Symptom/action troubleshooting

Table 14. Symptom/action troubleshooting (Continued)

Symptom

Action

 

 

Tracker controller displays

Verify if the electrical power has been off for more than 1 week (the actual time

the wrong date.

varies depending on storage temperature).

 

Verify that jumper pin J1 on the main module is in place.

 

Note: The controller default date (displayed when the controller is initially powered up or whenever

 

the super capacitor is unable to back up the controller time) is January 1, 2000.

 

 

Outdoor air temperature is

Measure the resistance of the outdoor air temperature thermistor (preferably at

not reading correctly.

the termination module). Check the measurement using Table 19 on page 71.

 

Inspect the location of the outdoor air temperature sensor. It must not be

 

mounted in the sunlight or near another source of radiant heat.

 

Note: The outdoor air temperature sensor can be used for this purpose only.

 

 

Ethernet link is not detected

Verify that the correct type of cable is used. When communicating over a network,

(on the Ethernet board, the

use a patch cable. When communicating to an Ethernet card on a lap top com-

left LED is off)

puter, use a crossover cable.

 

 