Wire 24 Vac power
Wire 24 Vac power
After the termination module is mounted in the selected location, wire 24 Vac power to the termination board. Table 5 shows the specifications for power wiring.
Table 5. Power wiring specifications
24 Vac power | Description | Wire specifications | |
terminals | |||
|
| ||
|
|
| |
24 Vac | Power input | Trane recommends 18 AWG (1.02 mm2) wire and | |
24 Vac nominal | metal conduit. | ||
Earth ground | 1 phase 40 VA minimum, class 2 | Low voltage (24 Vac) wire must comply with | |
| transformer required | National Electrical Code (NEC) and federal, state, | |
|
| and local electrical codes. | |
|
|
|
IMPORTANT
The 24 Vac wire conduit may not contain input/output or communica- tion wires. Failure to comply may cause the Tracker controller to mal- function due to electrical noise.
1.Route input wires into the termination module through the conduit box or any of the conduit access openings designated for input and communication wiring (Figure 12 on page 19).
2.Wire the two 24 Vac power input wires and the ground wire to the controller 24 VAC terminals (Figure 14 on page 24).
| 25 |