Tripp Lite SU60KX manual PS Output Volt NOK, 14a 14b

Page 92

5 Troubleshooting (continued)

5.2 Troubleshooting Flow Charts (continued)

5.2.14 “PS OUTPUT VOLT NOK”

Start

Is the output

N

 

Fix the connection

wire connection

 

 

 

 

OK?

 

 

 

 

 

 

 

Y

 

 

 

 

 

 

 

 

 

END

Fix the connection

N

Are the Actual value and LCD value the same?

Y

Check if any power

module output voltages

are out of range(4)

END

 

Is the

Y

Is the

(1)

N

Wire #10

LCD value

 

 

 

 

connection

 

zero?

 

 

 

OK?

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

 

 

Y

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace P board or M

 

 

 

 

board (3)

 

 

 

 

Calibrate parameter on

 

 

 

 

EEPROM(2)

 

 

 

Fig 5.2.14a

Note (1): Wire #10 connects CNP9 on the NH-SYS-P board with CNFC20 on the NH-SYS-FC board (Figure 5.2.14b).

Note (2): To learn about EEPROM parameter setting and calibration, refer to section 3.2.

Note (3): For the location of the NH-SYS-P board and NH-SYS-M boards, turn to section 1.5. To replace the NHS-SYS-M board, remove the EEPROM chip from the old NHS-SYS-M board and insert it into the new one.

Note (4): Check the output voltage of each power module one at a time. If normal, check the next power module.

Fig 5.2.14b

110

Image 92
Contents Th Street, Chicago, IL 60609 USA Table of Contents KX Models Basic OperationTechnical Specifications KTV Models SU40K SU60K SU60KTV SU80KTVSU80K Model Model Capacity SU80K 80kVA/64kWControl Panel Features FeaturesAdvanced Features Front and Rear Panel Features 3a SU40KX front3b SU40KX rear 3c SU40K front 3d SU40K rear 3e SU80K front 3f SU80K rear System Layout Internal Battery LayoutOperating Principles Opening and Closing the Unit Power Module Layout3a Power Module Block Diagram Online Normal Mode Single UPS Battery Backup Mode Single UPSAuto Bypass Mode Single UPS Manual Bypass Mode Single UPSAuto Bypass Mode Parallel UPS Online Mode Parallel UPSBattery Backup Mode Parallel UPS Manual Bypass Mode Parallel UPS Hot Standby Mode Parallel UPSControl Panel and Breaker Diagrams Normal LED Battery LED Bypass LED Fault LEDPreliminary Checklist Single UPS Standard Start-Up Procedure Single UPSBattery Start-Up Procedure Single UPS Manual Bypass Procedure Single UPS Shutdown Procedure Single UPSPreliminary Checklist Parallel UPS Start-Up Procedure Parallel UPSShutdown Procedure Parallel UPS Manual Bypass Procedure Parallel UPS Switching from Manual Bypass to Normal Mode Parallel UPS Printed Circuit Boards PCB SU80KX SU60KX SU40KX SU80KTV SU20KXPCB Location System F3 FB M LA, LB, LC, LD Models LA, LB, LC LA, LB, LC, LD F1BYP F1MAIN F2BYP F2MAIN LCD PCB Location Power Module PCB Board Name DescriptionBlock and Wiring Diagrams 1a SU20KX Block Diagram1c SU40KX Block Diagram KX ModelsTheory of Operation DC Auxiliary Power CircuitAuxiliary Power Failure Detection Output Current Detection W18Input Voltage Detection Located at NH-SYS-M board System MCU and Control CircuitOutput Voltage Detection Located at NH-SYS-M board System MCU and Control CircuitBattery Voltage Detection UP10BBypass SCR Short-Circuit Detection Scrst RBypass SCR Driver TSA1Watchdog for System MCU LCD Panel Control Circuit To LCDFan Control Circuit Located on NH-SYS-M board System MCU and Control CircuitBypass SCR Temperature Detection Communication Circuit for RS232RS232 Port Communication Circuit for SlotsCommunication Circuit for Output Dry Contact Output DRY ContactCommunication Circuit for Input Dry Contact and Repo Input DRY ContactExternal Battery Cabinet Temperature Detection EXTBTEMP1Detection Circuit for Manual Bypass Switch Detection Circuit for Output BreakerControl Circuit for Power Module CentralokTo PM1 to PM2 CM93 CM106 CM109 Control Circuit for External ParallelTheory of Operation Emergency Power Off EPO Communication01 RS232 Port 02a Front Control Panel02c Remote Emergency Power Off Repo02b Setting Eeprom on the NH-M Board Polling and Updating EepromCalibrating Eeprom Gain Setting Output Dry Contact Status Upgrading Firmware for the System Board Output Manual Bypass Main Input N C S T G R G I N G R a D E Communication Upgrading Firmware for the Power Module PM1 U P S T G R G I N Link the UPS to a PC via the RS232 port Communication Communication Communication T I N G L O W E D Downloading the Event Log Front View of SU20KX and SU40KX Internal BatteryBattery Strings Installing and Removing Internal Batteries Terminals Battery compartment. Warning Observe proper polarity by Connecting negative to negative black to black and positiveDamage the UPS system and create a serious risk of personal Injury and property damageBattery Cabinet 2a BP480V26B 2b BP480V40CInternal Battery 2d W1 and W2 Cables 2e Connection between UPS and Battery Cabinet2f Wiring between UPS and Battery Cabinet 1a Warning Message List TroubleshootingAlarm Messages 1b Power Module Warning Message List ConditionTroubleshooting Flow Charts Main VOLT/FREQ NOKMain Sequence NOK Bypass VOLT/FREQ NOK Bypass Static Switch Over Temperature Bypass Sequence NOKBypass Static Switch Fault Bypass Static Switch OverloadSame fault message? Replace the power module UPS Internal Comm Abnormal10a Battery Test FailBattery Over Charge Battery BAD 11a 11bBypass FAN Failure 12a 12b 12cTransformer Overheat 13a 13bPS Output Volt NOK 14a 14bPS EXT Parallel Comm Abnormal 15a 15bParallel Failure 16a 16bRedundancy Loss 17aPower Module Failure Power Module Identify115 116 Power Module Replacement AC Input DC Input Output 119 120 Preventive Maintenance Safety OverviewUPS Procedure Suggested tools and suppliesInternal Battery Procedure Appendix a Service Equipment and Tools Recommended Equipment and ToolsSoftware Tools Multi-Meter OscilloscopeAppendix B Torque Table KX ModelsTable B.1 Fig B.aTable B.3 ModelsTable B.2 Fig B.b Fig B.c Fig B.d KTV ModelsTable B.4 NH-SYS-R Board Appendix C PCB and Test PointNH-SYS-P Board