Chapter 3 Termination board wiring

Figure 18. Termination resistor placement with a Tracker controller in the middle of the link

 

 

 

 

 

 

 

 

 

 

Tracker

 

 

 

 

 

 

 

 

 

 

termination boardTB1

 

 

 

 

 

 

 

 

 

 

1

 

Legend

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

=

Twisted pair, shielded wire

=

Shield termination

 

3

 

 

per Trane specifications

=

 

 

 

 

 

 

=

Shield ground

 

Figure note

 

 

4

 

 

 

 

 

 

 

5

 

=

 

 

 

 

 

 

 

 

 

 

Termination resistor

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

(Last device on the link)

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

Comm5 device

 

 

Comm5 device

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

B

A

B

A

 

B

A

B

A

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

13

COMM

 

 

1

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

Splice

3

 

15

 

 

 

 

 

 

 

 

 

 

 

(Last device on the link)

 

 

 

 

 

 

 

 

Comm5 device

 

 

Comm5 device

 

 

 

 

 

B

A

B

A

 

B

A

B

A

 

 

 

 

1

 

 

 

 

 

 

 

 

 

2 Splice 3

Figure Notes:

1105 termination resistor

2Shield must be cut back and taped at last unit controller of each link.

3A continuous shield is required. At each unit controller, splice shield wire and tape back to prevent grounding.

36

BMTK-SVN01D-EN

Page 44
Image 44
Trane BMTK-SVN01D-EN, Building Automation System manual Tracker