Installing the Server Into a Rack With Optional Slide Rails
The service label on the top cover of the Sun Fire X2100 M2 server contains instructions for installing your server into a
http://www.sun.com/documentation
The slide rails for the Sun Fire X2100 M2 server are compatible with a wide range of equipment racks that meet the following standards:
■
■Rack horizontal opening and unit vertical pitch conforming to ANSI/EIA
■Distance between front and rear mounting planes of 610 mm and 915 mm (24 inches to 36 inches).
■Clearance depth (to front cabinet door) in front of front rack mounting plane at least 25.4 mm (1 inch).
■Clearance depth (to rear cabinet door) behind front rack mounting plane at least 800 mm (31.5 inches) with the cable management arm, or 700 mm (27.5 inches), without the cable management arm.
■Clearance width (between structural supports and cable troughs) between front and rear mounting planes at least 456 mm (18 inches).
Caution – Always load equipment into a rack from the bottom up so that it will not become
Caution – Ensure that the temperature in the rack does not exceed the server’s maximum ambient rated temperatures. Consider the total airflow requirements of all equipment installed in the rack, to ensure that the equipment is operated within its specified temperature range.
4 Sun Fire X2100 M2 Server Installation Guide • August 2006