DELTA MCS-1800 3U Power Shelf

Installation, Operations and

Maintenance Manual

Figure 1-1 shows a front view of shelf.

Environmental Data

System Environmental Data

Specification

Value

Operating temperature

0to +50

Storage temperature

-40to +70

Humidity

0% to 95% RH

Altitude

-300 ft. to 10,000 ft.

Weight

Approximately 48 lbs.

Lightning/surge

ANSI/IEEE C62.41-1, and IEC 1000-4-5

Seismic

Bellcore GR-63-CORE, Zone 4

2.3.4 -48V System with Power Distribution and Rectifiers(MODUL NAME: ES48/90-JFAxx)

(1)

AC Input:

175VAC ~ 275VAC, 36Amps. Max

(2)

System Capacity:

90Amps. Max.

(3)

Rectifier:

-48V/30A×1~3

(4)

Control and Supervisory

 

(5)

Load Distribution:

100A Breaker×4 @ Single Pole

(6)

Low Voltage Disconnect Switch: 100A×1 @ Single Pole at Battery Side

Figure 1-1 shows a front view of shelf.

 

Environmental Data

 

 

System Environmental Data

 

 

 

 

 

 

Specification

Value

 

 

Operating temperature

0to +50

 

 

Storage temperature

-40to +70

 

 

Humidity

0% to 95% RH

 

 

Altitude

-300 ft. to 10,000 ft.

 

 

Weight

Approximately 48 lbs.

 

 

EMI/FRI

FCC Part 15, Class B and CISPR 22, Class B

 

 

Lightning/surge

ANSI/IEEE C62.41-1, and IEC 1000-4-5

 

 

Seismic

Bellcore GR-63-CORE, Zone 4

 

 

Safety

CUL and UL Listed and Marked

2.4 Electrical Data

The system electrical data is provided in the following tables.

2.4.1 Input

2-3

Image 8
Contents Delta MCS-1800 Power Shelf Delta MCS 1800 3U Power Shelf Table of Contents System Start -Up Procedure System Alarms and TroubleshootingMaintenance Acronyms and AbbreviationsUsing This Manual GeneralProduct Description Product Main FeaturesSystem Specifications Specification Value Environmental DataElectrical Data InputStatus/Alarm Indicators OutputMechanical Data Dimension Value Power Supply Unit PSU SpecificationsDescription ElectricalProtection Condition ResponseEnvironmental AdjustmentsAdjustment Description Operation and Adjustment System Alarm PSU Block DiagramCurrent Limit Setting PSU Operating PrincipleAlarm Control Unit Input CharacteristicsCharacteristic Value Input Voltage Range OutputSettings Description IndicatorsVoltage/Current Relay OutputALU Alarm Signal Descriptions PhysicalAlarm Control Unit Block Diagram Settings and ControlSettings Description Comment AC High Voltage AlarmAC Low Voltage Alarm Temperature AlarmTemperature Shut Down Control Settings Description Comment Remote SMR On/OffHvsd Recovery Floating / Equalize controlLow Voltage Battery Disconnect System equipped with PDU Battery Connections System equipped with PDUDC Distribution DC CablingInstallation AC High Voltage Aux. Relay output wiring Temperature and Alarm ConnectionsSignal I/P connector System Start-Up Procedure System Alarms and Troubleshooting AC Fail Voltage Alarm DescriptionHigh Voltage Shutdown Alarm High Voltage Alarm DescriptionFuse/Circuit Breaker Fail Alarm System equipped with PDU Low Voltage AlarmLow Voltage Disconnect Alarm System equipped with PDU Alarm Unit Fail Rectifier Fail AlarmRemoving and Replacing a Rectifier Unit MaintenanceCleaning and Maintenance Acronyms and Abbreviations Cispr10-2 10-3 Attachment ES 48/120-JAAxx、ES 24/200-JAAxx -48V/+24VPower Shelf PDU Delta MCS 1800 3U Power Shelf Alarm Relay Output 4ES 48/120-JAAxx Shelf Wiring MCS 1800 Series Shelf 5ES 24/200-JAAxx Shelf Wiring Diagram ES 48/90-JBAxx -48V Power Shelf With PDU ES 48/90-JBAxx DC Output Lug Distribution Delta MCS 1800 3U Power Shelf 台達電子工業股份有限公司 交換式電源供應器 ES 48/90-JBAxx Battery and Load Breaker Distribution ES 48/90-JBAxx Shelf Wiring MCS 1800 Series Shelf ES 48/90-JFAxx -48V Power Shelf With PDU ES 48/90-JFAxx Alarm Relay Output connectors ES 48/90-JFAxx AC Input Connector ES 48/90-JFAxx Battery Temperature ES 48/90-JFAxx DC Output Lug Distribution ES 48/90-JFAxx Shelf Wiring MCS 1800 Series Shelf Alarm Control Unit SMR RFA Power Supply Unit Eeprom SMR Block Diagram TEL -3-4526107P/N MCS-1800 Power Shelf