Wire optional inputs and outputs

Wire the alarm relay

Wire the alarm relay to the termination board output.

CAUTION

Avoid Equipment Damage!

Use a dedicated power transformer for this output. Failure to do so will damage the main module, if the alarm output is powered from the Tracker 24 Vac input (TB-1 and TB-2) and the circuit shorts to ground.

1.Route input wires into the termination module through a conduit opening (Figure 12 on page 19) or the conduit box.

2.Connect the wires to the ALARM RELAY terminals on the termina- tion board (Figure 14 on page 24).

3.Connect the other end of the wires to the customer-supplied power supply and load.

Wire the priority shutdown device

Wire the priority shutdown device to the termination board input.

1.Route input wires into the termination module through a conduit opening (Figure 12 on page 19) or the conduit box.

2.Connect the wires to the PRIORITY SHUTDOWN terminals on the termination board (Figure 14 on page 24).

3.Connect the other end of the wires to the contacts of the priority shut- down device.