Trane BMTK-SVN01D-EN, Building Automation System manual Termination board wiring

Models: BMTK-SVN01D-EN Building Automation System

1 88
Download 88 pages 6.89 Kb
Page 32
Image 32

Chapter 3 Termination board wiring

Figure 14. Tracker field wiring connections

 

 

 

 

 

Line voltage

 

 

 

24 Vac

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOAD

Line voltage

Comm5 device

Comm5 device

A

 

A

Comm5

A

 

A

Comm5

 

 

 

 

 

 

 

 

 

link

 

 

 

link

B

 

B

B

 

B

 

 

 

 

 

 

 

 

 

 

 

 

Splice

®

1

24VAC

 

1

2

 

2

 

 

 

 

 

3

 

 

 

4

ALARM

RELAY

 

5

3

 

 

PRIORITY

SHUTDOWN

 

6

 

 

 

 

7

 

 

4

 

 

 

8

METER

INPUT

 

9

4

 

 

THERMISTOR

 

 

10

 

 

 

 

 

11

 

 

 

12

 

 

 

13

COMM

 

 

14

 

5

 

 

 

 

 

15

 

 

 

Legend

= Transformer

= Thermistor device per Trane specifications

= Termination resistor

=

Twisted pair, shielded wire

=

Earth ground

per Trane specifications

=

Shield termination

=

Shield ground

=

Contact points

=

Figure note

Figure Notes:

1All customer wiring must be in accordance with national, state, and local electrical codes.

2Trane recommends a dedicated transformer for 24 Vac power.

3Alarm relay circuit must not exceed 24 Vac, 1 A.

4Do not apply voltage to the priority shutdown inputs.

5Example of Comm5 communication link wiring. See product-specific literature for Comm5 wire connection details.

24

BMTK-SVN01D-EN

Page 32
Image 32
Trane BMTK-SVN01D-EN, Building Automation System manual Termination board wiring