Checking Compatibility
Check that your rack is compatible with the
TABLE 2-1 Rack Compatibility
Item | Requirement |
|
|
Structure | |
| rear). |
Rack horizontal opening and | Conforms to ANSI/EIA |
unit vertical pitch | 60927 standards. |
Distance between front and rear | Minimum 610 mm and Maximum 915 mm (24 |
mounting planes | inches to 36 inches). |
Clearance depth in front of front | Distance to front cabinet door is at least 25.4 |
mounting plane | mm (1 inch). |
Clearance depth behind front | Distance to rear cabinet door is at least 800 |
mounting plane | mm (31.5 inches) with the cable management |
| arm, or 700 mm (27.5 inches), without the |
| cable management arm. |
Clearance width between front | Distance between structural supports and |
and rear mounting planes | cable troughs is at least 456 mm (18 inches). |
Server Dimensions | Length: (not including PSU handle): 28.0 inches |
| (711.2 mm) |
| Width: (not including ears): 16.75 inches (425.5 |
| mm) |
| Height: 1U |
|
|
Caution – Always load equipment into a rack from the bottom up so that it will not become
Caution – Ensure that the temperature in the rack does not exceed the server’s maximum ambient rated temperatures. Consider the total airflow requirements of all equipment installed in the rack to ensure that the equipment is operated within its specified temperature range.
Chapter 2 Installing the Sun Fire X4150 Server Into a Rack with