Delta Electronics 700VA, 3KVA manual Communication Interface, RS-232

Page 27

8. COMMUNICATION INTERFACE

The UPS provides RS-232and Dry contact protocols in one D-sub 9 connector. Using proper UPS management software and cable, the UPS can be managed over LAN/intranet/internet environment. The pin assignment of the D-sub 9 connector is defined as follows:

ASSIGNMENT DESCRIPTION

PIN

 

RS-232

Dry Contact

1

Low battery(Open collector)

2

UPS TxD(typical RS-232 level)

3

UPS RxD(typical RS-232 level)

Remote shutdown(5~12V)

4

Reserved for PNP

5

GND

GND

6

Reserved for PNP

Reserved

7

Reserved for PNP

Reserved

8

Utility Fail(Open collector)

9

6

7

8

 

9

1

2

3

4

5

Open Collector

G N D

Fig 8-1 Pin Assignment

Fig 8-2 Open Collector Circuit

Maximum voltage and current on pin 1,8 is 30VDC, 10mA.

8-1 RS-232

Pin2

: PC receives line RS-232data from UPS.

Pin3

: PC transmits line RS-232data to UPS.

Pin5

: Signal ground.

Pin4,6,7

: Reversed for plug and play function.

26

SHEET 27 TO 28

Image 27
Contents Sheet 1 to UL safety instructions Important Safety InstructionsOther safety notes TUV safety instructions For installationOther safety instructions EC conformity declaration Theory of operation IntroductionComplete Protection FeatureHigh power density PFC Power Factor CorrectionGreen function design Safety approvalsIntelligent design Considerate designRead before Operation Annotation and symbolOperation Panel Sheet 11 to Rear Panel Sheet 13 to Unpacking InstallationBefore Installation InstallationUPS  If input type is terminal typeConnecting the battery bank Charging the batteryConnecting the RS-232/Dry contact Sheet 18 to Turning OFF the UPS Cold start when utility is not presentOperation Turning on the UPSSilence function UPS self-testSheet 21 to Programmable output Optional UPS internal faultDerating power Storing the message into EepromMaintenance Placement Problem Possible Cause Solution TroubleshootingFault Message RS-232 Communication InterfaceDry Contact Sheet 29 to Technical specifications Sheet 31 to END