DELTA
Installation, Operations and
Maintenance Manual
Table 1 displays the system input specifications.
Table 1 System Input Specifications
Specification
Value
Nominal range | 175 ~ 275VAC |
| 90 ~ 275VAC Full Load |
Operational range | 150V ~ 175Vac |
| 90V ~ 150Vac |
| 50℃ ~ 65℃ |
Frequency | 45 ~ 65Hz |
Power Factor | >0.99 @ 220VAC, Full Load |
THD | <5% @ 220VAC, Full Load |
Efficiency | >90% @ 220VAC, Full Load |
2.4.2 Output
Table 2 displays the system output specifications.
Table 2 System Output Specifications
| Specification | Value |
|
|
|
| DC Volts | 38~60 VDC |
| 20~30 VDC (+24V Version) | |
|
| |
| Load regulation | <1% |
|
|
|
| Line regulation | <0.2% |
|
|
|
| Current Limit | 110% |
|
|
|
| Current share | <5% |
|
|
|
| Noise: |
|
| Audio band | <2mv |
| Wide band | <10 mVrms |
| Acoustic | <55 dBA |
2.4.3 Status/Alarm Indicators |
|
The Power Shelf has the following status/alarm indicators:
Load Current
AC ON
Rectifier Fail Alarm (RFA)
Current Limit (CL)
Float/Equalize (FL/EQU)
Major Alarm (MAJ)
Minor Alarm (MIN)
High Voltage Alarm (HV)
High Voltage Shutdown (HVSD)
Low Voltage Alarm (LV)
Low Voltage Disconnect Open (LVDS OPEN)
Fuse Blown (FUSE ALM)
AC Fail (AC FAIL)