BMTK-SVN01D-EN 65
®

Appendix A

Installation checklists

Required supplies

Table15 lis ts the supplies required for all Tracker installations.

Optional supplies

Table16 lis ts the supplies that may or may not be necessary, depending
on the Tracker installation.
Table 15. Required supplies checklist
;Wiring installation Item
24 Vac 18 AWG (1.02 mm2) wire recommended
24 Vac, 40 VA minimum transformer
Comm Communication wire (see Table7 on page 30
and Table8 on page 31 for specifications)
Table 16. Optional supplies checklist
;Inputs/output
wiring installation Item
Alarm relay wiring 18 AWG (1.02 mm2) wire and metal conduit
Priority shutdown
wiring and
Meter input
18—22 AWG (1.02 mm2—0.643 mm2) wire and
metal conduit
Thermistor wire 18—22 AWG (1.02 mm2—0.643 mm2) twisted
pair, shielded wire
Alarm relay power
supply
Power supply for alarm relay output (not to
exceed 24 Vac)
Alarm relay output
load
Load for alarm relay output (not to exceed
1 amp at 24 Vac)
Thermistor Outdoor air temperature sensor