®
Pre-installation wiring notes
The wiring for the Tracker system will have been completed prior to Tracker installation. All Tracker wiring conforms to the following guidelines:
•The Tracker controller receives 24 Vac from a dedicated power circuit. If not, the Tracker controller may malfunction.
•Each UCM receives 24 Vac from a dedicated power source. If not, the UCM may malfunction.
•Input wires and ac power wires are run in separate conduits or wire bundles. If not, the Tracker controller may malfunction due to induced electrical noise.
•Comm5 cable and ac power wires are run in separate conduits or wire bundles. If not, the Tracker controller may malfunction due to induced electrical noise.
•UCM communication cables do not run near lighting ballasts or other transformers. If they do, the UCM may malfunction due to induced electrical noise.
| 69 |