®

Chapter 3 Termination board wiring

UCM wiring configurations

The Tracker UCM Comm5 communication-link wiring must be installed in a daisy-chain configuration (Figure 15 on page 32 and Figure 16 on page 33).

Figure 15. Daisy-chain configuration for UCM communication-link wiring (preferred configuration)

Tracker

Controller

Trane UCM

Trane UCM

Trane UCM

Figure Note:

Maximum wire length for daisy-chained wiring is 4593 ft (1400 m).

32

BMTK-SVN01D-EN

Page 40
Image 40
Trane BMTK-SVN01D-EN, Building Automation System manual UCM wiring configurations, Figure Note