Delta Electronics 700VA, 3KVA manual  If input type is terminal type, Ups

Page 15

(2)Plug the other end of the power cord into a two-pole, three-wire, grounding receptacle only. Avoid using extension cords and adapter plug.

{ If input type is terminal type

(1)Be sure to utilize UL1015#12 AWG WIRE for GES302N11XX model and UL1015#10 AWG WIRE for GES202N11XX model for power connection.

(2)Connect one end of L,N,G strings to those of the terminal block and the other end

to those of the switch box (L-L, N-N, G-G).

{Avoid using extension cords and adapter plug from UPS.

{Turn on the input breaker (if the breaker can be turned on) on the rear panel of

UPS.

{After that, the fan (in rear panel) will run and all LEDs will light for about 2-3 sec. Meanwhile the CPU inside the UPS setups the initial parameters. User also can check whether all LEDs are normal or not. The UPS is set in “STANDBY mode” initially, after a ‘bee’ is heard, the load LED lights on and the line LED shows AC utility status. Shown as fig 3-1.

Fig 3-1 Stand-By Mode

2. Checking the site wiring fault LED (If the function is available)

{After the UPS is plugged in , check the site wiring fault LED ( fault LED in “STANDBY mode”). If the UPS is plugged into an improper wired AC power outlet, this LED flashes. Shown as fig 3-2.

Fig 3-2 Site Fault

{The detection of site wiring fault includes missing ground, hot-neutral polarity reversal and overloaded neutral circuit. If it lights up, unplug the UPS and have the site wiring checked by qualified electrician.

14

SHEET 15 TO 16

Image 15
Contents Sheet 1 to UL safety instructions Important Safety InstructionsOther safety notes TUV safety instructions For installationOther safety instructions EC conformity declaration Theory of operation IntroductionComplete Protection FeatureHigh power density PFC Power Factor CorrectionGreen function design Safety approvalsIntelligent design Considerate designRead before Operation Annotation and symbolOperation Panel Sheet 11 to Rear Panel Sheet 13 to Unpacking InstallationBefore Installation InstallationUPS  If input type is terminal typeConnecting the battery bank Charging the batteryConnecting the RS-232/Dry contact Sheet 18 to Turning OFF the UPS Cold start when utility is not presentOperation Turning on the UPSSilence function UPS self-testSheet 21 to Programmable output Optional UPS internal faultDerating power Storing the message into EepromMaintenance Placement Problem Possible Cause Solution TroubleshootingFault Message RS-232 Communication InterfaceDry Contact Sheet 29 to Technical specifications Sheet 31 to END