Delta MCS-1800 manual Product Description, Product Main Features, System Specifications

Page 6

DELTA MCS-1800 3U Power Shelf

Installation, Operations and

Maintenance Manual

2 Product Description

2.1Product Description

This power Shelf consists of modular rectifiers, an Alarm Control Unit (ALU), and a DC distribution module. Up to four rectifiers and an alarm unit can be equipped on a shelf containing an integrated distribution module. The rectifiers can operate from a universal range of AC line voltages. The High Line (HL) operations are defined at an AC line input range of 165VAC~ 264VAC. The Low Line (LL) operations are defined at an AC line input range of 90 VAC-130 VAC.

The system is controlled and monitored by the ALU. System level rectifier voltage settings, system status, and alarms are displayed on the ALU. The system float voltage, equalize voltage, and alarm thresholds are set from RMS. The ALU also provides automatic derating of the output power over the whole operating line voltages. Figure 1 shows different functional blocks of the system.

2.2Product Main Features

The Power Shelf has the following main features:

-48 VDC/120 Amps, or +24VDC/200Amps, N+1 redundancy Modular design for scalable, cost effective expansion

Front access for simple installation and maintenance High power density

Active Power Factor Correction (>. 99PFC) High efficiency

Temperature compensated float voltage control Alarm Control Unit

Low Voltage Battery Disconnect (LVBD) (System equipped with PDU) Remote Monitoring and control

2.3System Specifications

The system specifications are provided in the following sections.

2.3.1 -48V Standard Power Shelf Configuration(MODUL NAME: ES48/120-JAAxx)

(1)

AC Input:

175VAC ~ 275VAC, 48Amps. Max

(2)

System Capacity:

120Amps. Max.

(3)

Rectifier:

-48V/30A×1~4

(4)Control and Supervisory Unit Figure 1 shows a front view of shelf.

2-1

Image 6
Contents Delta MCS-1800 Power Shelf Delta MCS 1800 3U Power Shelf Table of Contents Maintenance System Start -Up ProcedureSystem Alarms and Troubleshooting Acronyms and AbbreviationsUsing This Manual GeneralProduct Main Features System SpecificationsProduct Description Specification Value Environmental DataElectrical Data InputStatus/Alarm Indicators OutputMechanical Data Dimension Value Description Power Supply Unit PSUSpecifications ElectricalProtection Condition ResponseAdjustments Adjustment DescriptionEnvironmental Operation and Adjustment Current Limit Setting System AlarmPSU Block Diagram PSU Operating PrincipleCharacteristic Value Alarm Control UnitInput Characteristics Input Voltage Range OutputVoltage/Current Settings DescriptionIndicators Relay OutputALU Alarm Signal Descriptions PhysicalAlarm Control Unit Block Diagram Settings and ControlAC Low Voltage Alarm Settings Description CommentAC High Voltage Alarm Temperature AlarmHvsd Recovery Temperature Shut DownControl Settings Description Comment Remote SMR On/Off Floating / Equalize controlDC Distribution Low Voltage Battery Disconnect System equipped with PDUBattery Connections System equipped with PDU DC CablingInstallation Temperature and Alarm Connections Signal I/P connectorAC High Voltage Aux. Relay output wiring System Start-Up Procedure High Voltage Shutdown Alarm System Alarms and TroubleshootingAC Fail Voltage Alarm Description High Voltage Alarm DescriptionLow Voltage Alarm Low Voltage Disconnect Alarm System equipped with PDUFuse/Circuit Breaker Fail Alarm System equipped with PDU Alarm Unit Fail Rectifier Fail AlarmMaintenance Cleaning and MaintenanceRemoving and Replacing a Rectifier Unit Acronyms and Abbreviations Cispr10-2 10-3 Attachment ES 48/120-JAAxx、ES 24/200-JAAxx -48V/+24VPower Shelf PDU Delta MCS 1800 3U Power Shelf Alarm Relay Output 4ES 48/120-JAAxx Shelf Wiring MCS 1800 Series Shelf 5ES 24/200-JAAxx Shelf Wiring Diagram ES 48/90-JBAxx -48V Power Shelf With PDU ES 48/90-JBAxx DC Output Lug Distribution Delta MCS 1800 3U Power Shelf 台達電子工業股份有限公司 交換式電源供應器 ES 48/90-JBAxx Battery and Load Breaker Distribution ES 48/90-JBAxx Shelf Wiring MCS 1800 Series Shelf ES 48/90-JFAxx -48V Power Shelf With PDU ES 48/90-JFAxx Alarm Relay Output connectors ES 48/90-JFAxx AC Input Connector ES 48/90-JFAxx Battery Temperature ES 48/90-JFAxx DC Output Lug Distribution ES 48/90-JFAxx Shelf Wiring MCS 1800 Series Shelf Alarm Control Unit SMR RFA Power Supply Unit Eeprom SMR Block Diagram TEL -3-4526107P/N MCS-1800 Power Shelf