Tripp Lite SU60KX manual Internal Battery Procedure

Page 104

7 Preventive Maintenance (continued)

7.3 UPS Procedure (continued)

7.3.5

Measure Ø to Ø and Ø to Neutral output voltage and output current as above and enter the values on the form. Compare the readings to the LCD display. If the voltage readings are within +/- 1% and the current readings are within +/- 1 ampere, check output metering OK on the form. If there is a greater discrepancy, enter that in NOTES. Then what do we do? Is there a troubleshooting tree to reference in the service manual?

7.3.6

Check DC BUS voltage from the LCD display and enter those voltages on the form. DC bus voltages should be 370V within +/- 3V. If there is a greater difference, enter that in NOTES. Then what do we do? Is there a troubleshooting tree to reference in the service manual?

7.3.7

Use a digital multi-meter to measure battery DC voltage at the terminal blocks and enter that information on the battery PM form. Use a clamp-on ammeter to measure DC charge current and enter that information on the battery PM form. What should the current be? Is there an expected limit not to be under or exceed?

7.3.8

Perform the visual battery inspection. Note any problems. Then take an infrared reading of ambient temperature and the inside of the battery compartment and enter that information on the form. Note on the form if battery temperature exceeds 95O F, or 32O F above ambient. What steps should be followed to address this issue? Is this an information only step?

7.3.9

If the battery PM is to be performed, it should be done at this time. See section 7.4 for the internal battery procedure.

7.3.10

When inspection is complete, replace the rear, side, top and front covers of the UPS.

7.3.11

When you turn on manual bypass under the following situation :

1.Replace the failure power module with a new one.

2.Replace the failure board/components in the system

Please follow the regular turn-on procedure. Turn on the bypass input, output and main input breaker. Verify the static switch is load on the bypass, turn off the manual bypass breaker.

7.3.12

Check the LCD display to verify DC BUS voltages are present, and then press the “ON” key. Verify that the inverter starts and operates correctly per the LED panel and LCD display.

7.3.13

Summarize the results of the inspection with the customer representative on site. Be sure to note any items that will require service or customer action.

7.4 Internal Battery Procedure

Battery module PM inspection should always be performed at a time approved by the customer since the Battery Module must be disconnected and critical loads will not be backed up.

Because the SU series UPS units are direct coupled, all terminals of the battery circuit have hazardous voltage with respect to ground when the battery is connected.

Always remove fuses and disconnect the Anderson connectors before working on any part of the battery module. However, hazardous voltages will still exist between battery terminals.

Always insulate the exposed ends of any cables that must be disconnected, using electrical tape. Secure loose cables so that they cannot come in contact with other cables, surfaces, or connections.

When any cable or connector is disconnected, always use a voltmeter to verify that zero voltage exists before reconnecting.

a)While the inverter is normal, press OFF switch, turn off the Main circuit breaker Switch, turn on the Manual Bypass switch, and turn off the Bypass circuit breaker Switch. Perform the visual battery inspection. Note any problems. Then take an infrared reading of ambient temperature and the inside of the battery compartment and enter that information on the form. Note on the form if battery temperature exceeds 84O F, or 10O F above ambient What action should be taken if this condtion is present? Where do we go to in the manual?

b)Remove the battery compartment panels, and disconnect the Anderson connectors.

NOTE: Hazardous voltage exists between the fuse clips even after the battery cable is disconnected, as well as between all electrical connections in the battery module!

