2 Product Description
2.1Product Description
This power Shelf consists of modular rectifiers, an Alarm Control Unit (ALU), and a DC distribution module. Up to four rectifiers and an alarm unit can be equipped on a shelf containing an integrated distribution module. The rectifiers can operate from a universal range of AC line voltages. The High Line (HL) operations are defined at an AC line input range of 165VAC~ 264VAC. The Low Line (LL) operations are defined at an AC line input range of 90
The system is controlled and monitored by the ALU. System level rectifier voltage settings, system status, and alarms are displayed on the ALU. The system float voltage, equalize voltage, and alarm thresholds are set from RMS. The ALU also provides automatic derating of the output power over the whole operating line voltages. Figure 1 shows different functional blocks of the system.
2.2Product Main Features
The Power Shelf has the following main features:
Front access for simple installation and maintenance High power density
Active Power Factor Correction (>. 99PFC) High efficiency
Temperature compensated float voltage control Alarm Control Unit
Low Voltage Battery Disconnect (LVBD) (System equipped with PDU) Remote Monitoring and control
2.3System Specifications
The system specifications are provided in the following sections.
2.3.1
(1) | AC Input: | 175VAC ~ 275VAC, 48Amps. Max |
(2) | System Capacity: | 120Amps. Max. |
(3) | Rectifier: |
(4)Control and Supervisory Unit Figure 1 shows a front view of shelf.