Delta MCS-1800 manual Installation

Page 23

DELTA MCS-180 3U 0 Power Shelf

Installation, Operations and

Maintenance Manual

6 Installation

6.1 Preliminary Inspection

Prior to removing the system from the crate, note any damage to the carton. Remove the system from the packaging and inspect the shelf and components for any dents or damage. If any damage is noted, contact the carrier immediately.

6.2 System Mounting

The power system is typically shipped with the shelf in one carton and rectifiers in individual cartons. The shelf typically is shipped with the ALU and the distribution module. The module can be mounted in a 19”relay rack provided by the customer.

This system allows the relay rack to be installed as close to a rear wall as is necessary for the installation. The front of the system should be clear of all obstruction and allow room for proper ventilation, installation, and maintenance.

6.3 Module Installation

In order to reduce the weight of the system, all power modules can be removed from the shelf when mounting the shelf onto a rack.

1)Ensure that the AC power is isolation.

2)Loosen the fixed thumbscrew on the rectifier and pull the rectifier out.

3)Loosen the fixed thumbscrew on the ALU panel and pull the ALU out.

4)Reverse the procedure, to install the rectifier and ALU.

6.4Shelf Wiring

The shelf comes fully assembled and is equipped with the ALU and the distribution module. All internal connections are made at the factory. No internal, shelf, or module wiring is required.

6.5 AC Input Connections

The power system is equipped with one power terminal located at the center rear of the shelf.

Warning:

1. AC power wire cannot less than AWG 10 and failure to use the appropriate power wire

 

causes safety hazards.

2.Each shelf requires a properly grounded AC input feeds supplied by Delta.

3.The system operates at AC voltages that can produce fatal electrical shock. Installation and maintenance personnel must observe all safety precautions.

4.Confirm the operating voltage and proper grounding of the incoming line before proceeding.

6.6Battery String Connections (System equipped with PDU)

Warning:

1. Verify the polarity of the battery leads prior to connecting the battery cables to the system.

 

Failure to connect the battery cables correctly to the system can cause damage to batteries

 

and the system.

6-1

Image 23
Contents Delta MCS-1800 Power Shelf Delta MCS 1800 3U Power Shelf Table of Contents Acronyms and Abbreviations System Start -Up ProcedureSystem Alarms and Troubleshooting MaintenanceGeneral Using This ManualProduct Description Product Main FeaturesSystem Specifications Environmental Data Specification ValueInput Electrical DataOutput Status/Alarm IndicatorsMechanical Data Dimension Value Electrical Power Supply Unit PSUSpecifications DescriptionCondition Response ProtectionEnvironmental AdjustmentsAdjustment Description Operation and Adjustment PSU Operating Principle System AlarmPSU Block Diagram Current Limit SettingInput Voltage Range Output Alarm Control UnitInput Characteristics Characteristic ValueRelay Output Settings DescriptionIndicators Voltage/CurrentPhysical ALU Alarm Signal DescriptionsSettings and Control Alarm Control Unit Block DiagramTemperature Alarm Settings Description CommentAC High Voltage Alarm AC Low Voltage AlarmFloating / Equalize control Temperature Shut DownControl Settings Description Comment Remote SMR On/Off Hvsd RecoveryDC Cabling Low Voltage Battery Disconnect System equipped with PDUBattery Connections System equipped with PDU DC DistributionInstallation AC High Voltage Aux. Relay output wiring Temperature and Alarm ConnectionsSignal I/P connector System Start-Up Procedure High Voltage Alarm Description System Alarms and TroubleshootingAC Fail Voltage Alarm Description High Voltage Shutdown AlarmFuse/Circuit Breaker Fail Alarm System equipped with PDU Low Voltage AlarmLow Voltage Disconnect Alarm System equipped with PDU Rectifier Fail Alarm Alarm Unit FailRemoving and Replacing a Rectifier Unit MaintenanceCleaning and Maintenance Cispr Acronyms and Abbreviations10-2 10-3 Attachment ES 48/120-JAAxx、ES 24/200-JAAxx -48V/+24VPower Shelf PDU Delta MCS 1800 3U Power Shelf Alarm Relay Output 4ES 48/120-JAAxx Shelf Wiring MCS 1800 Series Shelf 5ES 24/200-JAAxx Shelf Wiring Diagram ES 48/90-JBAxx -48V Power Shelf With PDU ES 48/90-JBAxx DC Output Lug Distribution Delta MCS 1800 3U Power Shelf 台達電子工業股份有限公司 交換式電源供應器 ES 48/90-JBAxx Battery and Load Breaker Distribution ES 48/90-JBAxx Shelf Wiring MCS 1800 Series Shelf ES 48/90-JFAxx -48V Power Shelf With PDU ES 48/90-JFAxx Alarm Relay Output connectors ES 48/90-JFAxx AC Input Connector ES 48/90-JFAxx Battery Temperature ES 48/90-JFAxx DC Output Lug Distribution ES 48/90-JFAxx Shelf Wiring MCS 1800 Series Shelf Alarm Control Unit SMR RFA Power Supply Unit Eeprom SMR Block Diagram TEL -3-4526107P/N MCS-1800 Power Shelf