Delta Electronics 3KVA, 700VA Unpacking, Before Installation, If input type is socket type

Page 14

3. INSTALLATION

3-1 Unpacking

zPlease read this user manual before installing the UPS.

z This UPS contains batteries which are potentially hazardous to user, even when the UPS is not connected to the utility power.

zBefore unpacking the UPS, check the packing box. If there are any visible damage, contact your dealer at once.

-This unit is to operate by any individuals with previous training. -This unit should be installed by service personnel.

3-2 Before Installation

zAvoid exposing the UPS to direct sunlight or other heat source. The UPS

should be facing away from direct sunlight glare.

zChoose a well-ventilated area to position your UPS to allow adequate dissipation of heat.

zEnsure the UPS surrounding area is clean and free from moisture.

zDo not put heavy objects on the cable or power cord.

3-3 Installation

Notice:

-AC output need a disconnect device such as a breaker which has to be provided by others.

-The wire length of output power cord connected to the output receptacle or pressure terminal should be less then 10 meters.

-The UPS provide with pressure terminal connector for field installed wiring, the terminal connector should be applied a 13.8 lb-in (1.554 N-m)of tightening torque.

-The over current protection and short circuit protection for the AC output is provided by internal circuits of UPS and breaker.

-Concerning about the battery voltage, ambient temperature and other specifications of the UPS, please refer to the specification section of this manual.

-Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions.Keep unauthorized personnel away batteries.

-When replacing batteries, replace with the same type and number .

1.Connecting to utility power (Refer to fig 3-4)

{If input type is socket type

(1) Connect the IEC plug of power cord to the IEC 320 connector on the UPS.

13

SHEET 14 TO 15

Image 14
Contents Sheet 1 to Important Safety Instructions UL safety instructionsOther safety notes Other safety instructions TUV safety instructionsFor installation EC conformity declaration Introduction Theory of operationPFC Power Factor Correction FeatureHigh power density Complete ProtectionConsiderate design Safety approvalsIntelligent design Green function designAnnotation and symbol Read before OperationOperation Panel Sheet 11 to Rear Panel Sheet 13 to Installation InstallationBefore Installation Unpacking If input type is terminal type UPSCharging the battery Connecting the battery bankConnecting the RS-232/Dry contact Sheet 18 to Turning on the UPS Cold start when utility is not presentOperation Turning OFF the UPSUPS self-test Silence functionSheet 21 to Storing the message into Eeprom UPS internal faultDerating power Programmable output OptionalMaintenance Placement Troubleshooting Problem Possible Cause SolutionFault Message Communication Interface RS-232Dry Contact Sheet 29 to Technical specifications Sheet 31 to END