Delta Electronics 700VA, 3KVA manual Feature, High power density, PFC Power Factor Correction

Page 7

In case the utility power fail, the AC-DC converter and charger will be off duty. The DC-DC converter works and converts the battery voltage into DC-BUS voltage. The DC-AC inverter converts the DC-BUS voltage into AC voltage. This is so called ON-BATTERY mode”.

The auxiliary power circuit supplies the designated power to all the control circuits.

Because the DC-AC inverter is always working, the DC-DC converter can work rapidly and replace the AC-DC converter while the utility power fails. Furthermore, the bypass relay continuously keeps in the position of inverter output to supply the regulated power for the load. There is no power failure to loading equipment.

2-2 Feature

The UPS, available in 700VA, 1KVA, 2KVA and 3KVA, is an advanced on-line UPS providing reliable and consistent sine-wave quality power to vital equipment. It supports personal computers, networks, servers, telecommunication equipment and a variety of other facilities. With its outstanding protection features, the unit keeps your applications safe and running smoothly at all times.

High power density

Other than traditional UPS adopting 0.7 output power factor, the UPS uses the latest technology and highest quality components giving output power factor up to 0.8. Compared to other UPS (1000VA/700W), these UPS series boosts a 12% more output power. This UPS with its compact size, generates higher power density thus giving convenience to the users. Moreover, through the use of advanced technology, the UPS efficiency increases to more than 87%. Compared with other traditional UPS with only 80 to 85% efficiency, this UPS produces greater electric power efficiency at less electric costs.

PFC (Power Factor Correction)

With this function, the investment in the capacity of circuit breakers can be reduced, specially it will be highly regarded as an important feature in critical load applications.

Complete Protection

On-line double conversion design, pure sinewave output and zero transfer time provide best protection. With a built-in surge, spike and line noise protection, the UPS prevents destructive hardware damage and extends system life. The EMI/RFI filtering design prevents electrical noise from affecting computer operation and data files. Besides, the UPS provides built-in Fax/Network cable (RJ11/RJ45) jacks protecting your hardware from surge, spikes and line-noise which travel along communication lines, therefore providing you a complete “back door” protection.

6

SHEET 7 TO 8

Image 7
Contents Sheet 1 to UL safety instructions Important Safety InstructionsOther safety notes For installation TUV safety instructionsOther safety instructions EC conformity declaration Theory of operation IntroductionComplete Protection FeatureHigh power density PFC Power Factor CorrectionGreen function design Safety approvalsIntelligent design Considerate designRead before Operation Annotation and symbolOperation Panel Sheet 11 to Rear Panel Sheet 13 to Unpacking InstallationBefore Installation InstallationUPS  If input type is terminal typeConnecting the battery bank Charging the batteryConnecting the RS-232/Dry contact Sheet 18 to Turning OFF the UPS Cold start when utility is not presentOperation Turning on the UPSSilence function UPS self-testSheet 21 to Programmable output Optional UPS internal faultDerating power Storing the message into EepromMaintenance Placement Problem Possible Cause Solution TroubleshootingFault Message RS-232 Communication InterfaceDry Contact Sheet 29 to Technical specifications Sheet 31 to END