main input and DC bus voltages are correct, then press the ON switch. Verify that the inverter starts and operates correctly per the LED panel and LCD display.

Appendix A Service Equipment and Tools

Recommended Equipment and Tools

Laptop: with series COM port

Multi-Meter

Oscilloscope

Clamp Meter: for measurement of current

Screwdriver: Phillips-head and slotted

Hex Wrench: 5mm and 6mm

Socket Wrench: 13mm and 17mm

Diagonal Cutters

Software Tools

NH_SYS_V1_3B1030.exe: For system EEPROM parameter settings and calibration.

FSL 3.75.exe: For upgrading the system MCU’s firmware on a NH-SYS-M board.

NH_PM_V1_4B1207.exe: For upgrading the power module’s firmware.

NH-Dry-Contact v1.0b1024.exe: For output dry contact status setting.

NH-EventLog v1.0b1115.exe: For downloading the UPS event log.

123

Image 105
Contents Th Street, Chicago, IL 60609 USA Table of Contents Basic Operation Technical SpecificationsKX Models SU40K SU60K SU60KTV SU80KTV KTV ModelsModel Capacity SU80K 80kVA/64kW SU80K ModelFeatures Advanced FeaturesControl Panel Features 3a SU40KX front Front and Rear Panel Features3b SU40KX rear 3c SU40K front 3d SU40K rear 3e SU80K front 3f SU80K rear Internal Battery Layout Operating PrinciplesSystem Layout Power Module Layout 3a Power Module Block DiagramOpening and Closing the Unit Battery Backup Mode Single UPS Online Normal Mode Single UPSAuto Bypass Mode Single UPS Manual Bypass Mode Single UPSOnline Mode Parallel UPS Battery Backup Mode Parallel UPSAuto Bypass Mode Parallel UPS Hot Standby Mode Parallel UPS Manual Bypass Mode Parallel UPSNormal LED Battery LED Bypass LED Fault LED Control Panel and Breaker DiagramsPreliminary Checklist Single UPS Standard Start-Up Procedure Single UPSBattery Start-Up Procedure Single UPS Shutdown Procedure Single UPS Manual Bypass Procedure Single UPSStart-Up Procedure Parallel UPS Preliminary Checklist Parallel UPSShutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS SU80KX SU60KX SU40KX SU80KTV SU20KX Printed Circuit Boards PCBPCB Location System F3 FB M LA, LB, LC, LD Models LA, LB, LC LA, LB, LC, LD F1BYP F1MAIN F2BYP F2MAIN LCD PCB Board Name Description PCB Location Power Module1a SU20KX Block Diagram Block and Wiring Diagrams1c SU40KX Block Diagram KX ModelsDC Auxiliary Power Circuit Auxiliary Power Failure DetectionTheory of Operation W18 Output Current DetectionLocated at NH-SYS-M board System MCU and Control Circuit Input Voltage DetectionLocated at NH-SYS-M board System MCU and Control Circuit Output Voltage DetectionUP10B Battery Voltage DetectionScrst R Bypass SCR Short-Circuit DetectionTSA1 Bypass SCR DriverWatchdog for System MCU To LCD LCD Panel Control CircuitLocated on NH-SYS-M board System MCU and Control Circuit Fan Control CircuitCommunication Circuit for RS232 Bypass SCR Temperature DetectionCommunication Circuit for Slots RS232 PortOutput DRY Contact Communication Circuit for Output Dry ContactInput DRY Contact Communication Circuit for Input Dry Contact and RepoEXTBTEMP1 External Battery Cabinet Temperature DetectionDetection Circuit for Output Breaker Detection Circuit for Manual Bypass SwitchCentralok Control Circuit for Power ModuleTo PM1 to PM2 CM93 Control Circuit for External Parallel CM106 CM109Theory of Operation Communication Emergency Power Off EPO01 RS232 Port 02a Front Control PanelRemote Emergency Power Off Repo 02b02c Polling and Updating Eeprom Setting Eeprom on the NH-M BoardCalibrating Eeprom Gain Setting Output Dry Contact Status Upgrading Firmware for the System Board Output Manual Bypass Main Input N C S T G R G I N G R a D E Communication Upgrading Firmware for the Power Module PM1 U P S T G R G I N Link the UPS to a PC via the RS232 port Communication Communication Communication T I N G L O W E D Downloading the Event Log Internal Battery Battery StringsFront View of SU20KX and SU40KX Installing and Removing Internal Batteries Terminals Connecting negative to negative black to black and positive Battery compartment. Warning Observe proper polarity byDamage the UPS system and create a serious risk of personal Injury and property damage2a BP480V26B 2b BP480V40C Battery CabinetInternal Battery 2e Connection between UPS and Battery Cabinet 2f Wiring between UPS and Battery Cabinet2d W1 and W2 Cables Troubleshooting Alarm Messages1a Warning Message List Condition 1b Power Module Warning Message ListMain VOLT/FREQ NOK Troubleshooting Flow ChartsMain Sequence NOK Bypass VOLT/FREQ NOK Bypass Sequence NOK Bypass Static Switch Over TemperatureBypass Static Switch Overload Bypass Static Switch FaultUPS Internal Comm Abnormal Same fault message? Replace the power moduleBattery Test Fail Battery Over Charge10a 11a 11b Battery BAD12a 12b 12c Bypass FAN Failure13a 13b Transformer Overheat14a 14b PS Output Volt NOK15a 15b PS EXT Parallel Comm Abnormal16a 16b Parallel Failure17a Redundancy LossFailure Power Module Identify Power Module115 116 Power Module Replacement AC Input DC Input Output 119 120 Safety Overview Preventive MaintenanceUPS Procedure Suggested tools and suppliesInternal Battery Procedure Recommended Equipment and Tools Appendix a Service Equipment and ToolsSoftware Tools Multi-Meter OscilloscopeKX Models Appendix B Torque TableTable B.1 Fig B.aModels Table B.2Table B.3 Fig B.b Fig B.c KTV Models Table B.4Fig B.d Appendix C PCB and Test Point NH-SYS-P BoardNH-SYS-R Board