Symptom/action troubleshooting

Symptom/action troubleshooting

Table 14 provides a list of symptoms that indicate a problem in the Tracker system. For each symptom, the table provides one or more actions that you can perform in an attempt to resolve the problem.

Table 14. Symptom/action troubleshooting

Symptom

Action

 

 

Tracker controller does not

Verify that the telephone cable is connected to the PC modem port (Figure 24 on

communicate by modem.

page 48).

 

Verify that the phone line is an analog line (not digital).

 

Perform the modem self-test procedure from the display module.

 

Note: The modem is an integral component of the main module and is not field replaceable.

 

Replacement of the modem requires replacement of the main module.

 

 

Tracker controller does not

Verify that the cable is connected to the PC direct connect port (Figure 24 on

communicate by EIA-232

page 48).

port.

Verify that the proper cable is used. (Refer to Table 10 on page 47.)

 

 

Verify that the PC workstation is using the Tracker controller software; other com-

 

munications software will not work.

 

Look for activity on the PC RX LED (Figure 30 on page 56).

 

 

Tracker controller did not

When the controller is initially powered up, it automatically discovers all communi-

discover UCMs when ini-

cating UCMs of the proper type and installs them into its database. The discovery

tially started.

process takes several minutes, depending on how many UCMs are installed on the

 

communication link.

 

After the controller has built its database after the initial power up, the controller no

 

longer automatically discovers UCMs. If you want to initiate the discovery process,

 

you must do so manually. Initiate the discovery process when a new UCM is added

 

to the system or an existing UCM is replaced.

 

Verify proper wiring of the Comm5 communication link. (UCMs can be discov-

 

ered only if Comm5 communication has been established.)

 

Wait at least 5 minutes for the controller to discover the UCMs.

 

Note: You can press the service pin button on a UCM at any time to check if it is communicating

 

with the controller. Pressing the service pin button causes the UCM status LED to flash on and off

 

(known as “winking”), if the controller is communicating with that UCM.

 

 

Touch screen beeps when

Touch screen is out of calibration.

touched but does not

Perform the procedures for calibrating the touch screen in Tracker Building Auto-

progress to the next screen.

mation System Controller Operations guide (BMT-SVU01A-EN).

 

 

 

Touch-screen back light and

Perform the adjust brightness and contrast procedure from the display module.

contrast is out of adjust-

 

ment.

 

 

 

Tracker I/O status is wrong.

Verify electrical connection using the post-installation checklist (Table 18 on

 

page 70).

 

Verify I/O status as indicated on home display on the display module.

 

Display Tracker I/O status self test from display module.

 

 

BMTK-SVN01D-EN

59