Wire the UCMs

Table 8. Specifications for Echelon Level 4 compliant cables

Specification

 

Value

 

 

 

dc resistance

 

18.0 /1000 feet at 20°C

(Maximum resistance of a single

 

 

copper conductor regardless of

 

 

whether or not it is solid or

 

 

stranded and regardless of

 

 

whether or not it is metal coated.)

 

 

 

 

 

dc resistance unbalance (maxi-

 

5%

mum)

 

 

 

 

 

Mutual capacitance of a pair

 

17 pF/foot

(maximum)

 

 

 

 

 

Pair-to-ground unbalance (maxi-

 

1000 pF/foot/1000 feet

mum)

 

 

 

 

 

Characteristic impedance

772 kHz

102 ± 15%

 

 

 

 

1.0 MHz

100 ± 15%

 

 

 

 

4.0 MHz

100 ± 15%

 

 

 

 

8.0 MHz

100 ± 15%

 

 

 

 

10.0 MHz

100 ± 15%

 

 

 

 

16.0 MHz

100 ± 15%

 

 

 

 

20.0 MHz

100 ± 15%

 

 

 

Attenuation (maximum dB/1000

772 kHz

4.5 dB/1000 feet at 20°C

feet at 20°C)

 

 

1.0 MHz

5.5 dB/1000 feet at 20°C

 

 

 

 

 

4.0 MHz

11.0 dB/1000 feet at 20°C

 

 

 

 

8.0 MHz

15.0 dB/1000 feet at 20°C

 

 

 

 

10.0 MHz

17.0 dB/1000 feet at 20°C

 

 

 

 

16.0 MHz

22.0 dB/1000 feet at 20°C

 

 

 

 

20.0 MHz

24.0 dB/1000 feet at 20°C

 

 

 

Worst-pair near-end crosstalk

772 kHz

58 dB

(minimum)

 

 

1.0 MHz

56 dB

(Values shown are for information

 

 

4.0 MHz

47 dB

only. The minimum NEXT cou-

 

 

pling loss for any pair combina-

8.0 MHz

42 dB

tion at room temperature is to be

 

 

10.0 MHz

41 dB

greater than the value determined

 

 

16.0 MHz

38 dB

using the formula NEXT

 

 

(FMHz)>NEXT(0.772)-15log10(FMHz/

20.0 MHz

36 dB

0.72) for all frequencies in the

 

 

range of 0.772 MHz–20 MHz for a

 

 

length of 1000 feet.)

 

 

 

 

 

dc resistance unbalance (maxi-

 

5%

mum)

 

 

 

 

 

BMTK-SVN01D-EN

31

Page 39
Image 39
Trane Building Automation System, BMTK-SVN01D-EN Specifications for Echelon Level 4 compliant cables, Specification Value