Schneider Electric 170AMM11030 manual Number of Channels Output Ranges

Page 7

Analog Outputs The following table contains specifications for analog outputs.

Number of Channels

2

 

 

 

 

Output Ranges

± 10 VDC

 

 

 

Resolution

14 Bit

 

 

 

Conversion Times

1.60 ms for all channels

 

 

 

Output Setting Time

3.2 ms to 0.1% of final value

 

 

 

Accuracy

Max. error @ 25°C ± 0.4% for -10 to +10 VDC

 

 

 

Linearity

± 1 LSB, Guaranteed Monotonic

 

 

 

Output Impedance

< 0.2 Ohms

 

 

 

Maximum Output Current

5 mA

 

 

 

Maximum Temperature Drift @ 60°C

± 100 ppm of full scale per °C

 

 

 

Data Format

Left justified

 

 

 

Crosstalk Between Channels

80 dB

 

 

 

Load

> 2K Ohms @ ±10 VDC

 

 

 

Channel to Channel Isolation

700 VDC

 

 

 

 

 

 

Discrete Inputs The following table contains specifications for discrete inputs.

 

Operating Voltage

16 to 42 VDC

 

 

 

 

Absolute Minimum Voltage

12 VDC

 

 

 

 

Absolute Maximum Voltage

45 VDC

 

 

 

 

Number of Points

16

 

 

 

 

Number of Groups

1

 

 

 

 

Points per Group

16

 

 

 

 

Type of Signal

True high (sourcing)

 

 

 

 

IEC 1131 I/O Type @ 24 VDC

1+

 

 

 

 

Minimum ON Voltage

> 11 VDC

 

 

 

 

Maximum OFF Voltage

< 5 VDC

 

 

 

 

Input Operating Current

1.2 mA and lower, off

 

 

2.5 to 10 mA, on

 

 

 

 

Input Voltage

 

 

 

 

 

Range

16 to +42 VDC

 

 

 

 

Surge

75 volt peak for 10 ms

 

 

 

 

Response Time

6.2 ms OFF to ON @ 24 VDC

 

 

7.3 ms ON to OFF @ 24 VDC

 

 

 

 

 

 

 

 

 

31005009 01 November 2003

7

Image 7
Contents Version 170AMM11030 Analog/Digital Momentum I/O Base User GuideSafety Information Front Panel 170AMM11030 Analog/Digital Momentum I/O BaseFront Panel Components OverviewDescriptions Components of the I/O ModuleLED Illustration The illustration below shows the LEDs Following table describes the LEDsOutput is protected against short-circuiting and overload SpecificationsSpecifications GeneralTo ground Number of Channels Output Ranges Operating Voltage Type of SignalFault Sensing Fault ReportingInternal Pin Connections Physical DimensionsTerminals on the I/O base and an optional busbar Field Wiring Guidelines Devices Wiring DiagramsDiscrete input and output analog input and output Discrete I/OAnalog I/O MapWord Function Register for OutputsZero is an illegal value for the parameter field words WordDamage Words 4 4x RegistersInput register is arranged as follows Register for InputsRange Output Operating RangeDiscrete Input Register Set to an OFF stateBits Description Words 5 .. are not used Words 3Analog Input Register Words 5Input Word Analog MapOutput Word Discrete I/O Points and IEC Compliant Data Mapping Points are field wired to rowRanges Decimal Values Input Measuring Range ±10 Input and Output RangesOutput Measuring Range ±10