Wire 24 Vac power

Wire 24 Vac power

After the termination module is mounted in the selected location, wire 24 Vac power to the termination board. Table 5 shows the specifications for power wiring.

Table 5. Power wiring specifications

24 Vac power

Description

Wire specifications

terminals

 

 

 

 

 

24 Vac

Power input

Trane recommends 18 AWG (1.02 mm2) wire and

TB1-1, TB1-2,

24 Vac nominal (19–30 Vac), 50/60 Hz,

metal conduit.

Earth ground TB1-3

1 phase 40 VA minimum, class 2

Low voltage (24 Vac) wire must comply with

 

transformer required

National Electrical Code (NEC) and federal, state,

 

 

and local electrical codes.

 

 

 

IMPORTANT

The 24 Vac wire conduit may not contain input/output or communica- tion wires. Failure to comply may cause the Tracker controller to mal- function due to electrical noise.

1.Route input wires into the termination module through the conduit box or any of the conduit access openings designated for input and communication wiring (Figure 12 on page 19).

2.Wire the two 24 Vac power input wires and the ground wire to the controller 24 VAC terminals (Figure 14 on page 24).

BMTK-SVN01D-EN

25

Page 33
Image 33
Trane Building Automation System, BMTK-SVN01D-EN manual Wire 24 Vac power, Power wiring specifications