Delta MCS-1800 Settings Description Comment, AC High Voltage Alarm, AC Low Voltage Alarm, Site ID

Page 20

DELTA MCS-1800 3U Power Shelf

 

 

 

 

Installation,

Operations and

 

 

 

 

Maintenance Manual

 

 

 

 

 

 

 

 

Settings

 

Description

 

Comment

 

 

 

 

 

 

 

 

 

 

Steps

-

0.1VDC

 

 

 

 

 

AC High Voltage Alarm

 

 

 

 

 

 

 

Function

-

AC high voltage alarm threshold adjustment

 

 

 

 

Default

-

264V

 

 

 

 

 

Recovery

-

261V

 

 

 

 

 

Steps

-

1V

 

 

 

 

 

AC Low Voltage Alarm

 

 

 

 

 

 

 

Function

-

AC Low voltage alarm threshold adjustment

 

 

 

 

Default

-

176V

 

 

 

 

 

Recovery

-

179V

 

 

 

 

 

Steps

-

1V

 

 

 

 

 

Temperature Alarm

 

 

 

 

 

 

 

Function

-

Battery Temperature alarm

 

 

 

 

Default

-

104(40)

 

 

 

 

 

Steps

-

1

 

 

 

 

 

Site ID

 

 

 

 

 

 

 

Function

-

Set identification number for this site

 

 

 

 

Setting

-

4 digits and number range is 0-9

 

 

 

 

Floating / Equalize charging

 

 

 

 

 

 

 

voltage

 

 

 

 

 

 

 

Function

-

Float / Equalize charging voltage

 

 

 

 

Default

-

Float

 

 

 

 

 

 

-

54.3VDC (-48V System)

 

 

 

 

 

-

27.2VDC (+24V System)

 

 

 

 

 

-

EQUALIZE

 

 

 

 

 

 

-

56.4VDC (-48V System)

 

 

 

 

 

-

28.2VDC (+24V System)

 

 

 

 

Steps

-

0.1V

 

 

 

 

 

LVDS Trip Voltage

 

 

 

 

 

 

 

Function

-

Sets LVDS trip voltage

 

 

 

 

Default

-

42VDC (-48V System)

 

 

 

 

 

-

22VDC (+24V System)

 

 

 

 

Recovery

-

When one rectifier work normally and not in the

 

 

 

 

 

 

CL Mode

 

 

 

 

 

Steps

-

0.1V

 

 

 

 

 

Compensation On/Off

 

 

 

 

 

 

 

Function

-

Enable / Disable Temperature Compensation

 

 

 

 

 

 

feature

 

 

 

 

 

Setting

-

ON/OFF

 

 

 

 

 

Default

-

On

 

 

 

 

 

Compensation Volt. Range

 

 

 

 

 

 

 

Function

-

To set Temperature Compensation Voltage

 

 

 

 

Default

-

-1.3VDC~+1.3VDC

(-48V System)

 

 

 

 

 

-

-0.7VDC~+0.7VDC

(+24V System)

 

 

 

 

Steps

-

0.1V

 

 

 

 

 

Equalize Duration Time

 

 

 

 

 

 

 

Function

-

To set the duration of equalizes charging after

 

 

 

 

 

 

AC recovery. This setting is active when battery

 

 

 

 

 

 

deeply discharge resulting from AC fail.

 

 

 

 

Default

-

1-10 hours

 

 

 

 

 

Steps

-

1 hour

 

 

 

 

 

Mains Recovery Charging

-

When mains recovery to avoid the charging

 

 

 

 

Current Limited

 

current too large, CSU will limit the charging

 

 

 

 

 

 

current.

 

 

 

 

 

 

- [ (IL+ Max. Cap.) / Parameter] / available SMR

 

 

 

4-5

Image 20
Contents Delta MCS-1800 Power Shelf Delta MCS 1800 3U Power Shelf Table of Contents System Start -Up Procedure System Alarms and TroubleshootingMaintenance Acronyms and AbbreviationsUsing This Manual GeneralProduct Description Product Main FeaturesSystem Specifications Specification Value Environmental DataElectrical Data InputStatus/Alarm Indicators OutputMechanical Data Dimension Value Power Supply Unit PSU SpecificationsDescription ElectricalProtection Condition ResponseEnvironmental AdjustmentsAdjustment Description Operation and Adjustment System Alarm PSU Block DiagramCurrent Limit Setting PSU Operating PrincipleAlarm Control Unit Input CharacteristicsCharacteristic Value Input Voltage Range OutputSettings Description IndicatorsVoltage/Current Relay OutputALU Alarm Signal Descriptions PhysicalAlarm Control Unit Block Diagram Settings and ControlSettings Description Comment AC High Voltage AlarmAC Low Voltage Alarm Temperature AlarmTemperature Shut Down Control Settings Description Comment Remote SMR On/OffHvsd Recovery Floating / Equalize controlLow Voltage Battery Disconnect System equipped with PDU Battery Connections System equipped with PDUDC Distribution DC CablingInstallation AC High Voltage Aux. Relay output wiring Temperature and Alarm ConnectionsSignal I/P connector System Start-Up Procedure System Alarms and Troubleshooting AC Fail Voltage Alarm DescriptionHigh Voltage Shutdown Alarm High Voltage Alarm DescriptionFuse/Circuit Breaker Fail Alarm System equipped with PDU Low Voltage AlarmLow Voltage Disconnect Alarm System equipped with PDU Alarm Unit Fail Rectifier Fail AlarmRemoving and Replacing a Rectifier Unit MaintenanceCleaning and Maintenance Acronyms and Abbreviations Cispr10-2 10-3 Attachment ES 48/120-JAAxx、ES 24/200-JAAxx -48V/+24VPower Shelf PDU Delta MCS 1800 3U Power Shelf Alarm Relay Output 4ES 48/120-JAAxx Shelf Wiring MCS 1800 Series Shelf 5ES 24/200-JAAxx Shelf Wiring Diagram ES 48/90-JBAxx -48V Power Shelf With PDU ES 48/90-JBAxx DC Output Lug Distribution Delta MCS 1800 3U Power Shelf 台達電子工業股份有限公司 交換式電源供應器 ES 48/90-JBAxx Battery and Load Breaker Distribution ES 48/90-JBAxx Shelf Wiring MCS 1800 Series Shelf ES 48/90-JFAxx -48V Power Shelf With PDU ES 48/90-JFAxx Alarm Relay Output connectors ES 48/90-JFAxx AC Input Connector ES 48/90-JFAxx Battery Temperature ES 48/90-JFAxx DC Output Lug Distribution ES 48/90-JFAxx Shelf Wiring MCS 1800 Series Shelf Alarm Control Unit SMR RFA Power Supply Unit Eeprom SMR Block Diagram TEL -3-4526107P/N MCS-1800 Power Shelf