Word 1 | System Info Register | |||
| This word enables the module’s operation, and specifies if user shutdown values are | |||
| expected. |
|
| |
|
|
|
|
|
|
|
| CAUTION | |
|
|
|
|
|
|
|
| Zero is an illegal value for the parameter field (words | |
|
|
| A zero value in the parameter field will cause an output shut down state, | |
|
|
| and no inputs or outputs are updated. Any bit set in the parameter field, | |
|
|
| including those defined as not used, will enable the module. | |
|
|
| Failure to follow this precaution can result in injury or equipment | |
|
|
| damage. | |
|
|
|
|
|
|
|
|
| |
| Word 1 |
| Description | |
|
|
|
| |
| Bits 0 ... 14 |
| Not used | |
|
|
|
| |
| Bit 15 |
| 0 = Disables user defined shutdown values. | |
|
|
|
| 1 = Enables user defined shutdown values. |
|
|
|
|
|
Valid setting for word one are 0001 ... FFFF
The module’s default value at
(module shut down).
Word 2 | Discrete Fail State Reaction and Value Register | |||
| This word combines the value and reaction in a fail state. | |||
|
|
|
| |
| Word 2 | Description | ||
|
|
|
| |
| Bit 0 ... 7 | Discrete fail state value for outputs 1 ... 8 | ||
|
|
|
| |
| Bits 8 ... 13 | Not used | ||
|
|
|
|
|
| Bit 14 | 0 | = hold last value, 1 = user defined value | |
|
|
|
|
|
| Bit 15 | 0 | = all outputs reset, 1 = check bit 14 | |
|
|
|
|
|
|
|
|
|
|
Word 3 | Analog Fail State Reaction Register | |
| This word contains two 2 bit fields that define the fail state for each channel. The four | |
| possible values of fail state are as follows. | |
|
|
|
| 2 Bit Value | Fail State |
|
|
|
| 00 | Minimum output voltage |
|
|
|
| 01 | Hold last value (default) |
|
|
|
| 10 | User defined shutdown value |
|
|
|
| 11 | Hold last value (not normally used) |
|
|
|
14 | 31005009 01 November 2003 |