2 INTRODUCTION

2-1 Theory of operation

The main topology of the UPS consists of bypass path, AC-DC converter, DC-AC inverter, battery charger, DC-DC converter, control circuit and detection circuit. Moreover, the intelligent power management software is also optional. The function and efficiency are superior to the traditional UPS.

Description of block diagram

B r e a k e r

A C I/P

E M I Filter

 

 

B Y P A S S

 

 

 

P F C C o n t r o l

L E D B o a r d

C o n t r o l B o a r d

 

 

Circuit

 

 

 

 

 

 

 

T o C o n t r o l B o a r d

 

 

 

 

 

To Auxiliary Power

 

 

 

R e l a y

 

 

 

 

B Y P A S S

 

 

 

 

 

R E L A Y

A C - D C D o u b l e

 

 

Half - bridge DC - AC Inverter

A C

O / P

Booster

 

 

 

 

 

 

 

Battery Bank

 

 

 

 

 

C h a r g e r

 

D C - D C C o n v e r t e r

 

 

 

 

 

T o C o n t r o l B o a r d

 

 

 

T o C o n t r o l B o a r d

 

 

 

 

 

 

 

Auxiliary

 

 

 

To External Battery Bank

P o w e r

 

 

 

Fig. 2.1 is the hardware block diagram of the UPS.

The UPS operation is described as below:

When the utility power is applied into the UPS, it was divided into two ways after going through the breaker and EMI filter. One way is connected to AC-DC converter which converts the utility AC power into a DC voltage which is called DC-BUS voltage then divide into two path. One path goes to charger which converts the DC-BUS voltage into a proper DC voltage to charge the UPS battery. The other path goes into DC-AC half bridge inverter. The other way works as a bypass path. The bypass relay near the output will choose either the bypass path or inverter output. In general, the UPS will internally do the self-diagnosis. If there is no problem, the bypass relay will choose the inverter output. This is so called ON-LINE mode”.

5

SHEET 6 TO 7

Image 6
Contents Sheet 1 to Important Safety Instructions UL safety instructionsOther safety notes TUV safety instructions For installationOther safety instructions EC conformity declaration Introduction Theory of operationPFC Power Factor Correction FeatureHigh power density Complete ProtectionConsiderate design Safety approvalsIntelligent design Green function designAnnotation and symbol Read before OperationOperation Panel Sheet 11 to Rear Panel Sheet 13 to Installation InstallationBefore Installation Unpacking If input type is terminal type UPSCharging the battery Connecting the battery bankConnecting the RS-232/Dry contact Sheet 18 to Turning on the UPS Cold start when utility is not presentOperation Turning OFF the UPSUPS self-test Silence functionSheet 21 to Storing the message into Eeprom UPS internal faultDerating power Programmable output OptionalMaintenance Placement Troubleshooting Problem Possible Cause SolutionFault Message Communication Interface RS-232Dry Contact Sheet 29 to Technical specifications Sheet 31 to END