Delta MCS-1800 manual Protection, Condition Response

Page 12

DELTA MCS-1800 3U Power Sh elf

Installation, Operations and

Maintenance Manual

3.2.1.2 Output

Table 7 displays the rectifier output specifications.

Table 7 Rectifier Output Specifications

Specification

Value

 

 

 

40 to 60VDC [factory preset at –54.3VDC, 30Amps (HL) /

DC Output Voltage

15Amps (LL)] –48V Version

20 to 30VDC [factory preset at 27.2VDC, 50Amps (HL) /

 

 

25Amps (LL)] +24V Version

 

 

Output Power

1800W Maximum (-48V Version)

1500W Maximum (+24V Version)

 

 

 

Regulation:

 

Load

<1% (Load 0 to 100%)

Line

<0.1%

Current Limit

110% Max. of Rated Output Current

 

 

Noise:

 

Audio Band

<2mV

Wide Band

<20 mVrms (10 KHz to 100 MHz)

Acoustic

<55 dBA @ 1M

Current Sharing

<5% of Rated Output Current

 

 

Dynamic Response

10% to 90% Load Change Overshoot ≤5% Rated Output

Voltage Recovery Time <1 ms to ≤1% Rated Output Voltage

 

 

 

Protection

Fuse

 

 

3.2.1.3 Protection

Table 8 displays the protection specifications.

Table 8 Protection Specifications

Condition

Response

High Output Voltage (Exceeds

Automatic Shutdown and Latch

Preset Value)

 

Over Current/Output Short

Automatic Shutdown and Recovery

 

 

Over Temperature

Automatic Shutdown and Recovery

 

 

Brownout

No Damage

 

 

AC Input Voltage High

Automatic Shutdown and Recovery

 

 

AC Input Voltage Low

Automatic Shutdown and Recovery

 

 

3-2

Image 12
Contents Delta MCS-1800 Power Shelf Delta MCS 1800 3U Power Shelf Table of Contents System Start -Up Procedure System Alarms and TroubleshootingMaintenance Acronyms and AbbreviationsUsing This Manual GeneralProduct Main Features System SpecificationsProduct Description Specification Value Environmental DataElectrical Data InputStatus/Alarm Indicators OutputMechanical Data Dimension Value Power Supply Unit PSU SpecificationsDescription ElectricalProtection Condition ResponseAdjustments Adjustment DescriptionEnvironmental Operation and Adjustment System Alarm PSU Block DiagramCurrent Limit Setting PSU Operating PrincipleAlarm Control Unit Input CharacteristicsCharacteristic Value Input Voltage Range OutputSettings Description IndicatorsVoltage/Current Relay OutputALU Alarm Signal Descriptions PhysicalAlarm Control Unit Block Diagram Settings and ControlSettings Description Comment AC High Voltage AlarmAC Low Voltage Alarm Temperature AlarmTemperature Shut Down Control Settings Description Comment Remote SMR On/OffHvsd Recovery Floating / Equalize controlLow Voltage Battery Disconnect System equipped with PDU Battery Connections System equipped with PDUDC Distribution DC CablingInstallation Temperature and Alarm Connections Signal I/P connectorAC High Voltage Aux. Relay output wiring System Start-Up Procedure System Alarms and Troubleshooting AC Fail Voltage Alarm DescriptionHigh Voltage Shutdown Alarm High Voltage Alarm DescriptionLow Voltage Alarm Low Voltage Disconnect Alarm System equipped with PDUFuse/Circuit Breaker Fail Alarm System equipped with PDU Alarm Unit Fail Rectifier Fail AlarmMaintenance Cleaning and MaintenanceRemoving and Replacing a Rectifier Unit Acronyms and Abbreviations Cispr10-2 10-3 Attachment ES 48/120-JAAxx、ES 24/200-JAAxx -48V/+24VPower Shelf PDU Delta MCS 1800 3U Power Shelf Alarm Relay Output 4ES 48/120-JAAxx Shelf Wiring MCS 1800 Series Shelf 5ES 24/200-JAAxx Shelf Wiring Diagram ES 48/90-JBAxx -48V Power Shelf With PDU ES 48/90-JBAxx DC Output Lug Distribution Delta MCS 1800 3U Power Shelf 台達電子工業股份有限公司 交換式電源供應器 ES 48/90-JBAxx Battery and Load Breaker Distribution ES 48/90-JBAxx Shelf Wiring MCS 1800 Series Shelf ES 48/90-JFAxx -48V Power Shelf With PDU ES 48/90-JFAxx Alarm Relay Output connectors ES 48/90-JFAxx AC Input Connector ES 48/90-JFAxx Battery Temperature ES 48/90-JFAxx DC Output Lug Distribution ES 48/90-JFAxx Shelf Wiring MCS 1800 Series Shelf Alarm Control Unit SMR RFA Power Supply Unit Eeprom SMR Block Diagram TEL -3-4526107P/N MCS-1800 Power Shelf