Schneider Electric 170AMM11030 manual Specifications, General

Page 5

Specifications

Overview

This section contains specifications for the 170AMM11030 Momentum I/O base.

General

 

 

The following table contains general specifications for the I/O base. Each discrete

Specifications

output is protected against short-circuiting and overload.

 

 

 

 

External Power Requirement

 

 

 

 

 

Normal Operating Voltage Range

16 to 42 VDC

 

 

 

 

Absolute Minimum Voltage

12 VDC

 

 

 

 

Absolute Maximum Voltage

45 VDC

 

 

 

 

Electrical

 

 

 

 

 

Module Current

400 mA at 24 VDC

 

 

 

 

EMC for Industrial Environment

 

 

 

 

 

Immunity

IEC 1131-2

 

 

Surge on auxiliary power supply 500 V

 

 

 

 

Emissions

EN 50081-2

 

 

 

 

ENV 50140

10 V/M

 

 

 

 

Agency Approvals

UL, CSA, CE, FM Class 1, Div. 2 (pending)

 

 

 

 

Isolation

 

 

 

 

 

Discrete I/O point to discrete I/O point

None

 

 

 

 

Field to ground

500 VAC

 

 

 

 

Field to communication adapter

500 VAC

 

 

 

 

Analog output channel to channel

700 VDC

 

 

 

 

Environmental

 

 

 

 

 

Storage Temperature

-40 to 85° C

 

 

 

 

Operating Temperature

0 to 60° C

 

 

 

 

Humidity Operating

95% RH @ 60° C

 

 

 

 

Humidity Non-Operating

95% RH @ 60° C

 

 

 

 

Vibration Operating

10 - 57 HZ 0.075 MMDA

 

 

57 - 150 HZ 1 G

 

 

 

 

Shock Non-Operating

15 G, 11 MS, 3 shocks/axis

 

 

 

 

Free Fall (Unpackaged)

0.1 meter

 

 

 

 

 

 

31005009 01 November 2003

5

Image 5
Contents Version 170AMM11030 Analog/Digital Momentum I/O Base User GuideSafety Information Front Panel Components 170AMM11030 Analog/Digital Momentum I/O BaseOverview Front PanelLED Illustration The illustration below shows the LEDs Components of the I/O ModuleFollowing table describes the LEDs DescriptionsSpecifications SpecificationsGeneral Output is protected against short-circuiting and overloadTo ground Number of Channels Output Ranges Fault Sensing Type of SignalFault Reporting Operating VoltageTerminals on the I/O base and an optional busbar Physical DimensionsInternal Pin Connections Field Wiring Guidelines Discrete input and output analog input and output Wiring DiagramsDiscrete I/O DevicesAnalog I/O MapWord Function Register for OutputsDamage WordZero is an illegal value for the parameter field words Words 4 4x RegistersRange Register for InputsOutput Operating Range Input register is arranged as followsBits Description Set to an OFF stateDiscrete Input Register Analog Input Register Words 3Words 5 Words 5 .. are not usedOutput Word Analog MapInput Word Discrete I/O Points and IEC Compliant Data Mapping Points are field wired to rowRanges Decimal Values Input Measuring Range ±10 Input and Output RangesOutput Measuring Range ±10