Delta MCS-1800 manual Cleaning and Maintenance, Removing and Replacing a Rectifier Unit

Page 29

DELTA MCS-1800 3U Power Shelf

Installation, Operations and

Maintenance Manual

9 Maintenance

9.1Cleaning and Maintenance

9.1.1General

Special maintenance is not necessary for this system, unless the system is being operated in a severely harsh environment (dusty environment). The front panels and the cover of the DC distribution cabinet were treated with a special coating. Do not use organic cleanser or volatile solvent because corrosion damage may occur. For periodic cleaning, brush the dust from the cover and panel. If necessary, use a gentle cleanser or a lightly dampened lint free cloth to remove any dirt or smudges.

9.1.2 Periodic Maintenance

Periodic maintenance is not required for normal operation. If necessary, wipe dust from the front of the power system using a lint free, soft cloth and gently wipe the front of the distribution module, the ALU, and the rectifiers. If necessary, use a gentle detergent to clean.

Warning: Do not use a spray cleanser to clean the equipment. Using a spray cleanser directly on the equipment can result in serious equipment damage.

9.2Removing and Replacing a Rectifier Unit

9.2.1Removing a Rectifier

Warning: Do not touch the DC output bus when pulling out the PSU module.

To remove a rectifier, perform the following steps.

1.Switch off PSU module.

2.Loosen the captive retaining screws located on the bottom of the front panel.

3.Pull out the rectifier unit slowly from the shelf.

9.2.2Replacing a Rectifier

To replace a rectifier, perform the following steps:

1.Make sure the breaker on the front panel of PSU is switched off.

2.Install the rectifier unit carefully. Place the rectifier on the shelf, ensuring that the rails are on the track.

Warning: Do not force the module into the slot. If does not slide in and connect easily, remove and reset the unit.

3.Lock the rectifier into position by screwing in the captive retaining screws located at the bottom of the rectifier.

4.Switch on the PSU and check the AC ON LED lights on the front of the PSU on the front of the rectifier. AC ON LED lights.

9-1

Image 29
Contents Delta MCS-1800 Power Shelf Delta MCS 1800 3U Power Shelf Table of Contents System Alarms and Troubleshooting System Start -Up ProcedureMaintenance Acronyms and AbbreviationsGeneral Using This ManualProduct Description Product Main FeaturesSystem Specifications Environmental Data Specification ValueInput Electrical DataOutput Status/Alarm IndicatorsMechanical Data Dimension Value Specifications Power Supply Unit PSUDescription ElectricalCondition Response ProtectionEnvironmental AdjustmentsAdjustment Description Operation and Adjustment PSU Block Diagram System AlarmCurrent Limit Setting PSU Operating PrincipleInput Characteristics Alarm Control UnitCharacteristic Value Input Voltage Range OutputIndicators Settings DescriptionVoltage/Current Relay OutputPhysical ALU Alarm Signal DescriptionsSettings and Control Alarm Control Unit Block DiagramAC High Voltage Alarm Settings Description CommentAC Low Voltage Alarm Temperature AlarmControl Settings Description Comment Remote SMR On/Off Temperature Shut DownHvsd Recovery Floating / Equalize controlBattery Connections System equipped with PDU Low Voltage Battery Disconnect System equipped with PDUDC Distribution DC CablingInstallation AC High Voltage Aux. Relay output wiring Temperature and Alarm ConnectionsSignal I/P connector System Start-Up Procedure AC Fail Voltage Alarm Description System Alarms and TroubleshootingHigh Voltage Shutdown Alarm High Voltage Alarm DescriptionFuse/Circuit Breaker Fail Alarm System equipped with PDU Low Voltage AlarmLow Voltage Disconnect Alarm System equipped with PDU Rectifier Fail Alarm Alarm Unit FailRemoving and Replacing a Rectifier Unit MaintenanceCleaning and Maintenance Cispr Acronyms and Abbreviations10-2 10-3 Attachment ES 48/120-JAAxx、ES 24/200-JAAxx -48V/+24VPower Shelf PDU Delta MCS 1800 3U Power Shelf Alarm Relay Output 4ES 48/120-JAAxx Shelf Wiring MCS 1800 Series Shelf 5ES 24/200-JAAxx Shelf Wiring Diagram ES 48/90-JBAxx -48V Power Shelf With PDU ES 48/90-JBAxx DC Output Lug Distribution Delta MCS 1800 3U Power Shelf 台達電子工業股份有限公司 交換式電源供應器 ES 48/90-JBAxx Battery and Load Breaker Distribution ES 48/90-JBAxx Shelf Wiring MCS 1800 Series Shelf ES 48/90-JFAxx -48V Power Shelf With PDU ES 48/90-JFAxx Alarm Relay Output connectors ES 48/90-JFAxx AC Input Connector ES 48/90-JFAxx Battery Temperature ES 48/90-JFAxx DC Output Lug Distribution ES 48/90-JFAxx Shelf Wiring MCS 1800 Series Shelf Alarm Control Unit SMR RFA Power Supply Unit Eeprom SMR Block Diagram TEL -3-4526107P/N MCS-1800 Power Shelf