Discrete Outputs The following table contains specifications for discrete outputs.

Description

Solid state switch

 

 

Operating Voltage

16 - 42 VDC

 

 

Absolute Minimum Voltage

12 VDC

 

 

Absolute Maximum Voltage

45 VDC

 

 

Maximum Voltage

50 VDC for 1 ms

 

 

Number of Points

8

 

 

Number of Groups

1

 

 

Points per Group

8

 

 

Current Capacity

250 mA per point 2 amps per module

 

 

Type of Signal

True high (sourcing)

 

 

Leakage Current

< 1 mA @ 42 VDC

 

 

Surge Current

5 amps for 1 ms

 

 

On State Voltage Drop

< 1.0 VDC max at 0.25 amp current

 

 

Fault Sensing

Overload and short circuit

 

 

Fault Reporting

System bit

 

 

Response Time

1.8 ms OFF to ON

 

1.8 ms ON to OFF

 

 

CAUTION

Discrete VDC outputs incorporate thermal shutdown and overload protection.

The output current of a shorted output is limited to a nondestructive value. The short circuit heats the output driver, and the output will switch off. The output will switch on again if the driver leaves the over temperature condition and the user resets the output under program control. If the short circuit still exists after the output point is reset, the driver will reach the over temperature condition again and will switch off again.

Failure to follow this precaution can result in injury or equipment damage.

8

31005009 01 November 2003

Image 8
Contents 170AMM11030 Analog/Digital Momentum I/O Base User Guide VersionSafety Information 170AMM11030 Analog/Digital Momentum I/O Base Front Panel ComponentsOverview Front PanelComponents of the I/O Module LED Illustration The illustration below shows the LEDsFollowing table describes the LEDs DescriptionsSpecifications SpecificationsGeneral Output is protected against short-circuiting and overloadTo ground Number of Channels Output Ranges Type of Signal Fault SensingFault Reporting Operating VoltageTerminals on the I/O base and an optional busbar Physical DimensionsInternal Pin Connections Field Wiring Guidelines Wiring Diagrams Discrete input and output analog input and outputDiscrete I/O DevicesMap Analog I/ORegister for Outputs Word FunctionDamage WordZero is an illegal value for the parameter field words 4x Registers Words 4Register for Inputs RangeOutput Operating Range Input register is arranged as followsBits Description Set to an OFF stateDiscrete Input Register Words 3 Analog Input RegisterWords 5 Words 5 .. are not usedOutput Word Analog MapInput Word Points are field wired to row Discrete I/O Points and IEC Compliant Data MappingInput and Output Ranges Ranges Decimal Values Input Measuring Range ±10Output Measuring Range ±10