122

Image 104
Contents Th Street, Chicago, IL 60609 USA Table of Contents KX Models Basic OperationTechnical Specifications KTV Models SU40K SU60K SU60KTV SU80KTVSU80K Model Model Capacity SU80K 80kVA/64kWControl Panel Features FeaturesAdvanced Features Front and Rear Panel Features 3a SU40KX front3b SU40KX rear 3c SU40K front 3d SU40K rear 3e SU80K front 3f SU80K rear System Layout Internal Battery LayoutOperating Principles Opening and Closing the Unit Power Module Layout3a Power Module Block Diagram Online Normal Mode Single UPS Battery Backup Mode Single UPSAuto Bypass Mode Single UPS Manual Bypass Mode Single UPSAuto Bypass Mode Parallel UPS Online Mode Parallel UPSBattery Backup Mode Parallel UPS Manual Bypass Mode Parallel UPS Hot Standby Mode Parallel UPSControl Panel and Breaker Diagrams Normal LED Battery LED Bypass LED Fault LEDPreliminary Checklist Single UPS Standard Start-Up Procedure Single UPSBattery Start-Up Procedure Single UPS Manual Bypass Procedure Single UPS Shutdown Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPSShutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Printed Circuit Boards PCB SU80KX SU60KX SU40KX SU80KTV SU20KXPCB Location System F3 FB M LA, LB, LC, LD Models LA, LB, LC LA, LB, LC, LD F1BYP F1MAIN F2BYP F2MAIN LCD PCB Location Power Module PCB Board Name DescriptionBlock and Wiring Diagrams 1a SU20KX Block Diagram1c SU40KX Block Diagram KX ModelsTheory of Operation DC Auxiliary Power CircuitAuxiliary Power Failure Detection Output Current Detection W18Input Voltage Detection Located at NH-SYS-M board System MCU and Control CircuitOutput Voltage Detection Located at NH-SYS-M board System MCU and Control CircuitBattery Voltage Detection UP10BBypass SCR Short-Circuit Detection Scrst RBypass SCR Driver TSA1Watchdog for System MCU LCD Panel Control Circuit To LCDFan Control Circuit Located on NH-SYS-M board System MCU and Control CircuitBypass SCR Temperature Detection Communication Circuit for RS232RS232 Port Communication Circuit for SlotsCommunication Circuit for Output Dry Contact Output DRY ContactCommunication Circuit for Input Dry Contact and Repo Input DRY ContactExternal Battery Cabinet Temperature Detection EXTBTEMP1Detection Circuit for Manual Bypass Switch Detection Circuit for Output BreakerControl Circuit for Power Module CentralokTo PM1 to PM2 CM93 CM106 CM109 Control Circuit for External ParallelTheory of Operation Emergency Power Off EPO Communication01 RS232 Port 02a Front Control Panel02c Remote Emergency Power Off Repo02b Setting Eeprom on the NH-M Board Polling and Updating EepromCalibrating Eeprom Gain Setting Output Dry Contact Status Upgrading Firmware for the System Board Output Manual Bypass Main Input N C S T G R G I N G R a D E Communication Upgrading Firmware for the Power Module PM1 U P S T G R G I N Link the UPS to a PC via the RS232 port Communication Communication Communication T I N G L O W E D Downloading the Event Log Front View of SU20KX and SU40KX Internal BatteryBattery Strings Installing and Removing Internal Batteries Terminals Battery compartment. Warning Observe proper polarity by Connecting negative to negative black to black and positiveDamage the UPS system and create a serious risk of personal Injury and property damageBattery Cabinet 2a BP480V26B 2b BP480V40CInternal Battery 2d W1 and W2 Cables 2e Connection between UPS and Battery Cabinet2f Wiring between UPS and Battery Cabinet 1a Warning Message List TroubleshootingAlarm Messages 1b Power Module Warning Message List ConditionTroubleshooting Flow Charts Main VOLT/FREQ NOKMain Sequence NOK Bypass VOLT/FREQ NOK Bypass Static Switch Over Temperature Bypass Sequence NOKBypass Static Switch Fault Bypass Static Switch OverloadSame fault message? Replace the power module UPS Internal Comm Abnormal10a Battery Test FailBattery Over Charge Battery BAD 11a 11bBypass FAN Failure 12a 12b 12cTransformer Overheat 13a 13bPS Output Volt NOK 14a 14bPS EXT Parallel Comm Abnormal 15a 15bParallel Failure 16a 16bRedundancy Loss 17aPower Module Failure Power Module Identify115 116 Power Module Replacement AC Input DC Input Output 119 120 Preventive Maintenance Safety OverviewUPS Procedure Suggested tools and suppliesInternal Battery Procedure Appendix a Service Equipment and Tools Recommended Equipment and ToolsSoftware Tools Multi-Meter OscilloscopeAppendix B Torque Table KX ModelsTable B.1 Fig B.aTable B.3 ModelsTable B.2 Fig B.b Fig B.c Fig B.d KTV ModelsTable B.4 NH-SYS-R Board Appendix C PCB and Test PointNH-SYS-P Board