3. INSTALLATION
3-1 Unpacking
zPlease read this user manual before installing the UPS.
z This UPS contains batteries which are potentially hazardous to user, even when the UPS is not connected to the utility power.
zBefore unpacking the UPS, check the packing box. If there are any visible damage, contact your dealer at once.
3-2 Before Installation
zAvoid exposing the UPS to direct sunlight or other heat source. The UPS
should be facing away from direct sunlight glare.
zChoose a
zEnsure the UPS surrounding area is clean and free from moisture.
zDo not put heavy objects on the cable or power cord.
3-3 Installation
Notice:
-AC output need a disconnect device such as a breaker which has to be provided by others.
-The wire length of output power cord connected to the output receptacle or pressure terminal should be less then 10 meters.
-The UPS provide with pressure terminal connector for field installed wiring, the terminal connector should be applied a 13.8
-The over current protection and short circuit protection for the AC output is provided by internal circuits of UPS and breaker.
-Concerning about the battery voltage, ambient temperature and other specifications of the UPS, please refer to the specification section of this manual.
-Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions.Keep unauthorized personnel away batteries.
-When replacing batteries, replace with the same type and number .
1.Connecting to utility power (Refer to fig 3-4)
{If input type is socket type
(1) Connect the IEC plug of power cord to the IEC 320 connector on the UPS.
13
SHEET 14 TO 15